Sports Core-outdoor Whirlpool

100 WILLOW CREEK DR, Kohler, WI 53044 · Sheboygan County

17cited violations
8serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
Sheboygan County Health & Human Services
License / ID
HSAT-7QXRLG
Status
Permitted
Phone
(920) 457-4441
Official record
Sheboygan County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20253147
2024131

Inspections

  1. Dec 23, 2025 Follow Up · 1 critical, 1 repeat
    • Serious Critical Repeat

      GATES AND DOORS MECHANISM 54 INCHES

      A self-closing latching and lockable mechanism is not present at least 54 inches from the bottom of the gate or door.

      Correction: Install a self-closing latching and lockable mechanism at least 54 inches from the bottom of the gate or door in order to prevent small children or other personnel requiring supervision from accessing this area.

      Code ATCP 76.34(2)(b) - SELF-CLOSING, LATCHING MECHANISM

  2. Dec 5, 2025 Routine · 3 critical, 4 non-critical, 1 repeat
    • Not serious Non-critical

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed.

      Correction: Provide interlock between the power to the recirculation system and power to the chemical feeder(s).

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 30 ppm.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Corrected on site

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") was noted at 540 mV at the onset of the inspection.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV. Once the chemical controller was powered on, the ORP was noted at 733 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      FIRST AID KIT ITEMS

      The first aid kit is present but missing items.

      Correction: Replace the missing items in the first aid kit.

      Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS

    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 3.0 for a non-stabilized public whirlpool using sodium hypochlorite and was noted at <0.2 ppm free chlorine at the onset of the inspection.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. After the chemical controller was powered on, the free chlorine residual was noted at 6.8 ppm during the inspection.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Corrected on site

      PH

      The pH was 8.0 at the beginning of the whirlpool inspection.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better. After the controller was powered on - the pH was noted at 7.4

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical Repeat

      GATES AND DOORS MECHANISM 54 INCHES

      A self-closing latching and lockable mechanism is not present at least 54 inches from the bottom of the gate or door.

      Correction: Install a self-closing latching and lockable mechanism at least 54 inches from the bottom of the gate or door in order to prevent small children or other personnel requiring supervision from accessing this area.

      Code ATCP 76.34(2)(b) - SELF-CLOSING, LATCHING MECHANISM

  3. Feb 17, 2025 Routine · 3 critical, 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter weight for the outdoor whirlpool is clogged w/ sand and is not providing a valid reading.

      Correction: Adjust or repair the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed a written combined chlorine management plan for the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in the whirlpool and the pool water is not tested daily for the combined chlorine level.

      Correction: Test pool water daily for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Serious Critical Repeat

      FIRST AID KIT-PROVIDED IN POOL AREA

      The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is.

      Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.

      Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT

    • Serious Critical

      GATES AND DOORS MECHANISM 54 INCHES

      A self-closing latching and lockable mechanism is not present at least 54 inches from the bottom of the gate or door. The door leading to the pool/locker room areas is not latching nor lockable.

      Correction: Install a self-closing latching and lockable mechanism at least 54 inches from the bottom of the gate or door.

      Code ATCP 76.34(2)(b) - SELF-CLOSING, LATCHING MECHANISM

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the drain cover specifications.

      Correction: Obtain information that describes make, model and gpm rating for the drain covers per the Virginia Graeme Baker Act.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  4. May 9, 2024 Routine · 1 critical, 2 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter appears clogged with sand.

      Correction: Unclog the flowmeter to provide an accurate reading.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in a whirlpool and pool water is not tested at least daily for the combined chlorine level.

      Correction: Test pool water at least daily for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Serious Critical

      FIRST AID KIT-PROVIDED IN POOL AREA

      The first aid kit is missing from the pool area.

      Correction: Provide a first aid kit in the pool area.

      Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT

Source: Sheboygan County Health & Human Services. History last read Oct 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.