Best Western Plus
1200 GATEWAY BLVD, Hudson, WI 54016 · St. Croix County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- St. Croix County Public Health
- License / ID
- PLAE-D8LQWC
- Status
- Permitted
- Phone
- (715) 386-6200
- Official record
- St. Croix County Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2025 | 4 | 20 | 3 |
| 2024 | 3 | 14 | 2 |
Inspections
-
Dec 19, 2025 Re-inspection · No items found
No violations cited.
-
Oct 7, 2025 Re-inspection · No items found
No violations cited.
-
Oct 3, 2025 Re-inspection · 1 critical, 8 non-critical, 9 repeat
-
Not serious
Non-critical
Repeat
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are not all adjusted in the same direction to provide a uniform distribution pattern.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
Repeat
DOORS
Doors to chemical storage areas not locked and marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
Repeat
INTERLOCK-LOG KEPT
A log of the monthly interlock tests cannot be found.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The combined chlorine plan is not available.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
Results for chemicla testing with an ORP meter are not available.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. VGBA log and affidavit not available.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Serious
Critical
Repeat
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Acids and chlorine are not seperated.
Correction: Store oxidizers separately from acids. Organize acids and chlorines so they are stored seperate.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Not serious
Non-critical
Repeat
-
Sep 23, 2025 Routine · 2 critical, 9 non-critical
-
Not serious
Non-critical
SKIMMER POOL RECIRCULATION FLOW
Both the skimmer and main drain valves are open at 100%.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are not all adjusted in the same direction to provide a uniform distribution pattern.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
DOORS
Doors to chemical storage areas not locked and marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests cannot be found.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The combined chlorine plan is not available.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
Results for chemicla testing with an ORP meter are not available.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. VGBA log and affidavit not available.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Serious
Critical
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Acids and chlorine are not seperated.
Correction: Store oxidizers separately from acids. Organize acids and chlorines so they are stored seperate.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
PH
The pH is at 8.0+.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Not serious
Non-critical
-
Nov 4, 2024 Re-inspection · No items found
No violations cited.
-
Oct 8, 2024 Re-inspection · 1 critical, 6 non-critical, 7 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Weir door missing
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
PIPING LABELED, TAGGED OR CODED
The piping is not labeled, tagged or color-coded.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
Repeat
FILTERS MAINTAINED OPERABLE
Filters shells and appurtenances are not being maintained in operable condition. plumbing is leaking.
Correction: Maintain filter shells and appurtenances in operable condition.Repair leaks
Code ATCP 76.11(6)(a) 2. - FILTER OPERABLE
-
Not serious
Non-critical
Repeat
THERMOMETER CAN BE OBSERVED
The thermometer not correct
Correction: Locate the thermometer where it can be easily observed.
Code ATCP 76.19(4)(a)2 - THERMOMETER CAN BE SEEN
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Sep 3, 2024 Pre-inspection · 1 critical, 6 non-critical
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Weir door missing
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
PIPING LABELED, TAGGED OR CODED
The piping is not labeled, tagged or color-coded.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
FILTERS MAINTAINED OPERABLE
Filters shells and appurtenances are not being maintained in operable condition. plumbing is leaking.
Correction: Maintain filter shells and appurtenances in operable condition.Repair leaks
Code ATCP 76.11(6)(a) 2. - FILTER OPERABLE
-
Not serious
Non-critical
THERMOMETER CAN BE OBSERVED
The thermometer not correct
Correction: Locate the thermometer where it can be easily observed.
Code ATCP 76.19(4)(a)2 - THERMOMETER CAN BE SEEN
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical