The Osthoff Resort- South Building - Outdoor Kidney Pool
101 OSTHOFF AVE, Elkhart Lake, WI 53020 · Sheboygan County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Sheboygan County Health & Human Services
- License / ID
- HSAT-7QWUAW
- Status
- Permitted
- Phone
- (920) 876-3366
- Official record
- Sheboygan County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 4 | 2 |
| 2025 | 1 | 3 | 0 |
| 2024 | 1 | 5 | 1 |
| 2023 | 1 | 2 | 0 |
Inspections
-
Jun 12, 2026 Routine · 2 critical, 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
Flow meter is not functioning. The bobber in the flow meter is lodged and not able to show the flow.
Correction: Repair or replace the flow meter in order to observe an accurate reading of the flow.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 220.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Serious
Critical
PH
The pH is 7.1.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
TELEPHONE ACCESSIBLE
Emergency phone is not working. A dial tone was not able to be observed.
Correction: Provide a working telephone or other technology capable of connecting with emergency services. Pool shall be closed until this can be obtained.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Not serious
Non-critical
Repeat
-
Jun 26, 2025 Routine · 3 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not functioning and is unable to measure the flow.
Correction: Adjust or repair the flowmeter so that it is functioning properly.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is 40 ppm.
Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is ~250 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
-
Jun 10, 2024 Routine · 1 critical, 4 non-critical
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Corrected on site
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
Facility address is not posted next to the emergency telephone. CORRECTED: Moving forward this facility will make the forward the main desk when someone picks up the phone. No address of facility near the phone is required due to the phone being directed straight to the receptionist.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
VGBA documents missing or unavailable during the inspection today: this includes the pump curve, when last installation occurred, and specs for main drain and equalizers.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room. CORRECTED: CO detecors obtained and proof provided during the exit interview 6/14/24.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
-
Jul 27, 2023 Routine · 2 non-critical, 1 repeat
-
Not serious
Non-critical
Corrected on site
CHLORINE TOO HIGH
The chlorine residual exceeded 10 ppm.
Correction: The pool must be closed and may not reopen until the chlorine residual comes into an acceptable range. The pool basin was partially dumped and re-filled over the course of 3-4 hours. The free chlorine was noted at 9.2 ppm and the pool was re-opened. Identify the root cause of the high level in order to prevent re-occurence.
Code ATCP 76.14(4)(f)
-
Not serious
Non-critical
Repeat
FIRST AID SUPPLIES MISSING
8" by 10" gauze pads and a resuscitation pocket face mask are missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit including two durable blankets.
Code [C] ATCP 76.27(1)
-
Not serious
Non-critical
Corrected on site
Source: Sheboygan County Health & Human Services. History last read Oct 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.