Hyatt Regency Green Bay Swimming Pool
333 MAIN ST, Green Bay, WI 54301 · Brown County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- Brown County Health & Human Services
- License / ID
- APUU-DZ9S3U
- Status
- Pending
- Phone
- (312) 640-7430
- Official record
- Brown County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 5 | 0 |
Inspections
-
Nov 3, 2026 Pre-inspection · 5 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The pool turnover rate was 6.296.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 621 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
POOL EQUIPMENT-REPAIRED AS NECESSARY
The pool equipment is not repaired as necessary. There is a pipe noted leaking with water on the floor in the equipment room.
Correction: The pool equipment is not repaired as necessary.
Code ATCP 76.33(1)(e)4. - EQPT REPAIRED AS NEEDED
-
Not serious
Non-critical
Source: Brown County Health & Human Services. History last read Nov 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.