Anvil Lake Hideaway
2090 S ANVIL LAKE RD, Eagle River, WI 54521 · Vilas County
Establishment
- Type
- Lodging (Tourist Rooming House - 1 TRH)
- Inspected by
- Vilas County Public Health
- License / ID
- ASPR-DJKNAJ
- Status
- Permitted
- Phone
- (720) 737-3040
- Official record
- Vilas County Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 5 | 2 |
| 2025 | 2 | 1 | 0 |
Inspections
-
Mar 5, 2026 Routine · 5 non-critical
-
Serious
Critical
Carbon monoxide alarm installation - FBA within IKU or sleeping room
A carbon monoxide alarm is not provided in the sleeping room with a FBA located in the closet.
Correction: Provide a carbon monoxide alarm with a fuel-burning appliance is located within the sleeping room or its attached bathroom.
Code ATCP 72.18(12)(b)
-
Serious
Critical
Hazardous substances - storage - original and labeled container
A closet consisting of containers of chemicals were not stored and secured in an area accessible only to staff in the main sleeping room.
Correction: Store chemicals, flammable materials, and other hazardous substances in a separate, secure area accessible only to staff, except for chemicals used for utensil sanitization.
Code ATCP 72.19(3)(b)2.
-
Not serious
Priority Foundation
Smoke alarm installed outside each separate sleeping area
A smoke alarm is not provided outside of each separate sleeping area, within 21 feet of any door to a sleeping room. The hallway does not have a smoke alarm.
Correction: Provide a smoke alarm outside of each separate sleeping area, within 21 feet of any door to a sleeping room.
Code ATCP 72.18(11)(b)2.
-
Not serious
Priority Foundation
Bunk beds - 2.5' spacing between beds
A vertical separation of less than 2.5 feet measured from the top of the lower mattress to the bottom of the frame of the upper bunk bed was observed in sleeping room with FBA.
Correction: Provide a vertical separation of at least 2.5 feet measured from the top of the lower mattress to the bottom of the frame of the upper bunk bed.
Code ATCP 72.18(3)(d)2.
-
Not serious
Priority Foundation
Building evacuation diagram (TRH) - posted or provided
The building evacuation diagram is not conspicuously posted in each sleeping room or is not provided in the check-in materials.
Correction: Post the building evacuation diagram in each sleeping room or provide in the check-in materials given to guests.
Code ATCP 72.18(6)(b)1.
-
Serious
Critical
-
Nov 5, 2025 Follow Up · No items found
No violations cited.
-
Jul 14, 2025 Pre-inspection · 1 non-critical
-
Not serious
Non-critical
PRIVATE WELL-WATER UNSAFE; POTABLE WATER PROVISIONS
The well water from the well servicing this property has been determined by laboratory analysis to be unsafe per DNR 809 standards.
Correction: Provide safe potable water from a tested and approved source on a temporary basis until the well is tested safe or a new well is drilled and the water is determined safe. Immediately discontinue use of the well's water supply for drinking, cooking and ice making purposes. Bathing is OK. Provide bottled water and ice supply from an approved source until a safe on-premise water supply is available.
Code [E] ATCP 72.10 (3)
-
Not serious
Non-critical
Source: Vilas County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.