RecordWell Data

Grandstay Residential Suites-whirlpool

5310 PRILL RD, Eau Claire, WI 54701 · Eau Claire County

19cited violations
5serious tier
5inspections

Establishment

Type
Pool / recreational water (Whirlpool)
Inspected by
Eau Claire City-County Health Department
License / ID
VRER-DF5LRL
Status
Permitted
Official record
Eau Claire City-County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
20254185

Inspections

  1. Jun 8, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      WALLS, CEILINGS, FLOORS

      Walls of whirlpool and floor of shower room in need of repair.

      Correction: Maintain the walls, ceilings and floors in a pool area in clean and sanitary condition.

      Code ATCP 76.33(1)(c) - FLOORS, WALLS, CEILINGS

  2. Nov 14, 2025 Re-inspection 2 · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Past file from Health Dept. available.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover. Covers need to be replaced in 2025 as docuements state they were replaced in 2018.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  3. Oct 28, 2025 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Past file from Health Dept. available.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover. Covers need to be replaced in 2025 as docuements state they were replaced in 2018.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  4. Oct 27, 2025 Routine · 5 critical, 10 non-critical
    • Not serious Non-critical

      LICENSE NOT POSTED

      The license is not posted for public view.

      Correction: Post the license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Not serious Non-critical

      ACTION PLAN DEVELOPED

      An action plan will be required for submitting logs for chemical readings.

      Correction: Prepare and submit the required Action Plan to the department or its agent. A plan will be required to submit logs weekly for three months If plans aren't submitted a reinspection fee will be charged for follow up.

      Code ATCP 76.07(4)(a) - ACTION PLAN DEVELOPED

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests. keep a log of interlock testing which is included in the monthly log.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level. No record of testing.

      Correction: Test pool water at least twice a week for the combined chlorine level. You must record testing of chemicals on your testing log.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity. No record of testing-you must record testing on the provided testing log.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Not serious Non-critical

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit. This must be documented on the daily reporting log.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

    • Not serious Non-critical

      OPERATOR RESPONSIBILITIES

      The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality There are no records being kept. Operator has been testing, but there is no record of it.

      Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.

      Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES

    • Not serious Non-critical

      TOILET ROOMS-CLEAN

      Toilet room not kept clean.

      Correction: Keep the toilet rooms clean.

      Code ATCP 76.33 (2)(c)1. TOILET ROOM CLEAN

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Past file from Health Dept. available.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover. Covers need to be replaced in 2025 as docuements state they were replaced in 2018.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is at 12.0 for chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Fresh water was added to lower the chlorine level to 10.0 ppm.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      MAXIMUM CHLORINE

      The maximum chlorine residual exceeds 10 ppm.

      Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A. Fresh water was added to whirlpool and the chlorine level is now at 10ppm.

      Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE

    • Serious Critical

      SHEPHERD'S CROOK PROVIDED

      The shepherd's crook is missing.

      Correction: Provide a shepherd's crook.

      Code ATCP 76.26(1)(b)1.a. -SHEPHERED'S CROOK PROVIDED

    • Serious Critical

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working or not present.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services. Close pool until a phone is in working order.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

    • Serious Critical

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The Responsible Supervisor or operator has not closed the pool due to a nonfunctional emergency phone.

      Correction: Close the pool in the event of a nonfunctional emergency phone.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

  5. Mar 26, 2025 Pre-inspection · 1 non-critical
    • Not serious Non-critical

      ACTION PLAN DEVELOPED

      The current floor has been damaged and repairs have been attempted, but the grates are no longer available. Currently a holder is placed in the floor drain and a mesh floor covering is placed over area where grates were removed.

      Correction: Prepare and submit the required Action Plan to the department or its agent. A plan must be developed to address continued effort to repair or replace area where grate was removed. Area is not in a high traffice area and does not cause standing water at this time. If this changes this will facilitate a more progressive plan for repair.

      Code ATCP 76.07(4)(a) - ACTION PLAN DEVELOPED

Source: Eau Claire City-County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.