Acorn Lodge - Whirlpool

10370 MAIN ST, Boulder Junction, WI 54512 · Vilas County

15cited violations
8serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
Vilas County Public Health
License / ID
ASPR-9VJHRX
Status
Permitted
Phone
(715) 385-2150
Official record
Vilas County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262136
2024111
2023111

Inspections

  1. Sep 29, 2026 Re-inspection · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The whirlpool flowmeter is not being maintained in operating condition. The psi gauge on flowmeter is not functioning at the time of inspection.

      Correction: Repair or replace the flowmeter for the whirlpool.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Current VGBA drain cover installed 2017 and expired in 2022.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Current VGBA drain cover installed 2017 and expired in 2022. No updated logs of the VGBA drain cover maintenance.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  2. Aug 31, 2026 Routine · 6 critical, 4 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The whirlpool flowmeter is not being maintained in operating condition. The psi gauge on flowmeter is not functioning at the time of inspection.

      Correction: Repair or replace the flowmeter for the whirlpool.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is <10 ppm at the time of inspection.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Current VGBA drain cover installed 2017 and expired in 2022.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Current VGBA drain cover installed 2017 and expired in 2022. No updated logs of the VGBA drain cover maintenance.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      RECIRCULATION SYSTEM CONTINUOUS OPERATION

      The pool recirculation system is not operational or not continuously operated. The facility does not have chemical interlock feeder system to dispense chemicals into the pool.

      Correction: The pool must be closed immediately until the recirculation system is in place and in continuous operation.

      Code ATCP 76.11(1) - RECIRCULATION SYSTEM PRESENT, CONTINUOUSLY O

    • Serious Critical

      INTERLOCK-PRESENT (Electrical or Flow)

      Recirculation system not equipped with either electrical or flow interlock.

      Correction: Install proper chemical feed interlocks.

      Code ATCP 76.13(1)(c) - INTERLOCK OF EITHER TYPE PRESENT

    • Serious Critical

      AUTOMATIC AND CONTINUOUS DISINFECTION

      Pool not automatically and continuously disinfected by means of disinfectant or sanitizer and feeding equipment. The facility does not provide an automatic recirculation system to dispense chemicals into the pool

      Correction: Ensure that each pool in use is automatically and continuously disinfected by means of disinfectant or sanitizer and feeding equipment that is in compliance with this section and s. ATCP 76.13.

      Code ATCP 76.14 (1) - AUTOMATIC DISINFECTION

    • Serious Critical

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

    • Serious Critical

      CLOSING CRITERIA-NON-OPERATIONAL RECIRD PUMP

      The Responsible Supervisor or operator has not closed the pool when there is a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder. No disinfectant or sanitizer feeder is present at this facility.

      Correction: Close the pool in the event of a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder.

      Code ATCP 76.30 (1)(d) - NON-OPERATIONAL RECIRC PUMP

    • Serious Critical

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The Responsible Supervisor or operator has not closed the pool due to a nonfunctional emergency phone.

      Correction: Close the pool in the event of a nonfunctional emergency phone.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

  3. Oct 25, 2024 Routine · 1 critical, 1 repeat
    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 0.32 (Liquid Chlorine)

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Proof of correction was not submitted to the department Friday afternoon. Re-inspection is required.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  4. Oct 13, 2023 Routine · 1 critical
    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 1.53 ppm for Free Chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Operator was taking corrective action to adjust free chlorine level during inspection.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

Source: Vilas County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.