Wyndham Garden Appleton Whrilpool

1565 N FEDERATED DR, Appleton, WI 54913 · Outagamie County

26cited violations
5serious tier
6inspections

Establishment

Type
Pool / recreational water (Whirlpool)
Inspected by
Outagamie County Public Health
License / ID
KMCN-DCCLY4
Status
Permitted
Official record
Outagamie County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026241
20254224

Inspections

  1. Jan 19, 2026 Re-inspection · 2 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Basket Cover was observed in a broken condition.

      Correction: Notified Person in Charge (PIC). PIC shall repair or replace the basket cover within 7-10 days. Failure to comply may result in additional follow up. This will be re-evaluated at the next routine inspection report.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified Person in Charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. Failure to provide one may result in additional follow up. This will be re-evaluated at the next routine inspection.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

  2. Jan 9, 2026 Routine · 1 critical, 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is 40.

      Correction: Notified Person in Charge (PIC). PIC shall maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. Re-evaluation will be completed within 7-10 days.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 0.14 for Free Available Chlorine.

      Correction: Notified Person in Charge (PIC). PIC immeditly identified that the chlorine container was emptied and replaced it. PIC will close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Re-evaluation will take place within 7-10 days.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  3. Apr 11, 2025 Pre-inspection Follow Up · 1 critical, 4 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity observed at 40 PPM.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Serious Critical Repeat

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

  4. Mar 31, 2025 Pre-inspection Follow Up · 1 critical, 4 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity observed at 40 PPM.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Serious Critical Repeat

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

  5. Jan 9, 2025 Pre-inspection Follow Up · 5 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity observed at 40 PPM.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

  6. Jan 2, 2025 Pre-inspection · 2 critical, 5 non-critical
    • Not serious Non-critical

      INTERLOCKED-ELECTRICAL

      Power to recirculation system is not interlocked with the power to the chemical feed. When pumps are turned off, feeders are continually feeding chemicals.

      Correction: Notified peson-in-charge (PIC). PIC shall provide interlock between the power to the recirculation system and power to the chemical feeder(s) within 7 days. This will be reviewed during the re-inspection in 7 days. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity observed at 40 PPM.

      Correction: Notified person-in-charge (PIC). PIC shall maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Notified person-in-charge (PIC). PIC shall provide eye wash solution for the first aid kit within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Notified person-in-charge (PIC). PIC shall provide signage or provide other communication warning against prolonged breath holding within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower handwashing faucet is in not working order. Additionally, the shower room's door is not lockable when in use or when door is closed.

      Correction: Notified person-charge (PIC). PIC shall maintain the shower, toilet and dressing facilities in good repair within 30 days. This will be reviewed during the next routine inspection. Failure to comply may result in further enforcement actions.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Serious Critical

      MAXIMUM CHLORINE

      The maximum chlorine residual exceeds 10 ppm. Actual reading for the whirlpool observed at 13.88 PPM.

      Correction: Notified person-in-charge (PIC). PIC shall immediately close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A. This will be reviewed during the next routine inspection. Failure to comply will result in license being withheld and may result in further enforcement actions.

      Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE

    • Serious Critical

      GATES AND DOORS MECHANISM 54 INCHES

      A self-closing latching and lockable mechanism is present but not in working order. The door does not self-latch and can be opened from the outside. Operator has to manually force the door close to fully lock and latch.

      Correction: Notified perosn-in-charge (PIC). PIC shall install a self-closing latching and lockable mechanism at least 54 inches from the bottom of the gate or door within 30 days. Operator shall ensure that the door remains closed and locked at all times while door is being serviced and or replaced. This will be reviewed during the next routine inspection. Failure to comply will result in license being withh

      Code ATCP 76.34(2)(b) - SELF-CLOSING, LATCHING MECHANISM

Source: Outagamie County Public Health. History last read Oct 19, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.