Wyndham Garden Appleton Swimming Pool

1565 N FEDERATED DR, Appleton, WI 54913 · Outagamie County

34cited violations
6serious tier
5inspections

Establishment

Type
Pool / recreational water (Swimming)
Inspected by
Outagamie County Public Health
License / ID
KMCN-DCCM3K
Status
Permitted
Official record
Outagamie County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026120
20254326

Inspections

  1. Jan 5, 2026 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      VACUUM SAND FILTER BAKWASHED

      The vacuum sand filters are not backwash according to manufacturer's recommendations. Backwash differential of 10 PSI. Pressure gauge readings were observed passed backwash differential at 29 PSI

      Correction: Notified Person in Charge (PIC). PIC shall backwash vacuum filters according to manufacturer's recommendations within the next 30 days. Failure to comply may result in enforcement actions.

      Code ATCP 76.11(6)(b) 3. - VACUUM SAND FILTER BACKWASH

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified Person in Charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed at the next routine inspection. Failure to comply may result in enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

  2. Apr 11, 2025 Pre-inspection Follow Up · 1 critical, 6 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is incorrect. Flow for main drain was observed opened all the way or at 100 percent and flow for skimmer was observed open roughly 80 percent.

      Correction: Notified person-in-charge (PIC). PIC shall adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Notified person-in-charge (PIC). PIC shall adjust or repair the flowmeter within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin observed with cracks and not maintained in a cleanable condition. Physical cracked chips can be seen on the floor of swimming pool basin.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition within 90 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Serious Critical Repeat

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

  3. Mar 31, 2025 Pre-inspection Follow Up · 1 critical, 6 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is incorrect. Flow for main drain was observed opened all the way or at 100 percent and flow for skimmer was observed open roughly 80 percent.

      Correction: Notified person-in-charge (PIC). PIC shall adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Notified person-in-charge (PIC). PIC shall adjust or repair the flowmeter within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin observed with cracks and not maintained in a cleanable condition. Physical cracked chips can be seen on the floor of swimming pool basin.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition within 90 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Serious Critical Repeat

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

  4. Jan 9, 2025 Pre-inspection Follow Up · 1 critical, 6 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is incorrect. Flow for main drain was observed opened all the way or at 100 percent and flow for skimmer was observed open roughly 80 percent.

      Correction: Notified person-in-charge (PIC). PIC shall adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Notified person-in-charge (PIC). PIC shall adjust or repair the flowmeter within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin observed with cracks and not maintained in a cleanable condition. Physical cracked chips can be seen on the floor of swimming pool basin.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition within 90 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Serious Critical Repeat

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

  5. Jan 2, 2025 Pre-inspection · 3 critical, 8 non-critical
    • Not serious Non-critical

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is incorrect. Flow for main drain was observed opened all the way or at 100 percent and flow for skimmer was observed open roughly 80 percent.

      Correction: Notified person-in-charge (PIC). PIC shall adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Notified person-in-charge (PIC). PIC shall adjust or repair the flowmeter within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity observed at 38 PPM.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin observed with cracks and not maintained in a cleanable condition. Physical cracked chips can be seen on the floor of swimming pool basin.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition within 90 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical

      WATER HEATERS-MAINTAINED OPERATIONAL

      Water heater observed not in operating condition.

      Correction: Notified person-in-charge (PIC). PIC shall maintain water heater in operating condition within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33(4)(a) - MAINTAINED

    • Serious Critical

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level observed at 0.25 PPM for free chlorine.

      Correction: Notified person-in-charge (PIC). PIC shall immediately close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      GATES AND DOORS MECHANISM 54 INCHES

      A self-closing latching and lockable mechanism is present but not in working order. The door does not self-latch and can be opened from the outside. Operator has to manually force the door close to fully lock and latch.

      Correction: Notified perosn-in-charge (PIC). PIC shall install a self-closing latching and lockable mechanism at least 54 inches from the bottom of the gate or door within 30 days. Operator shall ensure that the door remains closed and locked at all times while door is being serviced and or replaced. This will be reviewed during the next routine inspection. Failure to comply will result in license being withh

      Code ATCP 76.34(2)(b) - SELF-CLOSING, LATCHING MECHANISM

Source: Outagamie County Public Health. History last read Oct 19, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.