Siebkens Resort - Swimming Pool
284 S LAKE ST, Elkhart Lake, WI 53020 · Sheboygan County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Sheboygan County Health & Human Services
- License / ID
- BSTR-B87LHQ
- Status
- Permitted
- Phone
- (713) 775-5149
- Official record
- Sheboygan County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 7 | 1 |
| 2025 | 2 | 9 | 0 |
| 2024 | 1 | 6 | 0 |
| 2023 | 1 | 4 | 2 |
Inspections
-
Jun 1, 2026 Routine · 1 critical, 6 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
SKIMMER POOL RECIRCULATION FLOW
At the time of the inspection, the skimmers were not pulling water past the skimmer baskets.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is 50.
Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
REAGENTS REPLACED
At the time of the inspection, R-0871 test kit reagent was not replaced as recommended by the manufacturer. Reagent expired 10/2025.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
CYANURIC TEST
Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.
Correction: Test water for the cyanuric acid at least once a week.
Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
INTERLOCK LOG-INFORMATION
Electrical interlock was observed onsite with maintenance staff, however, the monthly testing log is missing.
Correction: Maintain a log that is documented with the date, results, and the name of the person performing the interlock test.
Code ATCP 76.13 (1)(c)4.a - INTERLOCK LOG, INFORMATION REQUIRED
-
Not serious
Non-critical
Repeat
-
Jun 19, 2025 Follow Up · 3 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
POOL RULES SIGNAGE-NO ANIMALS
Pool rules still missing rule: Do not bring animals into the pool area.
Correction: Include pool rule on sign: Do not bring animals into the pool area.
Code ATCP 76.29(1)(b)1.e. - NO ANIMALS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is still not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
POOL DECK-GOOD REPAIR
At the time of the inspection the pool deck area was observed with cracked/chipped concrete on the deck surface.
Correction: Maintain pool deck area in good repair to prevent injuries and facilitate cleaning.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Not serious
Non-critical
Repeat
-
Jun 9, 2025 Routine · 6 non-critical, 4 repeat
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests was unable to be located during the inspection.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. Recommend utilizing the combine chlorine template form provided by our office.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
POOL RULES SIGNAGE-NO ANIMALS
Pool rules missing rule: Do not bring animals into the pool area.
Correction: Include pool rule on sign: Do not bring animals into the pool area.
Code ATCP 76.29(1)(b)1.e. - NO ANIMALS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises. Obtain a pump curve and information that describes make, model, and gpm rating for the drain cover(s).
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
POOL DECK-GOOD REPAIR
At the time of the inspection the pool deck area was observed with cracked/chipped concrete on the deck surface.
Correction: Maintain pool deck area in good repair to prevent injuries and facilitate cleaning.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Not serious
Non-critical
-
Jun 4, 2024 Routine · 6 non-critical
-
Not serious
Non-critical
SKIMMER POOL RECIRCULATION FLOW
At the time of the inspection the water flow over the skimmer basket was extremely low. It appeared very little or no circulation was occuring through the skimmers.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
Corrected on site
COMBINED CHLORINE PLAN PRESENT
The operator does not have a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. Template plan was provided with the annual inspection report.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not available at the time of the inspection.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
POOL DECK-GOOD REPAIR
At the time of the inspection the pool deck was not maintained in good repair and was observed to be cracking/chipping at various location around the pool.
Correction: Maintain pool deck area in good repair to facilitate cleaning and prevent unintentional patron injuries.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Not serious
Non-critical
-
Jul 25, 2023 Routine · 2 critical, 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flowmeter for the pool is not providing an accurate reading and appears to be improperly sized.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
BACKFLOW - HOSE BIBBS
The hose bibb by the drinking fountain is not protected against backsiphonage.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.
Code [A] ATCP 76.33(1)(d)
-
Serious
Critical
Repeat
RECIRCULATION RATE NOT MET - POOLS
The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.
Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(a)
-
Serious
Critical
DISINFECTANT FEEDER NOT ELECTRICALLY CONNECTED
The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.
Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.
Code ATCP 76.13(1)(c)
-
Not serious
Non-critical
Repeat
Source: Sheboygan County Health & Human Services. History last read Oct 18, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.