RecordWell Data

The Osthoff Resort- Main Building - Outdoor Pool

101 OSTHOFF AVE, Elkhart Lake, WI 53020 · Sheboygan County

14cited violations
5serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Sheboygan County Health & Human Services
License / ID
HSAT-7QWD8U
Status
Permitted
Phone
(920) 876-3366
Official record
Sheboygan County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026122
2025142
2024151
2023130

Inspections

  1. Jun 12, 2026 Routine · 2 critical
    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

    • Serious Critical

      GATES AND DOORS-SELF-CLOSING

      The gate or door does not self-close. The hinge is broken that closes the gate.

      Correction: Provide a self-closing gate or door.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

  2. May 29, 2025 Routine · 2 critical, 2 non-critical
    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 190 ppm.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      POSTING SIGNAGE-NO DIVING

      No-Diving signage is not present where it is required.

      Correction: Post signage indicating No-Diving.

      Code ATCP 76.29(1)(d) - NO DIVING

    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 0.8 for Chlorine

      Correction: CORRECTED ONSITE: It was discovered that a valve was shut off and not enough water was flowing through the eriosion pucks. This was adjusted and levels were back in range. Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Corrected on site

      FREE OF CHEMICAL, PHYSICAL, AND MICROBIAL SUBSTANCES

      Main drain was missing a screw from the drain on the east or right side.

      Correction: CORRECTED ONSITE: an employee swam down in the pool and replaced the missing screw. Close the pool until the water is free of chemical, physical, and microbial substances known to be, or suspected of being, capable of creating toxic reactions or skin or membrane irritations.

      Code ATCP 76.16 (1) - WATER FREE OF PHYSICAL, MICROBIAL

  3. Jun 10, 2024 Routine · 1 critical, 4 non-critical
    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Corrected on site

      TELEPHONE-EMERGENCY NUMBERS AND ADDRESS

      Emergency phone does not provide the location of the facility. CORRECTED: Moving forward this facility will make the forward the main desk when someone picks up the phone. No address of facility near the phone is required due to the phone being directed straight to the receptionist.

      Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.

      Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED

    • Not serious Non-critical

      EMERGENCY BLANKETS

      Two emergency blankets in good condition are not available in the pool area.

      Correction: Provide two emergency blankets in good condition in the pool area.

      Code ATCP 76.27(3) - EMERGENCY BLANKETS

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical Corrected on site

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room. CORRECTED: CO detecors obtained and proof provided during the exit interview 6/14/24.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

  4. Jul 27, 2023 Routine · 3 non-critical, 2 repeat
    • Not serious Non-critical

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration is over 50 ppm.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Not serious Non-critical Repeat

      SKIMMER BASKET OR WEIR MISSING

      The skimmer weir doors are missing on all skimmer openings.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

    • Not serious Non-critical Repeat

      FIRST AID SUPPLIES MISSING

      8" x 10" gauze pads are missing from the first aid kit.

      Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.

      Code [C] ATCP 76.27(1)

Source: Sheboygan County Health & Human Services. History last read Oct 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.