Inspections

  1. Nov 4, 2026 Follow Up · 15 non-critical, 15 repeat
    • Serious Critical Repeat

      Smoke alarms provided

      Smoke alarms are not provided within each individually keyed unit.

      Correction: Provide smoke alarms within each individually keyed unit at the locations specified in rule.

      Code ATCP 72.18(11)(a)

    • Serious Critical Repeat

      Smoke alarm maintained - working order; expiration

      The smoke alarms in the rooms listed above are either not working or, based on the the manufacturer’s date of expiration, they need to be replaced.

      Correction: Repair or replace the smoke alarms within 5 calendar days.

      Code ATCP 72.18(11)(e)

    • Serious Critical Repeat

      Individually keyed unit door lock provided

      The door locks to enter room 107 and 203 are not working properly.

      Correction: Repair or replace the door locks to enter rooms 107 and 203.

      Code ATCP 72.18(5)(a)

    • Serious Critical Repeat

      Pest control - extensive infestation - hire PCO

      Insect infestation was observed in rooms 111 and 207 but there was also evidence of infestation in common areas throughout the hotel. The infestation appears to be so extensive that it is unlikely that a nonprofessional can eradicate the pests effectively.

      Correction: Hire a licensed pest control operator to eliminate infestation. Regular reporting from pest control company must be submitted to the health department that shows that infestation is being remediated.

      Code ATCP 72.19(2)(a)1.a.

    • Not serious Priority Foundation Repeat

      Building evacuation diagram (hotel, motel, condo) - posted

      The building evacuation diagram in noted rooms are not conspicuously posted.

      Correction: Post the building evacuation diagram in each individually keyed unit.

      Code ATCP 72.18(6)(a)1.

    • Not serious Priority Foundation Repeat

      Emergency lights maintained in good repair

      The emergency lighting in both hallways and stairwells are not working.

      Correction: Repair or replace the emergency lights. This was referred to City of New Richmond Fire Inspector on 10/26/26.

      Code ATCP 72.18(7)(a)

    • Not serious Priority Foundation Repeat

      PIC communication to employee on symptom reporting

      The person in charge does not have procedures in place to inform employees of their duty to report symptoms of vomiting, diarrhea, or diagnosis of a food or waterborne communicable disease to the person in charge.

      Correction: Develop procedures to inform employees of their duty to report symptoms of vomiting, diarrhea, or diagnosis of a food or waterborne communicable disease to the person in charge.

      Code ATCP 72.22(1)

    • Not serious Non-critical Repeat

      Ceiling height >= 7'

      In room 207 there is a 3rd bed stuck under a slanted ceiling that is less than 7 feet.

      Correction: Remove 3rd bed under the low ceiling.

      Code ATCP 72.18(3)(a)

    • Not serious Non-critical Repeat

      Individually keyed unit sliding exterior door lock provided

      The sliding doors to the patios in room 206 and 208 do not have working locks on them.

      Correction: Repair or replace the locks on the sliding patio doors in room 206 and 208.

      Code ATCP 72.18(5)(b)

    • Not serious Non-critical Repeat

      Fire rated doors - self-closing

      The required fire rated doors are not self-closing and were propped open.

      Correction: Enable the fire rated door to self-close or keep them closed at all times.

      Code ATCP 72.18(9)(c)2.

    • Not serious Non-critical Repeat

      Sleeping rooms maintained in a clean condition

      There is a lot of cleaning that needs to be done. This includes floors, walls, ceilings, furniture, lighting, carpeting, and all surface areas in the rooms listed above. They are all dirty and not maintained in a clean condition. Also in the rooms 105, 109, 110, 111, 114, 202, 204, 206, 213, 216, the Packaged Terminal Air Conditionar (PTAC) filters are dirty in the air conditioners. There was a chemical smell coming from the closet in room 208.

      Correction: Clean all the surface areas listed in the rooms above. Clean the PTAC filters in the rooms identified. Eliminate the chemical odor coming from room 208.

      Code ATCP 72.19(1)(a)1.

    • Not serious Non-critical Repeat

      Sleeping rooms maintained in good repair

      Room 110 has a hole in the wall. Room 208 has a hole in the closet wall. Room 111 has hole in the celing. Toilet seat cover are missing or not sized correctly in rooms 109, 111, 206, 211

      Correction: Maintain all sleeping rooms in good repair.

      Code ATCP 72.19(1)(a)2.

    • Not serious Non-critical Repeat

      Pest control - openable windows screened

      The windows in rooms listed above rooms are not equipped with screens. Evaluate all windows and patio doors and make corrections to ones that do not have a protected opening

      Correction: Install screen all of the windows in the rooms listed.

      Code ATCP 72.19(2)(a)3.b.

    • Not serious Non-critical Repeat

      Ice bucket with liner sanitization

      All the rooms do not have the proper ice buckets. An ice bucket with a single-use disposable liners are not being provided in each room. and is not wash, rinsed, and sanitized in an approved manner.

      Correction: There are two options either have a ice bucket for each room that are washed, rinsed, and sanitized between each guest OR provide a ice bucket for each room with a disposable liner and then spray sanitize the bucket between guests.

      Code ATCP 72.20(6)(f)

    • Not serious Non-critical Repeat

      Nonabsorbent mattress cover or mattress surface

      The beds in all the rooms listed above do not have non-absorbent mattress protectors that cover the entire sleeping surface.

      Correction: Provide a non-absorbent mattress protector that covers the entire sleeping surface for each bed.

      Code ATCP 72.20(8)(d)

  2. Aug 27, 2026 Routine · 8 non-critical
    • Not serious Priority Foundation

      Smoke alarm installed in each sleeping room

      A smoke alarm is not within each sleeping room. Rooms 207 and 209 smoke alarms do not work.

      Correction: Provide a smoke alarm within each sleeping room.

      Code ATCP 72.18(11)(b)3.

    • Not serious Priority Foundation

      Bed placement max ceiling height

      The placement of the 3rd bed in the cubby under steps in room 207 does not provide the occupant with maximum ceiling height clearance for emergency egress.

      Correction: Rearrange or remove bed to allow maximum ceiling height clearance for emergency egress.

      Code ATCP 72.18(3)(c)

    • Not serious Priority Foundation

      Building evacuation diagram (hotel, motel, condo) - posted

      The building evacuation diagram in room 212 is not conspicuously posted.

      Correction: Post the building evacuation diagram in each individually keyed unit.

      Code ATCP 72.18(6)(a)1.

    • Not serious Priority Foundation

      Fire rated doors - closed

      The fire rated door on 2nd floor south end is not maintained closed.

      Correction: Keep the fire rated door closed unless interconnected with fire alarm system.

      Code ATCP 72.18(9)(c)3.

    • Not serious Priority Foundation

      Pest control - outer openings protected

      Window in room 207 is not screened to protected from the entrance of pests.

      Correction: Maintain all openings to the outside to prevent the entrance of pests.

      Code ATCP 72.19(2)(a)3.a.

    • Not serious Priority Foundation

      Jetted, fill and drain bathtubs - procedures, demonstration of knowledge

      The person in charge cannot describe the cleaning and sanitizing procedures of the jetted, fill and drain bathtub. Did not fill tub above the jet outlets and turn on jets

      Correction: Develop procedures for cleaning and sanitizing jetted, fill and drain bathtubs following the manufacturer’s instructions. Cleaning and sanitization of jetted, fill and drain bathtubs shall occur after use between each guest stay.Send kanaka hot tub cleaning instructions

      Code ATCP 72.20(4)(b)

    • Not serious Non-critical

      License posted in public view

      A current license is not posted on the premises in a place visible to the public.

      Correction: Post a current license in the premises in a place visible to the public.

      Code ATCP 72.07(7)

    • Not serious Non-critical

      Nonabsorbent mattress cover or mattress surface

      The mattress in room 201 & 212 are not provided with a nonabsorbent mattress protector that covers the entire sleeping surface.

      Correction: Provide a nonabsorbent mattress protector that covers the entire sleeping surface or have an easily cleanable nonabsorbent mattress surface.

      Code ATCP 72.20(8)(d)

  3. Aug 29, 2025 Routine · 2 non-critical
    • Not serious Non-critical

      SMOKE DETECTORS - REQUIREMENT

      Smoke detectors are absent or not in working order in room #202.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations.

      Code ATCP 72.14 (2) (c)

    • Not serious Non-critical

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      PTAK filter is soiled in 103 and 202

      Correction: Maintain equipment and furnishings in a clean condition.

      Code [B] ATCP 72.11 (6)

  4. Aug 30, 2024 Re-inspection · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from Room 105, 215, 109, 107.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical Repeat

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door(s) are propped open or are open at time of inspection.

      Correction: Fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

  5. Aug 16, 2024 Re-inspection · 6 non-critical, 6 repeat
    • Not serious Non-critical Repeat

      DOOR LOCKS

      Patio door lock in Room 101 does not work.

      Correction: Provide door locks that are in working order. Repair door lock.

      Code ATCP 72.14 (2) (d)

    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from Room 105, 215, 109, 107.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical Repeat

      INSECT AND RODENT CONTROL

      Dead cockroaches are observed in Room 109 (evidence of spray on walls behind bed & nightstand) and Room 111 (room is not being rented and under complete renovation).

      Correction: Eliminate the presence and harborage of insects and rodents, all rooms above and beside these rooms (entire southwest wing of rooms) needs to be treated. Spray has been used, prevent cockroaches from moving to subsequent rooms. Do not rent out these rooms while being treated.

      Code ATCP 72.15 (3)

    • Not serious Non-critical Repeat

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door(s) are propped open or are open at time of inspection.

      Correction: Fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      FIRE EXTINGUISHERS - MAINTAINED

      Extinguishers are not labeled and tagged with month/year maintenance was performed, company performing the maintenance

      Correction: Annual pressure testing required with record maintained.

      Code [M] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

  6. Jul 26, 2024 Re-inspection · 6 non-critical, 6 repeat
    • Not serious Non-critical Repeat

      DOOR LOCKS

      Patio door lock in Room 101 does not work.

      Correction: Provide door locks that are in working order. Repair door lock.

      Code ATCP 72.14 (2) (d)

    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from Room 105, 215, 109, 107.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical Repeat

      INSECT AND RODENT CONTROL

      Dead cockroaches are observed in Room 109 (evidence of spray on walls behind bed & nightstand) and Room 111 (room is not being rented and under complete renovation).

      Correction: Eliminate the presence and harborage of insects and rodents, all rooms above and beside these rooms (entire southwest wing of rooms) needs to be treated. Spray has been used, prevent cockroaches from moving to subsequent rooms. Do not rent out these rooms while being treated.

      Code ATCP 72.15 (3)

    • Not serious Non-critical Repeat

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door(s) are propped open or are open at time of inspection.

      Correction: Fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      FIRE EXTINGUISHERS - MAINTAINED

      Extinguishers are not labeled and tagged with month/year maintenance was performed, company performing the maintenance

      Correction: Annual pressure testing required with record maintained.

      Code [M] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

  7. Jul 17, 2024 Routine · 12 non-critical, 6 repeat
    • Not serious Non-critical Repeat

      DOOR LOCKS

      Patio door lock in Room 101 does not work.

      Correction: Provide door locks that are in working order. Repair door lock.

      Code ATCP 72.14 (2) (d)

    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from Room 105, 215, 109, 107.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical

      INSECT AND RODENT CONTROL

      Dead cockroaches are observed in Room 109 (evidence of spray on walls behind bed & nightstand) and Room 111 (room is not being rented and under complete renovation).

      Correction: Eliminate the presence and harborage of insects and rodents, all rooms above and beside these rooms (entire southwest wing of rooms) needs to be treated. Spray has been used, prevent cockroaches from moving to subsequent rooms. Do not rent out these rooms while being treated.

      Code ATCP 72.15 (3)

    • Not serious Non-critical

      CARBON MONOXIDE DETECTORS - EXPIRATION

      The carbon monoxide detector in room 101 does not have expiration date on unit.

      Correction: Carbon monoxide detectors require an expiration date on the unit, replace all units with unknown expiration.

      Code [A] ATCP 72.145 (4)(a)

    • Not serious Non-critical

      UTENSIL SANITIZATION-ICE BUCKETS

      Guest ice buckets are not being washed, rinsed and sanitized between guest periods. Staff indicate they are washed in the bathroom sink

      Correction: Guest ice buckets must be washed, rinsed and sanitized in an approved manner before being provided for use by a different guest OR provide single use disposable liners for ice buckets

      Code [B] ATCP 72.11 (3)(a)

    • Not serious Non-critical

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      Room 101: back legs on desk appear moldy. Room 201: tabletop, microwave, under couch cushions are dirty. Room 215: microwave,under bed dirty.

      Correction: Maintain equipment and furnishings in a clean condition.

      Code [B] ATCP 72.11 (6)

    • Not serious Non-critical Repeat

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door(s) are propped open or are open at time of inspection.

      Correction: Fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      The AC unit filter is unclean in Rooms 101, 105, 201, 215, 216, 109, 107 The bathroom fan cover is dusty in Rooms 105, 216. The bathroom ceiling in Room 105 has mold above the bathtub.

      Correction: Clean the filters. Clean on a regular schedule and check all other rooms to ensure that the filters are clean. Clean bathroom fan covers. Clean on a regular schedule when dusty. Clean the ceiling of mold in bathrooms.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical

      FIRE EXTINGUISHERS - MAINTAINED

      Extinguishers are not labeled and tagged with month/year maintenance was performed, company performing the maintenance

      Correction: Annual pressure testing required with record maintained.

      Code [M] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      EXIT LIGHTING - PROVIDED

      Emergency lighting that was randomly tested were not working (outside Room 102, Room 110, Room 204).

      Correction: Emergency lights are not working when tested.

      Code [R] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      DIRECTIONS FOR ESCAPE

      No directions for escape provided on the back of door in Room 113, located in drawer in room.

      Correction: Provide directions for escape on back of door in each sleeping room.

      Code [V] ATCP 72.14 (1)

Source: St. Croix County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.