RecordWell Data

North Senior High School

2926 N 10TH ST, Sheboygan, WI 53083 · Sheboygan County

22cited violations
2serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Complex with Features)
Inspected by
Sheboygan County Health & Human Services
License / ID
HSAT-7QWKM9
Status
Permitted
Phone
(920) 459-3600
Official record
Sheboygan County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2025290
20242132

Inspections

  1. Dec 3, 2025 Routine · 4 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter weight appeared stuck or immobile and was not providing an accurate reading.

      Correction: Adjust the flowmeter so that it provides an accurate reading.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is ~ 30 ppm.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      WATER LEVEL-GUTTERS CONTINUOUS WATER SUPPLY

      The water level in this gutter pool is too low and is not providing effective skimming.

      Correction: Maintain the water level in the pool so that there is a continuous water supply over the gutter.

      Code ATCP 76.19(3)(b) - GUTTERS CONTINUOUS WATER SUPPLY

    • Not serious Non-critical

      LOCKERS-GOOD REPAIR

      Light shields covering the flourescent lights in the boys locker room were noted damaged and are in poor repair. Shower nozzles were noted leaking.

      Correction: Maintain locker room facilities in good repair.

      Code ATCP 76.33 (2)(d)2. - LOCKERS GOOD REPAIR

  2. Feb 10, 2025 Routine · 5 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      LIFEGUARD, ATTENDANT STAFFING PLAN REQUIRED

      No lifeguard and attendant staffing plan is available.

      Correction: Prepare and maintain a lifeguard staffing plan.

      Code ATCP 76.22(1)(a) - LIFEGUARD, ATTENDANT STAFFING PLAN REQUIR

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-PUMP CURVE

      The manufacturer’s pump performance curve diagram was not permanently maintained on premises:

      Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.

      Code ATCP 76.32(3)(a)3. - PUMP CURVE

  3. May 8, 2024 Follow Up · 1 critical, 5 non-critical, 2 repeat
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. The basin's turnover rate exceeds 9 hours.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level and document on testing logs. The R-0003 combined chlorine reagent is used when determining combined chlorine residuals. Follow the instructions provided on the Taylor test kit. Replace the R-0003 regeant as it is expired.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      THERMOMETER RETURN LINE

      An accurate thermometer is not located in the pool water return line.

      Correction: Provide an accurate thermometer in the pool water return line.

      Code ATCP 76.19(4)(a)1 - THERMOMETER

    • Not serious Non-critical

      LIFEGUARD, ATTENDANT STAFFING PLAN REQUIRED

      No lifeguard and attendant staffing plan was available or provided by the operator.

      Correction: Prepare and maintain a lifeguard staffing plan. A template can be provided to assist you in developing the plan.

      Code ATCP 76.22(1)(a) - LIFEGUARD, ATTENDANT STAFFING PLAN REQUIR

    • Serious Critical

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock. A checklist can be provided to assist you in developing the plan.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

  4. Feb 16, 2024 Routine · 1 critical, 6 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition and is clogged.

      Correction: Adjust or repair the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 10-20 ppm.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      THERMOMETER RETURN LINE

      An accurate thermometer is not located in the pool water return line.

      Correction: Provide an accurate thermometer in the pool water return line.

      Code ATCP 76.19(4)(a)1 - THERMOMETER

    • Not serious Non-critical

      RESCUE EQUIPMENT ACCESSIBLE

      The rescue equipment is not in a conspicuous place and readily accessible. The ring buoys were noted stored behind a locked door outside of the immediate pool area.

      Correction: Maintain rescue equipment in a conspicuous and accessible location.

      Code ATCP 76.26(1)(a)2. - RESCUE EQPT ACCESSIBLE

    • Not serious Non-critical

      WALLS, CEILINGS, FLOORS

      The pool deck permiter (lower recessed troughs w/ drains) contained body hair & debris and have not been maintained in clean and sanitary condition.

      Correction: Maintain the walls, ceilings and floors in a pool area in clean and sanitary condition.

      Code ATCP 76.33(1)(c) - FLOORS, WALLS, CEILINGS

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

Source: Sheboygan County Health & Human Services. History last read Oct 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.