Osseo Municipal Swimming Pool
13418 PARK AVE, Osseo, WI 54758 · Trempealeau County
Establishment
- Type
- Pool / recreational water (Pool - Complex with Features)
- Inspected by
- Trempealeau County Health Department
- License / ID
- HSAT-7QWN4R
- Status
- Permitted
- Phone
- (715) 597-2207
- Official record
- Trempealeau County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 9 | 3 |
| 2025 | 1 | 5 | 1 |
| 2023 | 1 | 2 | 1 |
Inspections
-
Aug 5, 2026 Routine · 3 critical, 6 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit is missing eye wash solution.
Correction: Provide eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments. Chemical interlock checklist not completed.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
Corrected on site
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device.
Correction: Provide soap in a permanently-installed dispensing device.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. Lifeguard permenant SW corner has cracks and is need of repair.
Correction: Maintain the pool equipment [Describe].
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
Modification(s) made but no DSPS Approval available for them.
The operator modified a pool and did not submit pool construction plans to DSPS for review and approval. Piping was damaged over winter, city removed concrete and replaced damaged piping in pool area. Called DSPS while on site, awaiting call back from DSPS.
Correction: Have WI-licensed architect or engineer submit pool construction (modification) plans to DSPS and obtain approval from DSPS for the construction of the pool.
Code ATCP 76.04 (2) - PLANS SUBMITTED TO DSPS FOR MODIFICATION, A
-
Serious
Critical
RESCUE TUBE
A rescue tube is not in good repair.
Correction: Provide a rescue tube.
Code ATCP 76.26(1)(b)2.b. -RESCUE TUBE
-
Serious
Critical
Corrected on site
HOSING - BACKFLOW PREVENTION DEVICE
Missing backflow device on SE corner of deck on water faucet.
Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION
-
Not serious
Non-critical
Repeat
-
Jul 8, 2025 Routine · 1 critical, 4 non-critical
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit eye wash solution is expired.
Correction: Provide new eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
FIRST AID KIT-INSTANT COLD PACKS
The first aid kit is missing instant cold packs.
Correction: Provide instant cold packs for the first aid kit.
Code ATCP 76.27(1)(b)9. - INSTANT COLD PACKS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
-
Aug 4, 2023 Routine · 1 critical, 1 non-critical
-
Not serious
Non-critical
FIRST AID SUPPLIES MISSING
Eyewash bottle is missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code [C] ATCP 76.27(1)
-
Serious
Critical
Corrected on site
BACKFLOW - HOSE BIBBS
The hose bibbs in all three area's on the deck are not installed and is not protected against backsiphonage.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.
Code [A] ATCP 76.33(1)(d)
-
Not serious
Non-critical
Source: Trempealeau County Health Department. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.