RecordWell Data

River Hill Inn & Suites

808 DOMINION DR, Hudson, WI 54016 · St. Croix County

20cited violations
4serious tier
7inspections

Establishment

Type
Pool / recreational water (Whirlpool)
Inspected by
St. Croix County Public Health
License / ID
TSPN-8PGQPL
Status
Permitted
Phone
(715) 386-8800
Official record
St. Croix County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026251
20253123
2024110
2023120

Inspections

  1. May 1, 2026 Re-inspection · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. Missing grout between basin tiles.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical Repeat

      POOL DECK-INDOOR-DISINFECTED

      Indoor pool deck area not disinfected at least weekly with disinfecting agents according to the manufacturer’s directions. Owner disinfects every month or two.

      Correction: Disinfect indoor pool deck area at least weekly with disinfecting agents according to the manufacturer’s directions. Note: It is recommended to avoid the use of an ammonia-based disinfectant as this can contribute to an increased level of chloramines in the pool water.

      Code ATCP 76.33(1)(b)2. - INDOOR DECK DISINFECTED

  2. Apr 28, 2026 Routine · 1 critical, 2 non-critical
    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. Missing grout between basin tiles.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical

      POOL DECK-INDOOR-DISINFECTED

      Indoor pool deck area not disinfected at least weekly with disinfecting agents according to the manufacturer’s directions. Owner disinfects every month or two.

      Correction: Disinfect indoor pool deck area at least weekly with disinfecting agents according to the manufacturer’s directions. Note: It is recommended to avoid the use of an ammonia-based disinfectant as this can contribute to an increased level of chloramines in the pool water.

      Code ATCP 76.33(1)(b)2. - INDOOR DECK DISINFECTED

    • Serious Critical

      MAXIMUM CHLORINE

      The maximum chlorine residual exceeds 10 ppm. Free chlorine residual is at 12 ppm.

      Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A. (3ppm to 10 ppm)

      Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE

  3. Jul 28, 2025 Follow Up · No items found

    No violations cited.

  4. Jun 18, 2025 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The pool equipment is not properly maintained. Underwater light is not operational.

      Correction: Maintain the pool equipment Repair or replace underwater light so it is operational.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

  5. Apr 30, 2025 Routine · 3 critical, 8 non-critical, 1 repeat
    • Not serious Non-critical

      LABEL, CONSPICUOUS

      Chemical container is not conspicuously labeled. Acid tank missing label for Sunnyside muratic acid.

      Correction: Provide a conspicuous, easily visible and read label on the chemical container.

      Code ATCP 76.12 (1)(a)

    • Not serious Non-critical

      SAFETY DATA SHEET

      A safety data sheet was not available for Sunnyside muratic acid.

      Correction: Maintain a safety data sheet for each chemical on site.

      Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS

    • Not serious Non-critical

      INTERLOCK LOG-MADE AVAILABLE

      Log of electronic interlock testing not made available to the department or its agent upon request.

      Correction: Make interlock test log available to the department or its agent upon request.

      Code ATCP 76.13 (1)(c)4.b - INTERLOCK LOG AVAILABLE

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      TEST KIT APPROVED

      Unapproved Taylor 2005C test kit in use.

      Correction: Provide a department approved test kit.

      Code ATCP 76.17 (1) - DEPARTMENT-APPROVED

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The pool equipment is not properly maintained. Underwater light is not operational.

      Correction: Maintain the pool equipment Repair or replace underwater light so it is operational.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. No pump curve, drain log, or affidavit available.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant for liquid chlorine sanitizer level is 3 PPM. Free Chlorine tested at 1.6 PPM. Taylor test kit has an accuracy of +/- 20%. Free chlorine is between 1.28 - 1.92 PPM.

      Correction: Close the pool until liquid chlorine disinfectant level is in compliance with ATCP 76.14 Table A (3-10 PPM).

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      CLOSING CRITERIA-GATE OR DOOR NOT EQUIPPED TO SELF-CLOSE, LATCH, LOCKABLE

      The Responsible Supervisor or operator has not closed the pool in the event that a door is not equipped with a self-closing and latching mechanism, except when staffed by a lifeguard or attendant.

      Correction: Close the pool in the event of a pool gate or door that is not equipped with a self-closing and latching mechanism, except when staffed by a lifeguard or attendant.

      Code ATCP 76.30 (1)(i) - GATE OR DOOR NOT EQUIPPED TO SELF-CLOSE

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

  6. May 9, 2024 Routine · 1 non-critical
    • Not serious Non-critical

      TEST KIT APPROVED

      Test kit not aproved. Sanjay took pictures of what chemical test kit to get.

      Correction: Get approved chemicals for testing pool water

      Code ATCP 76.17 (1) - DEPARTMENT-APPROVED

  7. May 10, 2023 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      TEST KIT NOT APPROVED

      The test kit used by the facility has not been approved by the department.

      Correction: Replace the test kit with one from the approved list.

      Code ATCP 76.17(1)

    • Not serious Non-critical

      SKIMMER BASKET OR WEIR MISSING

      The west side weir is missing.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

Source: St. Croix County Public Health. History last read Oct 18, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.