Best Western Plus
1200 GATEWAY BLVD, Hudson, WI 54016 · St. Croix County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- St. Croix County Public Health
- License / ID
- PLAE-D8LQSX
- Status
- Permitted
- Phone
- (715) 386-6200
- Official record
- St. Croix County Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2025 | 7 | 25 | 4 |
| 2024 | 3 | 14 | 0 |
Inspections
-
Dec 31, 2025 Re-inspection · No items found
No violations cited.
-
Dec 29, 2025 Re-inspection · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. During a reinspection on 12-18-25 it was observed that the pool orp meter was flashing and the acid tank was over flowing. Water was entering and overflowing the acid tank (for both pool & whirlpool) from the pickup tube hooked to the whirlpool peristaltic pump. 12-19-25: Whirlpool is closed until recirc pump is repaired. 12-29-25: Whirlpool is still closed until pool chemistry is within code. Leak at flowmeter needs repair. Whirlpool closed sign is in place.
Correction: Maintain the pool equipment. Repair the pool orp meter. Repair the water leak into the acid tank from the whirlpool pickup tubing. Verify all pool and whirlpool chemistry is correct.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
Repeat
-
Dec 19, 2025 Re-inspection · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. During a reinspection on 12-18-25 it was observed that the pool orp meter was flashing and the acid tank was over flowing. Water was entering and overflowing the acid tank (for both pool & whirlpool) from the pickup tube hooked to the whirlpool peristaltic pump. 12-19-25: Whirlpool is closed until recirc pump is repaired.
Correction: Maintain the pool equipment. Repair the pool orp meter. Repair the water leak into the acid tank from the whirlpool pickup tubing. Verify all pool and whirlpool chemistry is correct.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
Repeat
-
Dec 18, 2025 Re-inspection · No items found
No violations cited.
-
Oct 7, 2025 Re-inspection · 1 non-critical
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. Leak at flowmeter and backwash valve in maintenance room..
Correction: Maintain the pool equipment Repair leak at flowmeter and backwash valve.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
-
Oct 3, 2025 Re-inspection · 2 critical, 9 non-critical, 11 repeat
-
Not serious
Non-critical
Repeat
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are not adjusted for a uniform distribution pattern.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate is 1.86
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of under .5 hours for whirlpools.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
DOORS
Doors to chemical storage area not locked and marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine plan could not be found.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing of whirlpool with an ORP meter could not be found.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. The VGBA affidavit and log can not be found.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. Leak at flowmeter and backwash valve in maintenance room..
Correction: Maintain the pool equipment Repair leak at flowmeter and backwash valve.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
Repeat
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Chlorine is not stored separately from muratic acid. Organize and seperate chlorine from muratic acid.
Correction: Store oxidizers separately from acids.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
Repeat
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm and is at 17+ ppm. 10-3-25: The minimum chlorine residual is below 3 ppm and is at 1.6 ppm
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A. Free Chlorine should be between 3-10 ppm.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Not serious
Non-critical
Repeat
-
Sep 23, 2025 Routine · 2 critical, 9 non-critical
-
Not serious
Non-critical
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are not adjusted for a uniform distribution pattern.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate is 1.86
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of under .5 hours for whirlpools.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
DOORS
Doors to chemical storage area not locked and marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine plan could not be found.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing of whirlpool with an ORP meter could not be found.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. The VGBA affidavit and log can not be found.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. Leak at flowmeter and backwash valve in maintenance room..
Correction: Maintain the pool equipment Repair leak at flowmeter and backwash valve.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Chlorine is not stored separately from muratic acid. Organize and seperate chlorine from muratic acid.
Correction: Store oxidizers separately from acids.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm and is at 17+ ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A. Free Chlorine should be between 3-10 ppm.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Not serious
Non-critical
-
Nov 4, 2024 Re-inspection · No items found
No violations cited.
-
Oct 8, 2024 Re-inspection · 7 non-critical, 7 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Weir door is missing
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Needs to turnover ever 30 miniues so flow rate has to be 44.6 gpm. Flow meter curently reading 18 gpm. This gauge either is not working or flow rate needs to be increased.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
PIPING LABELED, TAGGED OR CODED
The piping is not labeled, tagged or color-coded.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
Repeat
FILTERS MAINTAINED OPERABLE
Plumbing is leaking in pool room
Correction: Repair plumbing leaks
Code ATCP 76.11(6)(a) 2. - FILTER OPERABLE
-
Not serious
Non-critical
Repeat
WHIRLPOOL, THERAPY POOL, EXERCISE POOL TEST ONE OTHER TIME DURING PEAK PATRON LOAD, PH AND SANITIZER; NO AUTOMATIC CONTROLLER
Whirlpool water not tested for pH and disinfectant at least two (of the total of 4) times during the day’s peak patron load. Record all testing on the daily log.
Correction: Test pool water for pH and disinfectant at least two (of the total of 4) times during the day’s peak patron load.
Code ATCP 76.18(2)(a)2.- WATER TESTED TOTAL OF 4 TIMES WHIRLPOOL,
-
Not serious
Non-critical
Repeat
THERMOMETER RETURN LINE
An accurate thermometer is not reaing corect temp
Correction: Provide an accurate thermometer in the pool water return line.
Code ATCP 76.19(4)(a)1 - THERMOMETER
-
Not serious
Non-critical
Repeat
ELECTRICAL GOOD REPAIR
Electrical equipment and lighting not maintained in good repair and in operating condition. Cover plate on eletrical outlet for the controller
Correction: Maintain electrical equipment and lighting in good repair and in operating condition.
Code ATCP 76.33(4)(c) - GOOD REPAIR
-
Not serious
Non-critical
Repeat
-
Sep 3, 2024 Pre-inspection · 7 non-critical
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Weir door is missing
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Needs to turnover ever 30 miniues so flow rate has to be 44.6 gpm. Flow meter curently reading 18 gpm. This gauge either is not working or flow rate needs to be increased.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
PIPING LABELED, TAGGED OR CODED
The piping is not labeled, tagged or color-coded.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
FILTERS MAINTAINED OPERABLE
Plumbing is leaking in pool room
Correction: Repair plumbing leaks
Code ATCP 76.11(6)(a) 2. - FILTER OPERABLE
-
Not serious
Non-critical
WHIRLPOOL, THERAPY POOL, EXERCISE POOL TEST ONE OTHER TIME DURING PEAK PATRON LOAD, PH AND SANITIZER; NO AUTOMATIC CONTROLLER
Whirlpool water not tested for pH and disinfectant at least two (of the total of 4) times during the day’s peak patron load. Record all testing on the daily log.
Correction: Test pool water for pH and disinfectant at least two (of the total of 4) times during the day’s peak patron load.
Code ATCP 76.18(2)(a)2.- WATER TESTED TOTAL OF 4 TIMES WHIRLPOOL,
-
Not serious
Non-critical
THERMOMETER RETURN LINE
An accurate thermometer is not reaing corect temp
Correction: Provide an accurate thermometer in the pool water return line.
Code ATCP 76.19(4)(a)1 - THERMOMETER
-
Not serious
Non-critical
ELECTRICAL GOOD REPAIR
Electrical equipment and lighting not maintained in good repair and in operating condition. Cover plate on eletrical outlet for the controller
Correction: Maintain electrical equipment and lighting in good repair and in operating condition.
Code ATCP 76.33(4)(c) - GOOD REPAIR
-
Not serious
Non-critical