Cobblestone Hotel & Suites
499 MAIN AVE, De Pere, WI 54115 · Brown County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- De Pere Health Department
- License / ID
- KBUE-CGPNAY
- Status
- Permitted
- Phone
- (920) 278-0111
- Official record
- De Pere Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 4 | 0 |
| 2025 | 1 | 1 | 0 |
| 2024 | 2 | 8 | 3 |
Inspections
-
Aug 27, 2026 Routine · 4 non-critical, 1 repeat
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 50ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. The alkalinity reagents are expired.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
POSTING SIGNAGE-NO DIVING
The No-Diving sign has letters that are under 4 inches high.
Correction: Post signage indicating No-Diving with at least 4 inch high letters.
Code ATCP 76.29(1)(d) - NO DIVING
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
-
Aug 14, 2025 Routine · 1 non-critical
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report: dates of interlock tests, results, and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
-
Aug 12, 2024 Follow Up · No items found
No violations cited.
-
Jul 25, 2024 Routine · 3 critical, 5 non-critical
-
Not serious
Non-critical
SAFETY DATA SHEET
A safety data sheet was not available for chlorine, acid, etc. in the pool area.
Correction: Maintain a safety data sheet for each chemical on site. Store SDSs so that they are readily accessible to staff without having to leave the pool area.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
POSTING SIGNAGE-NO DIVING
No-Diving signage is not present where it is required.
Correction: Post signage indicating No-Diving.
Code ATCP 76.29(1)(d) - NO DIVING
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
PH
The pH is 8.0.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better. The pool was being serviced by an Ecolab technician at the time of the inspection.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A. An Ecolab technician was on site during this inspection.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Serious
Critical
SHEPHERD'S CROOK PIECES SECURELY CONNECTED
The shepherd's crook is not securely held together.
Correction: Provide a shepherd's crook that is one piece or with sections that are securely connected.
Code ATCP 76.26(1)(b)1.c. - SHEPHERD'S CROOK PIECES SECURELY CONN
-
Not serious
Non-critical
Source: De Pere Health Department. History last read Oct 22, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.