Acorn Lodge - Whirlpool
10370 MAIN ST, Boulder Junction, WI 54512 · Vilas County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Vilas County Public Health
- License / ID
- ASPR-9VJHRX
- Status
- Permitted
- Phone
- (715) 385-2150
- Official record
- Vilas County Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 13 | 6 |
| 2024 | 1 | 1 | 1 |
| 2023 | 1 | 1 | 1 |
Inspections
-
Sep 29, 2026 Re-inspection · 3 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The whirlpool flowmeter is not being maintained in operating condition. The psi gauge on flowmeter is not functioning at the time of inspection.
Correction: Repair or replace the flowmeter for the whirlpool.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Current VGBA drain cover installed 2017 and expired in 2022.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Current VGBA drain cover installed 2017 and expired in 2022. No updated logs of the VGBA drain cover maintenance.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Not serious
Non-critical
Repeat
-
Aug 31, 2026 Routine · 6 critical, 4 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The whirlpool flowmeter is not being maintained in operating condition. The psi gauge on flowmeter is not functioning at the time of inspection.
Correction: Repair or replace the flowmeter for the whirlpool.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is <10 ppm at the time of inspection.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Current VGBA drain cover installed 2017 and expired in 2022.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Current VGBA drain cover installed 2017 and expired in 2022. No updated logs of the VGBA drain cover maintenance.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Serious
Critical
RECIRCULATION SYSTEM CONTINUOUS OPERATION
The pool recirculation system is not operational or not continuously operated. The facility does not have chemical interlock feeder system to dispense chemicals into the pool.
Correction: The pool must be closed immediately until the recirculation system is in place and in continuous operation.
Code ATCP 76.11(1) - RECIRCULATION SYSTEM PRESENT, CONTINUOUSLY O
-
Serious
Critical
INTERLOCK-PRESENT (Electrical or Flow)
Recirculation system not equipped with either electrical or flow interlock.
Correction: Install proper chemical feed interlocks.
Code ATCP 76.13(1)(c) - INTERLOCK OF EITHER TYPE PRESENT
-
Serious
Critical
AUTOMATIC AND CONTINUOUS DISINFECTION
Pool not automatically and continuously disinfected by means of disinfectant or sanitizer and feeding equipment. The facility does not provide an automatic recirculation system to dispense chemicals into the pool
Correction: Ensure that each pool in use is automatically and continuously disinfected by means of disinfectant or sanitizer and feeding equipment that is in compliance with this section and s. ATCP 76.13.
Code ATCP 76.14 (1) - AUTOMATIC DISINFECTION
-
Serious
Critical
TELEPHONE ACCESSIBLE
A telephone or other approved communication technology capable of connecting to emergency services is not working.
Correction: Provide a working telephone or other technology capable of connecting with emergency services.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Serious
Critical
CLOSING CRITERIA-NON-OPERATIONAL RECIRD PUMP
The Responsible Supervisor or operator has not closed the pool when there is a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder. No disinfectant or sanitizer feeder is present at this facility.
Correction: Close the pool in the event of a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder.
Code ATCP 76.30 (1)(d) - NON-OPERATIONAL RECIRC PUMP
-
Serious
Critical
CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE
The Responsible Supervisor or operator has not closed the pool due to a nonfunctional emergency phone.
Correction: Close the pool in the event of a nonfunctional emergency phone.
Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE
-
Not serious
Non-critical
-
Oct 25, 2024 Routine · 1 critical, 1 repeat
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.32 (Liquid Chlorine)
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Proof of correction was not submitted to the department Friday afternoon. Re-inspection is required.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
-
Oct 13, 2023 Routine · 1 critical
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1.53 ppm for Free Chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Operator was taking corrective action to adjust free chlorine level during inspection.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Source: Vilas County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.