RecordWell Data

The Commerce Tm By Wyndham

1525 COMMERCE COURT, River Falls, WI 54022 · St. Croix County

16cited violations
1serious tier
5inspections

Establishment

Type
Lodging (Hotel and Motel - 31 - 99 Rooms)
Inspected by
St. Croix County Public Health
License / ID
ETHN-CRRLN5
Status
Permitted
Official record
St. Croix County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026111
20252130
2024120
2023100

Inspections

  1. May 6, 2026 Routine · 1 non-critical
    • Serious Critical Corrected on site

      Carbon monoxide alarm installation - FBA outside IKU - alternate locations

      A carbon monoxide alarm is not provided in the sprinkler and furnace room with fuel burning appliances.

      Correction: Provide carbon monoxide alarm in the sprinkler and furnace room.

      Code ATCP 72.18(12)(c)1.-2.

  2. Jun 11, 2025 Re-inspection · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from room 101. 6-11-25: One of two window screens is still missing.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical Repeat

      FIRE EXTINGUISHERS - MAINTAINED

      Extinguishers are not tested annually. 6-11-25: Management is working with the River Falls Fire Department to have the extiguishers inspected.

      Correction: Annual pressure testing required with record maintained.

      Code [M] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

  3. May 5, 2025 Routine · 10 non-critical, 2 repeat
    • Not serious Non-critical

      PERMIT NOT DISPLAYED IN PUBLIC VIEW

      Permit is not displayed conspicuously to the public.

      Correction: Post the permit in a conspicuous location to the public.

      Code ATCP 72.04 (7)

    • Not serious Non-critical

      SMOKE DETECTORS - REQUIREMENT

      Smoke detector in room 118 is not operational. Smoke detectors in all inspected rooms are not stamped with install date or expiration date.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations.

      Code ATCP 72.14 (2) (c)

    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from room 101,

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical

      EMERGENCY ASSISTANCE

      No means of offering emergency assistance is provided to guests at time of registration.

      Correction: At time of registration either verbally offer emergency assistance to guests if needed, or provide a means that guests may identify themselves as needing assistance in an emergency.

      Code SS 97.623 (2)

    • Not serious Non-critical

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      A carbon monoxide detector is not provided in laundry room and sprinkler room where a fuel-burning appliance is located.

      Correction: Provide carbon monoxide detectors in all required locations.

      Code [A] ATCP 72.145 (3)

    • Not serious Non-critical

      PLUMBING FIXTURES – SANITARY CONDITION

      Ice machine on 1st floor drain and ice catch pan area moldy and unclean.

      Correction: Maintain plumbing and fixtures in a sanitary condition.

      Code [C] ATCP 72.10 (4)

    • Not serious Non-critical

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated doors at West end 1st and 2nd floor and East end 1st floor are propped open or are open at time of inspection. Alarm panel magnetic door closure system not operational

      Correction: Except for fire doors on magnetic closures controlled by a central activation of the fire alarm system, fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      MATTRESS PAD PROVIDED/SUFFICIENT SIZE

      Mattress pad does not completely cover mattress in rooms 110 and 118.

      Correction: Provide a mattress pad that completely covers the mattress.

      Code [H] ATCP 72.11 (5)

    • Not serious Non-critical

      FIRE EXTINGUISHERS - MAINTAINED

      Extinguishers are not tested annually

      Correction: Annual pressure testing required with record maintained.

      Code [M] ATCP 72.14 (1)

    • Not serious Non-critical

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

  4. Jun 4, 2024 Routine · 2 non-critical
    • Not serious Non-critical

      WINDOW SCREENING

      Window screen has rip and needs repair in room 111.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical

      MATTRESS PAD PROVIDED/SUFFICIENT SIZE

      Mattress pad does not completely cover mattress in room 111

      Correction: Provide a mattress pad that completely covers the mattress.

      Code [H] ATCP 72.11 (5)

  5. May 12, 2023 Pre-inspection · No items found

    No violations cited.

Source: St. Croix County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.