Americinn By Wyndham

500 BALDWIN PLAZA DR, Baldwin, WI 54002 · St. Croix County

53cited violations
7serious tier
9inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
St. Croix County Public Health
License / ID
MWIS-D5XH9J
Status
Permitted
Phone
(214) 405-7179
Official record
St. Croix County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026220
20254280
20243237

Inspections

  1. Jun 18, 2026 Follow Up · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      READABLE CHART

      Labels, tags or color-coding does not correspond to a conspicuously posted, easily read chart that explains the system.

      Correction: Provide the chart for labels, tags and color-coding

      Code ATCP 76.11(5m)(b) - PIPING CHART

  2. Jun 10, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      READABLE CHART

      Labels, tags or color-coding does not correspond to a conspicuously posted, easily read chart that explains the system.

      Correction: Provide the chart for labels, tags and color-coding

      Code ATCP 76.11(5m)(b) - PIPING CHART

  3. Nov 5, 2025 Follow Up · 6 non-critical, 6 repeat
    • Not serious Non-critical Repeat

      TEST KIT APPROVED

      Using the Taylor 5-way test kit for daily testing, not an approved test kit. 6-26-25: Taylor 2005 pool kit is unapproved.

      Correction: Obtain new reagents & color comparator for the Taylor DPD kit that is available, but expired. Use an approved test kit for testing the pool.

      Code ATCP 76.17 (1) - DEPARTMENT-APPROVED

    • Not serious Non-critical Repeat

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in whirlpool and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Not serious Non-critical Repeat

      OPERATING REPORTS-CHEMICAL TESTING

      The operator did not record the following on the operating report: Results for chemical testing.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical Repeat

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical Repeat

      OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT

      The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is pitting of the whirlpool basin.

      Correction: The whirlpool basin is pitting and peeling and needs to be fixed.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

  4. Jun 26, 2025 Re-inspection · 6 non-critical, 6 repeat
    • Not serious Non-critical Repeat

      TEST KIT APPROVED

      Using the Taylor 5-way test kit for daily testing, not an approved test kit. 6-26-25: Taylor 2005 pool kit is unapproved.

      Correction: Obtain new reagents & color comparator for the Taylor DPD kit that is available, but expired. Use an approved test kit for testing the pool.

      Code ATCP 76.17 (1) - DEPARTMENT-APPROVED

    • Not serious Non-critical Repeat

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in whirlpool and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Not serious Non-critical Repeat

      OPERATING REPORTS-CHEMICAL TESTING

      The operator did not record the following on the operating report: Results for chemical testing.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical Repeat

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical Repeat

      OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT

      The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is pitting of the whirlpool basin.

      Correction: The whirlpool basin is pitting and peeling and needs to be fixed.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

  5. Jun 25, 2025 Re-inspection · 8 non-critical, 8 repeat
    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      TEST KIT APPROVED

      Using the Taylor 5-way test kit for daily testing, not an approved test kit.

      Correction: Obtain new reagents & color comparator for the Taylor DPD kit that is available, but expired. Use an approved test kit for testing the pool.

      Code ATCP 76.17 (1) - DEPARTMENT-APPROVED

    • Not serious Non-critical Repeat

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in whirlpool and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Not serious Non-critical Repeat

      OPERATING REPORTS-CHEMICAL TESTING

      The operator did not record the following on the operating report: Results for chemical testing.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical Repeat

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical Repeat

      OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT

      The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is pitting of the whirlpool basin.

      Correction: The whirlpool basin is pitting and peeling and needs to be fixed.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical Repeat

      POOL DECK-INDOOR-DISINFECTED

      Indoor pool deck area not cleaned and disinfected at least weekly with disinfecting agents.

      Correction: Clean and disinfect indoor pool deck area at least weekly with disinfecting agents according to the manufacturer’s directions. Note: It is recommended to avoid the use of an ammonia-based disinfectant as this can contribute to an increased level of chloramines in the pool water.

      Code ATCP 76.33(1)(b)2. - INDOOR DECK DISINFECTED

  6. Jun 4, 2025 Routine · 8 non-critical
    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      TEST KIT APPROVED

      Using the Taylor 5-way test kit for daily testing, not an approved test kit.

      Correction: Obtain new reagents & color comparator for the Taylor DPD kit that is available, but expired. Use an approved test kit for testing the pool.

      Code ATCP 76.17 (1) - DEPARTMENT-APPROVED

    • Not serious Non-critical

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in whirlpool and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Not serious Non-critical

      OPERATING REPORTS-CHEMICAL TESTING

      The operator did not record the following on the operating report: Results for chemical testing.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical

      OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT

      The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT

    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is pitting of the whirlpool basin.

      Correction: The whirlpool basin is pitting and peeling and needs to be fixed.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical

      POOL DECK-INDOOR-DISINFECTED

      Indoor pool deck area not cleaned and disinfected at least weekly with disinfecting agents.

      Correction: Clean and disinfect indoor pool deck area at least weekly with disinfecting agents according to the manufacturer’s directions. Note: It is recommended to avoid the use of an ammonia-based disinfectant as this can contribute to an increased level of chloramines in the pool water.

      Code ATCP 76.33(1)(b)2. - INDOOR DECK DISINFECTED

  7. Aug 23, 2024 Pre-inspection Follow Up · 2 critical, 3 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not working. The gauge on the filter is reading 0 psi.

      Correction: Repair the flowmeter. Repair the pressure gauge and/or determine why the pressure gauge is reading 0psi.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      NEW CODE REQUIREMENT: The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      THERMOMETER RETURN LINE

      An thermometer was not located in the pool water return line.

      Correction: Provide an accurate thermometer in the pool water return line.

      Code ATCP 76.19(4)(a)1 - THERMOMETER

    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      Free chlorine disinfectant is at 2.2 ppm in the whirlpool.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Minimum free chlorine level in the whirlpool is 3.0ppm.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      WHIRLPOOL WATER TEMPERATURE

      The whirlpool water temperature is 86°F. Staff indicate they turn it up in the evening when more use or upon request.

      Correction: Increase temperature to 90F. Maintain the whirlpool water at greater than 90°F, and may not exceed 104°F.

      Code ATCP 76.19(4)(c) - WHIRLPOOL WATER TEMP

  8. Jul 26, 2024 Pre-inspection Follow Up · 2 critical, 3 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not working. The gauge on the filter is reading 0 psi.

      Correction: Repair the flowmeter. Repair the pressure gauge and/or determine why the pressure gauge is reading 0psi.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      NEW CODE REQUIREMENT: The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      THERMOMETER RETURN LINE

      An thermometer was not located in the pool water return line.

      Correction: Provide an accurate thermometer in the pool water return line.

      Code ATCP 76.19(4)(a)1 - THERMOMETER

    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      Free chlorine disinfectant is at 2.2 ppm in the whirlpool.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Minimum free chlorine level in the whirlpool is 3.0ppm.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      WHIRLPOOL WATER TEMPERATURE

      The whirlpool water temperature is 86°F. Staff indicate they turn it up in the evening when more use or upon request.

      Correction: Increase temperature to 90F. Maintain the whirlpool water at greater than 90°F, and may not exceed 104°F.

      Code ATCP 76.19(4)(c) - WHIRLPOOL WATER TEMP

  9. Jun 4, 2024 Pre-inspection · 3 critical, 10 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Weirs not available.

      Correction: Replace weirs as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not working. The gauge on the filter is reading 0 psi.

      Correction: Repair the flowmeter. Repair the pressure gauge and/or determine why the pressure gauge is reading 0psi.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      PIPING LABELED, TAGGED OR CODED

      The piping is not labeled, tagged or color-coded.

      Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.

      Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED

    • Not serious Non-critical

      READABLE CHART

      Easily readable chart that explains the system is not available

      Correction: Provide the chart that explains the system (all labels, tags or color coding shall correspond to an easily readible chart).

      Code ATCP 76.11(5m)(b) - PIPING CHART

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      NEW CODE REQUIREMENT: The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      THERMOMETER RETURN LINE

      An thermometer was not located in the pool water return line.

      Correction: Provide an accurate thermometer in the pool water return line.

      Code ATCP 76.19(4)(a)1 - THERMOMETER

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      NEW CODE REQUIRMENT: Signage warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical

      OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT

      The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.

      Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Serious Critical

      OPERATOR KNOWLEDGE- ELECTRICAL INTERLOCK FUNCTION

      NEW CODE REQUIREMENT: The person responsible is not able to describe how the chemical feeder electrical interlock functions.

      Correction: Ensure that operator can describe how the chemical feeder electrical interlock functions.

      Code ATCP 76.13 (1)(c)2.b - HOW ELECTRICAL INTERLOCK FUNCTIONS

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Free chlorine disinfectant is at 2.2 ppm in the whirlpool.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Minimum free chlorine level in the whirlpool is 3.0ppm.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      WHIRLPOOL WATER TEMPERATURE

      The whirlpool water temperature is 86°F. Staff indicate they turn it up in the evening when more use or upon request.

      Correction: Increase temperature to 90F. Maintain the whirlpool water at greater than 90°F, and may not exceed 104°F.

      Code ATCP 76.19(4)(c) - WHIRLPOOL WATER TEMP

Source: St. Croix County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.