RecordWell Data

Siebkens Resort - Swimming Pool

284 S LAKE ST, Elkhart Lake, WI 53020 · Sheboygan County

26cited violations
3serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Sheboygan County Health & Human Services
License / ID
BSTR-B87LHQ
Status
Permitted
Phone
(713) 775-5149
Official record
Sheboygan County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026171
2025290
2024160
2023142

Inspections

  1. Jun 1, 2026 Routine · 1 critical, 6 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      SKIMMER POOL RECIRCULATION FLOW

      At the time of the inspection, the skimmers were not pulling water past the skimmer baskets.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 50.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      REAGENTS REPLACED

      At the time of the inspection, R-0871 test kit reagent was not replaced as recommended by the manufacturer. Reagent expired 10/2025.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical

      INTERLOCK LOG-INFORMATION

      Electrical interlock was observed onsite with maintenance staff, however, the monthly testing log is missing.

      Correction: Maintain a log that is documented with the date, results, and the name of the person performing the interlock test.

      Code ATCP 76.13 (1)(c)4.a - INTERLOCK LOG, INFORMATION REQUIRED

  2. Jun 19, 2025 Follow Up · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      POOL RULES SIGNAGE-NO ANIMALS

      Pool rules still missing rule: Do not bring animals into the pool area.

      Correction: Include pool rule on sign: Do not bring animals into the pool area.

      Code ATCP 76.29(1)(b)1.e. - NO ANIMALS

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is still not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      POOL DECK-GOOD REPAIR

      At the time of the inspection the pool deck area was observed with cracked/chipped concrete on the deck surface.

      Correction: Maintain pool deck area in good repair to prevent injuries and facilitate cleaning.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

  3. Jun 9, 2025 Routine · 6 non-critical, 4 repeat
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests was unable to be located during the inspection.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool. Recommend utilizing the combine chlorine template form provided by our office.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      POOL RULES SIGNAGE-NO ANIMALS

      Pool rules missing rule: Do not bring animals into the pool area.

      Correction: Include pool rule on sign: Do not bring animals into the pool area.

      Code ATCP 76.29(1)(b)1.e. - NO ANIMALS

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises. Obtain a pump curve and information that describes make, model, and gpm rating for the drain cover(s).

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Not serious Non-critical Repeat

      POOL DECK-GOOD REPAIR

      At the time of the inspection the pool deck area was observed with cracked/chipped concrete on the deck surface.

      Correction: Maintain pool deck area in good repair to prevent injuries and facilitate cleaning.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

  4. Jun 4, 2024 Routine · 6 non-critical
    • Not serious Non-critical

      SKIMMER POOL RECIRCULATION FLOW

      At the time of the inspection the water flow over the skimmer basket was extremely low. It appeared very little or no circulation was occuring through the skimmers.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical Corrected on site

      COMBINED CHLORINE PLAN PRESENT

      The operator does not have a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool. Template plan was provided with the annual inspection report.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not available at the time of the inspection.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Not serious Non-critical

      POOL DECK-GOOD REPAIR

      At the time of the inspection the pool deck was not maintained in good repair and was observed to be cracking/chipping at various location around the pool.

      Correction: Maintain pool deck area in good repair to facilitate cleaning and prevent unintentional patron injuries.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

  5. Jul 25, 2023 Routine · 2 critical, 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter for the pool is not providing an accurate reading and appears to be improperly sized.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical

      BACKFLOW - HOSE BIBBS

      The hose bibb by the drinking fountain is not protected against backsiphonage.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code [A] ATCP 76.33(1)(d)

    • Serious Critical Repeat

      RECIRCULATION RATE NOT MET - POOLS

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Serious Critical

      DISINFECTANT FEEDER NOT ELECTRICALLY CONNECTED

      The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.

      Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.

      Code ATCP 76.13(1)(c)

Source: Sheboygan County Health & Human Services. History last read Oct 18, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.