Camp Brosius-hotel
8089 CTY RD P, Elkhart Lake, WI 53020 · Sheboygan County
Establishment
- Type
- Lodging (Hotel and Motel - 31 - 99 Rooms)
- Inspected by
- Sheboygan County Health & Human Services
- License / ID
- HSAT-7QWQ8E
- Status
- Permitted
- Phone
- (920) 876-2848
- Official record
- Sheboygan County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 4 | 12 | 5 |
| 2025 | 1 | 1 | 0 |
| 2024 | 1 | 0 | 0 |
| 2023 | 1 | 1 | 0 |
Inspections
-
Jul 7, 2026 Admin Follow Up · 1 non-critical
-
Not serious
Priority Foundation
Guard height >= 36" - elevated surfaces
The guard height on the stair case in the Inn is at 31 inches.
Correction: Modify the guard height to be equal to or greater than 36 inches on the top of the stairs on the third level
Code ATCP 72.18(2)(b)6.a.
-
Not serious
Priority Foundation
-
Jun 18, 2026 Admin Follow Up · 2 non-critical, 2 repeat
-
Not serious
Priority Foundation
Repeat
Guard height >= 36" - elevated surfaces
The guard height on the stair case in the Inn is at 31 inches.
Correction: Modify the guard height to be equal to or greater than 36 inches on the top of the stairs on the third level
Code ATCP 72.18(2)(b)6.a.
-
Not serious
Priority Foundation
Repeat
Fire alarm systems - annual inspection and test - performed
The fire alarm system has not been inspected and tested annually by a fire alarm system service company
Correction: Contact a fire alarm system service company to inspect and test the fire alarm system.
Code ATCP 72.18(9)(a)3.
-
Not serious
Priority Foundation
Repeat
-
Jun 8, 2026 Admin Follow Up · 3 non-critical, 3 repeat
-
Serious
Critical
Repeat
Slip-resistant flooring in shower and bathtubs
The shower house for the rustic cabins is not provided with slip-resistant flooring or materials.
Correction: Slip-resistant flooring or materials shall be provided in all shower and bathtub basins.
Code ATCP 72.17(5)(f)
-
Not serious
Priority Foundation
Repeat
Guard height >= 36" - elevated surfaces
The guard height on the stair case in the Inn is at 31 inches.
Correction: Modify the guard height to be equal to or greater than 36 inches on the top of the stairs on the third level
Code ATCP 72.18(2)(b)6.a.
-
Not serious
Priority Foundation
Repeat
Fire alarm systems - annual inspection and test - performed
The fire alarm system has not been inspected and tested annually by a fire alarm system service company
Correction: Contact a fire alarm system service company to inspect and test the fire alarm system.
Code ATCP 72.18(9)(a)3.
-
Serious
Critical
Repeat
-
Jun 3, 2026 Routine · 6 non-critical
-
Serious
Critical
Slip-resistant flooring in shower and bathtubs
The shower house for the rustic cabins is not provided with slip-resistant flooring or materials.
Correction: Slip-resistant flooring or materials shall be provided in all shower and bathtub basins.
Code ATCP 72.17(5)(f)
-
Serious
Critical
Smoke alarms provided
Smoke alarms are not provided within Yurt
Correction: Provide smoke alarms within each individually keyed unit at the locations specified in rule.
Code ATCP 72.18(11)(a)
-
Serious
Critical
Carbon monoxide alarms provided
A carbon monoxide alarm is not provided anywhere in the Annex
Correction: Provide carbon monoxide alarms at the locations specified in rule.
Code ATCP 72.18(12)(a)
-
Serious
Critical
Corrected on site
Fire alarm systems - operational
The fire alarm system is nonoperational due to no power in the ANNEX. CORRECTED: Fire panel power was turned on and observed to be functional.
Correction: This is required to be functional before campers are staying in this unit
Code ATCP 72.18(9)(a)1.
-
Not serious
Priority Foundation
Guard height >= 36" - elevated surfaces
The guard height on the stair case in the Inn is at 31 inches.
Correction: Modify the guard height to be equal to or greater than 36 inches on the top of the stairs on the third level
Code ATCP 72.18(2)(b)6.a.
-
Not serious
Priority Foundation
Fire alarm systems - annual inspection and test - performed
The fire alarm system has not been inspected and tested annually by a fire alarm system service company
Correction: Contact a fire alarm system service company to inspect and test the fire alarm system.
Code ATCP 72.18(9)(a)3.
-
Serious
Critical
-
Jun 3, 2025 Routine · 1 non-critical
-
Not serious
Non-critical
Corrected on site
FIRE ALARM – WORKING ORDER
The fire alarm system was noted inoperative during the inspection today. The panel was off in the Annex building and in the Inn.
Correction: CORRECTED ONSITE: the breaker was turned on and new back up batteries were obtained immendately and switched out when onsite today. Repair the fire alarm system immediately. Occupancy may not exist without operational system. Referral made to the department of safety and professional services for follow-up.
Code [O] ATCP 72.14 (1)
-
Not serious
Non-critical
Corrected on site
-
Jun 25, 2024 Routine · No items found
No violations cited.
-
May 22, 2023 Routine · 1 non-critical
-
Not serious
Non-critical
EXIT LIGHTING - PROVIDED
The battery back-up on the exit lighting is not in working order in the second story hotel hallway.
Correction: Provide lighting for exit lights. Exit signs must be illuminated at all times. Be sure to check other exit lights in the camp for back-up battery functionality
Code [R] ATCP 72.14 (1)
-
Not serious
Non-critical
Source: Sheboygan County Health & Human Services. History last read Oct 18, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.