Therapy Pool
621 SCIENCE DR, Madison, WI 53711 · Dane County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- University Environmental Health Program
- License / ID
- MWOK-BP6JL2
- Status
- Permitted
- Phone
- (608) 265-8350
- Official record
- University Environmental Health Program inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 2 | 1 |
| 2025 | 2 | 2 | 1 |
| 2024 | 2 | 3 | 1 |
Inspections
-
Oct 21, 2026 Routine · 1 non-critical
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not implemented their plan to minimize combined chlorine in the pool. Combined chlorine was noted as 0.8 ppm during inspection.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
-
Mar 19, 2026 Routine · 1 critical
-
Serious
Critical
Corrected on site
HAZARDOUS CONDITION
One screw was missing on one of the main drain covers. The screw was replaced per the manufacturer's instructions during the inspection. The person in charge noted that they will have their pool company inspect all screws tomorrow.
Correction: Correct the hazardous condition [Describe].
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Serious
Critical
Corrected on site
-
Oct 20, 2025 Routine · 1 critical, 1 non-critical
-
Not serious
Non-critical
REAGENTS REPLACED
Several reagents in the facility's Taylor test kit were expired or the expiration dates have worn off.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Serious
Critical
Modification(s) made but no DSPS Approval available for them.
EH&S records from 2022 and initial construction records have a National Line NFS-34-50B-135-E listed as the pool filter. During the inspection, a Poltank 34135-050-E as the filter. The person in charge stated that the filter may have been changed a few years ago. DSPS approval for replacement (not like-for-like) is not on file at the facility.
Correction: Have WI-licensed architect or engineer submit pool construction (modification) plans to DSPS and obtain approval from DSPS for the construction of the pool.
Code ATCP 76.04 (2) - PLANS SUBMITTED TO DSPS FOR MODIFICATION, A
-
Not serious
Non-critical
-
Apr 11, 2025 Routine · No items found
No violations cited.
-
Oct 14, 2024 Routine · No items found
No violations cited.
-
May 31, 2024 Routine · 1 critical, 2 non-critical
-
Not serious
Non-critical
ELECTRONIC MONITORING FREQUENCY OF TESTING
The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. Pool is not getting tested on Sundays.
Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.
Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ
-
Not serious
Non-critical
POSTING SIGNAGE-SUPERVISION OF CHILDREN
At a non-lifeguarded pool, no signage stating that children under 12 must be supervised is present.
Correction: Post signage stating that children under 12 must be supervised.
Code ATCP 76.29(1)(c) - SUPERVISE CHILDREN
-
Serious
Critical
Corrected on site
INTERLOCK LOG-INFORMATION
The monthly testing log is missing or incomplete. Corrected on site by altering the June form to include this information. We will check during monthly review that this was filled out correctly.
Correction: Maintain a log that is documented with the date, results, and the name of the person performing the interlock test.
Code ATCP 76.13 (1)(c)4.a - INTERLOCK LOG, INFORMATION REQUIRED
-
Not serious
Non-critical
Source: University Environmental Health Program. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.