Apple River Family Campground - Lower
345 CHURCHILL RD, Somerset, WI 54025 · St. Croix County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- St. Croix County Public Health
- License / ID
- BHEP-8CCL5B
- Status
- Permitted
- Phone
- (715) 247-3600
- Official record
- St. Croix County Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 1 | 0 |
| 2025 | 2 | 14 | 6 |
| 2024 | 1 | 1 | 0 |
| 2023 | 2 | 2 | 0 |
Inspections
-
Sep 8, 2026 Follow Up · No items found
No violations cited.
-
Jul 23, 2026 Re-inspection · 1 non-critical
-
Not serious
Non-critical
VGBA DRAIN COVER INFO-LIFESPAN
The VGBA log or other proof does not indicate drain cover life span.
Correction: Indicate in the log the drain cover life span.
Code ATCP 76.38(2)(b)4. - LIFESPAN
-
Not serious
Non-critical
-
Aug 15, 2025 Routine · 3 critical, 3 non-critical, 1 repeat
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. North Skimmer weir door is not attached..
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Leak in line to north skimmer.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Pool volume of 36270 / 60 / 82 = 7.4 hr turnover. needs to be 6 hr turnover
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
VGBA DRAIN COVER INFO-LIFESPAN
The VGBA log or other proof does not indicate drain cover life span.
Correction: Indicate in the log the drain cover life span.
Code ATCP 76.38(2)(b)4. - LIFESPAN
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
RING BOUY
A ring buoy not provided.
Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.
Code ATCP 76.26(1)(b)2.a - RING BOUY
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
-
Aug 15, 2025 Routine · 3 critical, 3 non-critical, 1 repeat
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Leak in line to north skimmer.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. North Skimmer weir door is not attached..
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Pool volume of 36270 / 60 / 82 = 7.4 hr turnover. needs to be 6 hr turnover
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
VGBA DRAIN COVER INFO-LIFESPAN
The VGBA log or other proof does not indicate drain cover life span.
Correction: Indicate in the log the drain cover life span.
Code ATCP 76.38(2)(b)4. - LIFESPAN
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
RING BOUY
A ring buoy not provided.
Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.
Code ATCP 76.26(1)(b)2.a - RING BOUY
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
-
Aug 13, 2024 Routine · 1 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Base on pool volume of 36260 and a flow rate of 82 gpm, turnover rate is 7.37. 36270/82/60=7.37 To get to a turnover rate of 6 hours, your flow rate should be at least 100.75 gpm. 36270/6/60=100.75. If the volume of your pool is not 36270, provide documentation.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
-
Aug 16, 2023 Re-inspection · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION RATE NOT MET - POOLS
The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.
Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(a)
-
Not serious
Non-critical
Repeat
-
Jun 21, 2023 Routine · 1 non-critical
-
Not serious
Non-critical
RECIRCULATION RATE NOT MET - POOLS
The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.
Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(a)
-
Not serious
Non-critical
Source: St. Croix County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.