Apple River Family Campground - Lower

345 CHURCHILL RD, Somerset, WI 54025 · St. Croix County

18cited violations
6serious tier
7inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
St. Croix County Public Health
License / ID
BHEP-8CCL5B
Status
Permitted
Phone
(715) 247-3600
Official record
St. Croix County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026210
20252146
2024110
2023220

Inspections

  1. Sep 8, 2026 Follow Up · No items found

    No violations cited.

  2. Jul 23, 2026 Re-inspection · 1 non-critical
    • Not serious Non-critical

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

  3. Aug 15, 2025 Routine · 3 critical, 3 non-critical, 1 repeat
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. North Skimmer weir door is not attached..

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Leak in line to north skimmer.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Pool volume of 36270 / 60 / 82 = 7.4 hr turnover. needs to be 6 hr turnover

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

    • Serious Critical

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

    • Serious Critical

      RING BOUY

      A ring buoy not provided.

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  4. Aug 15, 2025 Routine · 3 critical, 3 non-critical, 1 repeat
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Leak in line to north skimmer.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. North Skimmer weir door is not attached..

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Pool volume of 36270 / 60 / 82 = 7.4 hr turnover. needs to be 6 hr turnover

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

    • Serious Critical

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

    • Serious Critical

      RING BOUY

      A ring buoy not provided.

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications. [Describe].

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  5. Aug 13, 2024 Routine · 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Base on pool volume of 36260 and a flow rate of 82 gpm, turnover rate is 7.37. 36270/82/60=7.37 To get to a turnover rate of 6 hours, your flow rate should be at least 100.75 gpm. 36270/6/60=100.75. If the volume of your pool is not 36270, provide documentation.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

  6. Aug 16, 2023 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION RATE NOT MET - POOLS

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

  7. Jun 21, 2023 Routine · 1 non-critical
    • Not serious Non-critical

      RECIRCULATION RATE NOT MET - POOLS

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

Source: St. Croix County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.