Village Of Kohler

260 SCHOOL ST, Kohler, WI 53044 · Sheboygan County

22cited violations
3serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Sheboygan County Health & Human Services
License / ID
BSAW-889J3P
Status
Permitted
Phone
(920) 459-2423
Official record
Sheboygan County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026160
20251101
2024152
2023110

Inspections

  1. Jul 16, 2026 Routine · 6 non-critical, 3 repeat
    • Not serious Non-critical

      SKIMMERS MAINTAINED CLEAN

      Skimmers baskets require cleaning.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The pressure gauge on sand filter #1 is not in operating condition.

      Correction: Adjust or repair the pressure gauge.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential (ORP/HRR) is 495 mV.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      ELECTRONIC MONITORING MAINTENANCE

      The electronic monitoring device has not been periodically monitored for proper functioning. The oxidation/reduction potential of the water shall be maintained between 650 - 900 mV.

      Correction: Periodically monitor the electronic monitoring device to determine if it is functioning correctly, and maintain and test as appropriate. Improper functioning of electronic monitoring devices requires increased manual testing.

      Code ATCP 76.18(3)(b) - ELECTRONIC MONITORING DEVICE MAINTAINED

    • Not serious Non-critical Repeat

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises.

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

  2. Jul 29, 2025 Routine · 1 critical, 9 non-critical, 3 repeat
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers weirs are missing at two skimmer openings serving the wading pool.

      Correction: Repair or replace weirs on the skimmer openings to provide effective skimming of the wading pool basin as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The filter pressure gauges for the wading pool are not providing a reading in pounds per square inch.

      Correction: Adjust or repair the pressure gauges.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential (high resolution redox) is 417 mV.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical

      GATES AND DOORS-SELF-CLOSING

      The large black gate for the wading pool was noted ajar during the inspection and the gate or door does not self-close.

      Correction: Provide a self-closing gate or door. Maintain the pool areas secure and inaccessible to prevent unauthorized access to the pool area.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

  3. Jul 29, 2024 Routine · 2 critical, 3 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The filter pressure gauges (psi) were not available for a reading during the inspection. The gauges appear to be recently removed from their operational location.

      Correction: Provide functional filter pressure gauges.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential HRR is 580 mV.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      POOL RULES POSTED

      The pool rules are not posted in the outdoor wading pool area.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Serious Critical

      TELEPHONE-LOCATION

      The telephone or other approved communication technology is not within 25 feet of pool area.

      Correction: Provide a telephone or other telecommunication technology device that is within 25 feet of pool area.

      Code ATCP 76.26(2)(c) - TELEPHONE, LOCATION

    • Serious Critical

      FIRST AID KIT-PROVIDED IN POOL AREA

      The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is.

      Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.

      Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT

  4. Aug 16, 2023 Routine · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      WATER TESTING FREQUENCY - POOLS

      The water testing frequency for COMBINED CHLORINE is not in compliance with ATCP 76.18(1).

      Correction: Perform water testing in accordance with ATCP 76.18(1). Combined Chlorine is required to be tested 2x per week.

      Code ATCP 76.18(1)

Source: Sheboygan County Health & Human Services. History last read Oct 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.