RecordWell Data

Best Western Plus

1200 GATEWAY BLVD, Hudson, WI 54016 · St. Croix County

34cited violations
5serious tier
7inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
St. Croix County Public Health
License / ID
PLAE-D8LQWC
Status
Permitted
Phone
(715) 386-6200
Official record
St. Croix County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20254203
20243142

Inspections

  1. Dec 19, 2025 Re-inspection · No items found

    No violations cited.

  2. Oct 7, 2025 Re-inspection · No items found

    No violations cited.

  3. Oct 3, 2025 Re-inspection · 1 critical, 8 non-critical, 9 repeat
    • Not serious Non-critical Repeat

      INLETS CHECKED AND ADJUSTED

      Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are not all adjusted in the same direction to provide a uniform distribution pattern.

      Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.

      Code ATCP 76.11(2)(c) - INLETS POSITIONED

    • Not serious Non-critical Repeat

      DOORS

      Doors to chemical storage areas not locked and marked to indicate entry is for authorized personnel only.

      Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.

      Code ATCP 76.12 (2)(i) - DOORS

    • Not serious Non-critical Repeat

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests cannot be found.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The combined chlorine plan is not available.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      OPERATING REPORTS-CHEMICAL TESTING

      Results for chemicla testing with an ORP meter are not available.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-PUMP CURVE

      The manufacturer’s pump performance curve diagram was not permanently maintained on premises:

      Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.

      Code ATCP 76.32(3)(a)3. - PUMP CURVE

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. VGBA log and affidavit not available.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical Repeat

      CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS

      Acids and chlorine are not seperated.

      Correction: Store oxidizers separately from acids. Organize acids and chlorines so they are stored seperate.

      Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS

  4. Sep 23, 2025 Routine · 2 critical, 9 non-critical
    • Not serious Non-critical

      SKIMMER POOL RECIRCULATION FLOW

      Both the skimmer and main drain valves are open at 100%.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      INLETS CHECKED AND ADJUSTED

      Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are not all adjusted in the same direction to provide a uniform distribution pattern.

      Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.

      Code ATCP 76.11(2)(c) - INLETS POSITIONED

    • Not serious Non-critical

      DOORS

      Doors to chemical storage areas not locked and marked to indicate entry is for authorized personnel only.

      Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.

      Code ATCP 76.12 (2)(i) - DOORS

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests cannot be found.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The combined chlorine plan is not available.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      OPERATING REPORTS-CHEMICAL TESTING

      Results for chemicla testing with an ORP meter are not available.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-PUMP CURVE

      The manufacturer’s pump performance curve diagram was not permanently maintained on premises:

      Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.

      Code ATCP 76.32(3)(a)3. - PUMP CURVE

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. VGBA log and affidavit not available.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical

      CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS

      Acids and chlorine are not seperated.

      Correction: Store oxidizers separately from acids. Organize acids and chlorines so they are stored seperate.

      Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS

    • Serious Critical

      PH

      The pH is at 8.0+.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  5. Nov 4, 2024 Re-inspection · No items found

    No violations cited.

  6. Oct 8, 2024 Re-inspection · 1 critical, 6 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Weir door missing

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flow meter is not being maintained in operating condition.

      Correction: Adjust or repair the flow meter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      PIPING LABELED, TAGGED OR CODED

      The piping is not labeled, tagged or color-coded.

      Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.

      Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED

    • Not serious Non-critical Repeat

      FILTERS MAINTAINED OPERABLE

      Filters shells and appurtenances are not being maintained in operable condition. plumbing is leaking.

      Correction: Maintain filter shells and appurtenances in operable condition.Repair leaks

      Code ATCP 76.11(6)(a) 2. - FILTER OPERABLE

    • Not serious Non-critical Repeat

      THERMOMETER CAN BE OBSERVED

      The thermometer not correct

      Correction: Locate the thermometer where it can be easily observed.

      Code ATCP 76.19(4)(a)2 - THERMOMETER CAN BE SEEN

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  7. Sep 3, 2024 Pre-inspection · 1 critical, 6 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Weir door missing

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flow meter is not being maintained in operating condition.

      Correction: Adjust or repair the flow meter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      PIPING LABELED, TAGGED OR CODED

      The piping is not labeled, tagged or color-coded.

      Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.

      Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED

    • Not serious Non-critical

      FILTERS MAINTAINED OPERABLE

      Filters shells and appurtenances are not being maintained in operable condition. plumbing is leaking.

      Correction: Maintain filter shells and appurtenances in operable condition.Repair leaks

      Code ATCP 76.11(6)(a) 2. - FILTER OPERABLE

    • Not serious Non-critical

      THERMOMETER CAN BE OBSERVED

      The thermometer not correct

      Correction: Locate the thermometer where it can be easily observed.

      Code ATCP 76.19(4)(a)2 - THERMOMETER CAN BE SEEN

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

Source: St. Croix County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.