Comfort Suites
1253 JOHN Q HAMMONS DR, Madison, WI 53717 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 45809-34144
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 12 | 0 |
| 2025 | 1 | 0 | 0 |
| 2023 | 2 | 11 | 0 |
| 2022 | 2 | 11 | 0 |
| 2021 | 1 | 0 | 0 |
| 2020 | 1 | 0 | 0 |
| 2019 | 1 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2015 | 2 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
Apr 8, 2026 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf) - Not Corrected
The operator is not following a combined chlorine plan. The combined chlorine in the whirlpool is 1.6 ppm, testing is not being completed at least 2 times per week, and records are not maintained for fresh water added or for dates and times for breakpoint chlorination, and any complaints of eye or respiratory irritation.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
-
Mar 24, 2026 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
08d - RECIRCULATION RATE - WHIRLPOOL (Pf)
The whirlpool has a maximum turnover rate of greater than 30 minutes.
Correction: Adjust or repair the equipment so the turnover rate does not exceed 30 minutes.
Code ATCP 76.11(4)(c)
-
Not serious
Action taken:
10b - BACKWASH - SAND FILTER (Pf)
Backwash procedures are not conspicuously posted in the filter area.
Correction: Post pool backwash procedures in a conspicuous place in the filter area and backwash the sand filter in accordance manufacturer's instructions.
Code ATCP 76.11(6)(a)
-
Not serious
Action taken:
11b - CHEMICAL - STORAGE (P)(Pf)
Doors to chemical storage area is not marked to indicate entry is for authorized personnel only.
Correction: Mark doors to chemical storage area for authorized personnel only.
Code ATCP 76.12(2)
-
Not serious
Action taken:
11e - SDS AVAILABILITY (Pf)
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken: Water replenished during i
Corrected on site
16a - pH (P)
The pH is at or above 8.0.
Correction: Maintain the pH between 7.2 and 7.8.
Code ATCP 76.14(5)(c)
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf)
The operator is not following a combined chlorine plan. The combined chlorine in the whirlpool is 1.6 ppm, testing is not being completed at least 2 times per week, and records are not maintained for fresh water added or for dates and times for breakpoint chlorination, and any complaints of eye or respiratory irritation.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE (Pf)
The water testing frequency for combined chlorine and alkalinity are not in compliance with ATCP 76.18(2).
Correction: Perform water testing in accordance with ATCP 76.18(2). Test combined chlorine in whirlpool once per day and test alkalinity in whirlpool once per week.
Code ATCP 76.18(2)
-
Not serious
Action taken:
22a - THERMOMETER (Pf)
There is no functional or visible thermometer installed on the pool water return line.
Correction: Install a working thermometer on the pool water return line.
Code ATCP 76.19(4)(a)
-
Not serious
Action taken:
26p - EMERGENCY NUMBERS AND ADDRESS (Pf)
Emergency phone connects to front desk. Desk staff could not explain pool emergency procedure during inspection.
Correction: Train staff to promptly answer the call (2 rings) and to contact 911 immediately for emergency. Post the emergency numbers and facility address at the front desk.
Code ATCP 76.26(2)(d)
-
Not serious
Action taken:
26s - BLANKETS MISSING (Pf)
2 conventional or emergency blankets are not available in the pool area. One emergency blanket available by the first aid kit.
Correction: Provide 2 conventional or emergency blankets in the pool area.
Code ATCP 76.27(1)(3)
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms inside the pool equipment room and in the indoor pool area.
Code ATCP 76.33(4)(d)
-
Not serious
Action taken:
-
Jun 12, 2025 Re-Inspection · No Reinspection Required
No violations cited.
-
Dec 15, 2023 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
08d - RECIRCULATION RATE - WHIRLPOOL - Not Corrected
The whirlpool has a maximum turnover rate of greater than 30 minutes.
Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 30 minutes.
Code ATCP 76.11(4)(d)
-
Not serious
Action taken:
13c - DISINFECTANT FEEDER - NOT ELECTRICALLY CONNECTED - Not Corrected
The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.
Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken:
28d - MONTHLY REPORTS AVAILABLE - Not Corrected
Pump curve is not available for review.
Correction: Keep records available for review.
Code ATCP 76.32(3)
-
Not serious
Other
34e - VGBA COVERS - Not Corrected
Documentation provided shows main drain cover is expired as of 1/5/2020. Covers appear secure and intact.
Correction: Replace main drain covers. Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Dec 15, 2023 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
08d - RECIRCULATION RATE - WHIRLPOOL
The whirlpool has a maximum turnover rate of greater than 30 minutes.
Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 30 minutes.
Code ATCP 76.11(4)(d)
-
Not serious
Action taken:
13c - DISINFECTANT FEEDER - NOT ELECTRICALLY CONNECTED
The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.
Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken: Pool closed.
14a - CHLORINE TOO LOW
The chlorine residual is 0ppm at the time of the inspection.
Correction: Close the pool and raise the chlorine residual to 3-10ppm. Call inspector to schedule a reopening inspection.
Code ATCP 76.14(4)(a)
-
Not serious
Action taken: Pool closed.
14f - NO DISINFECTANT FEEDER
The pool is not being automatically and continually disinfected via a disinfectant feeder.
Correction: The pool must be closed and a disinfectant feeder, approved by the department of commerce, must be installed before the facility can re-open.
Code ATCP 76.14(1)
-
Not serious
Any of the following conditions or situa
Corrected on site
28a - CLOSING CRITERIA
The pool was not closed under the following conditions: Chlorine residual is 0ppm and a non-operational disinfectant feeder.
Correction: Ensure that the closing criteria are adhered to under the listed below.
Code ATCP 76.30
-
Not serious
Action taken:
28d - MONTHLY REPORTS AVAILABLE
Pump curve is not available for review.
Correction: Keep records available for review.
Code ATCP 76.32(3)
-
Not serious
Other
34e - VGBA COVERS
Documentation provided shows main drain cover is expired as of 1/5/2020. Covers appear secure and intact.
Correction: Replace main drain covers. Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Nov 28, 2022 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET - Not Corrected
A spare strainer basket for the skimmers is not located on site.
Correction: Provide a spare basket or screen.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken:
09a - FLOW METER - Not Corrected
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
11e - SDS AVAILABILITY - Not Corrected
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken:
16a - pH - Not Corrected
The pH is over 8.0ppm.
Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.
Code ATCP 76.14(4)(c)
-
Not serious
Other
34e - VGBA COVERS - Not Corrected
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Nov 17, 2022 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET
A spare strainer basket for the skimmers is not located on site.
Correction: Provide a spare basket or screen.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken:
09a - FLOW METER
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
11e - SDS AVAILABILITY
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken:
14c - CHLORINE TOO HIGH
The chlorine residual exceeded 10 ppm.
Correction: The pool must be closed and may not reopen until the chlorine residual comes into an acceptable range. Call inspector to notify of the Cl level.
Code ATCP 76.14(4)(f)
-
Not serious
Action taken:
16a - pH
The pH is over 8.0ppm.
Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.
Code ATCP 76.14(4)(c)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Sep 8, 2021 Routine Inspection · No Reinspection Required
No violations cited.
-
Mar 17, 2020 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 24, 2019 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 20, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
May 17, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Sep 11, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 6, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Sep 16, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Sep 12, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Nov 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.