RecordWell Data

Camp Evelyn

W6598 CAMP EVELYN RD, Plymouth, WI 53073 · Sheboygan County

8cited violations
4serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Moderate with Features)
Inspected by
Sheboygan County Health & Human Services
License / ID
HSAT-7QX3DC
Status
Permitted
Phone
(920) 946-7108 ext. Abby Weber
Official record
Sheboygan County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
2025122
2024132
2023120

Inspections

  1. Jun 10, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

  2. Jun 5, 2025 Routine · 2 critical, 1 repeat
    • Serious Critical Repeat

      PH

      The pH is 7.0.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical Corrected on site

      WATER CLARITY

      Main drain was observed missing a screw.

      Correction: CORRECTED ONSITE: screw was installed Maintain all maindrains with proper screws per manufactuers requirements

      Code ATCP 76.16 (2) - CLARITY

  3. Jun 28, 2024 Routine · 2 critical, 1 non-critical
    • Not serious Non-critical Corrected on site

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 40 ppm. CORRECTED: Adjusted and measured <30 ppm

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Serious Critical Corrected on site

      PH

      The pH is 7.1. CORRECTED: Adjusted and resampled at 7.4

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  4. Jun 8, 2023 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      RECORD RETENTION

      VGBA anti-entrapment main drain cover records are not available for review.

      Correction: Keep records in accordance with ATCP 76.32(3) and federal law.

      Code [A] ATCP 76.32(3)

    • Not serious Non-critical Repeat

      FIRST AID SUPPLIES MISSING

      Items are missing from the first aid kit near the pool.

      Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit and store near the pool area.

      Code [C] ATCP 76.27(1)

Source: Sheboygan County Health & Human Services. History last read Oct 18, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.