Kohler Memorial Bldg
260 SCHOOL ST, Kohler, WI 53044 · Sheboygan County
Establishment
- Type
- Pool / recreational water (Pool - Moderate with Features)
- Inspected by
- Sheboygan County Health & Human Services
- License / ID
- HSAT-7QWUQF
- Status
- Permitted
- Phone
- (920) 459-3873
- Official record
- Sheboygan County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 1 | 7 | 0 |
| 2024 | 2 | 6 | 3 |
| 2023 | 1 | 1 | 0 |
Inspections
-
Jul 16, 2026 Routine · 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises. The copy of the pool code was from 2007 and is outdated.
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
-
Jul 29, 2025 Routine · 7 non-critical, 2 repeat
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
The water potential (high resolution redox) is 528 mV.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
Repeat
LIFEGUARD, ATTENDANT STAFFING PLAN REQUIRED
No lifeguard and attendant staffing plan is available.
Correction: Prepare and maintain a lifeguard staffing plan.
Code ATCP 76.22(1)(a) - LIFEGUARD, ATTENDANT STAFFING PLAN REQUIR
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
-
Jul 29, 2024 Routine · 3 critical, 2 non-critical
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential HRR is 626 mV.
Correction: Maintain water potential between 650−900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
LIFEGUARD, ATTENDANT STAFFING PLAN REQUIRED
No lifeguard and attendant staffing plan is available during the inspection.
Correction: Prepare and maintain a lifeguard staffing plan.
Code ATCP 76.22(1)(a) - LIFEGUARD, ATTENDANT STAFFING PLAN REQUIR
-
Serious
Critical
LIFEGUARD RESCUE TUBE
The lifeguard does not have a rescue tube with a harness.
Correction: Provide a rescue tube with a harness for each lifeguard on duty.
Code ATCP 76.22(3)(a)2 - RESCUE TUBE
-
Serious
Critical
LIFEGUARD NO DISTRACTING DUTIES
The lifeguard was performing distracting duties. A lifeguard was noted picking up items on the pool deck while patrons were swimming.
Correction: Do not assign duties to lifeguards that would distract from lifeguarding responsibilities. Lifeguards should remain focused on patron safety and shall not be distracted during their duty.
Code ATCP 76.22(3)(b) - LIFEGUARD NO DISTRACTING DUTIES
-
Serious
Critical
RING BOUY
A ring buoy does not have an attached rope of sufficient length.
Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.
Code ATCP 76.26(1)(b)2.a - RING BOUY
-
Not serious
Non-critical
-
May 15, 2024 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
WATER TESTING FREQUENCY - POOLS
The water testing frequency for [chemical] is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Combined Chlorine must be tested 2x per week.
Code ATCP 76.18(1)
-
Not serious
Non-critical
Repeat
-
Aug 16, 2023 Routine · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
WATER TESTING FREQUENCY - POOLS
The water testing frequency for [chemical] is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Combined Chlorine must be tested 2x per week.
Code ATCP 76.18(1)
-
Not serious
Non-critical
Repeat
Source: Sheboygan County Health & Human Services. History last read Oct 18, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.