Birchwood Resort

7739 BIRCHWOOD DR, Saint Germain, WI 54558 · Vilas County

27cited violations
6serious tier
5inspections

Establishment

Type
Lodging (Tourist Rooming House - 10 - 19 TRH)
Inspected by
Vilas County Public Health
License / ID
AMAN-C3US7Q
Status
Permitted
Official record
Vilas County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20261102
2025162
2024140
2023272

Inspections

  1. Jul 22, 2026 Routine · 10 non-critical
    • Serious Critical

      Smoke alarms provided

      Smoke alarms are not provided at the top of the stairs in the Lodge & Unit #7.

      Correction: Provide smoke alarms within each individually keyed unit at the locations specified in rule.

      Code ATCP 72.18(11)(a)

    • Serious Critical

      Carbon monoxide alarm installation - FBA within IKU or sleeping room

      Lodge - A carbon monoxide alarm is not provided in the basement sleeping room with the furnace in the closet. Lodge - A carbon monoxide alarm is not provided outside of the basement sleeping rooms. (Place in basement living room area) Unit #11 - Carbon mononide alram is placed at the ceiling in the living room. (Move lower)

      Correction: Provide a carbon monoxide alarm outside of each separate sleeping area within 21 feet of any door to a sleeping room and in each sleeping room, if a fuel-burning appliance is located within the sleeping room or its attached bathroom.

      Code ATCP 72.18(12)(b)

    • Not serious Priority Foundation

      Smoke alarm installed outside each separate sleeping area

      A smoke alarm is not provided outside of each separate sleeping area, within 21 feet of any door to a sleeping room. The upstairs (kitchen) bedroom area does not have a smoke alarm.

      Correction: Provide a smoke alarm outside of each separate sleeping area, within 21 feet of any door to a sleeping room.

      Code ATCP 72.18(11)(b)2.

    • Not serious Priority Foundation

      Smoke alarm installed in each sleeping room

      A smoke alarm is not within each sleeping room. The Lodge basement sleeping area/living room/futon area does not have a smoke alarm. The bedrooms of Unit #11 do not have smoke alarms inside the bedrooms.

      Correction: Provide a smoke alarm within each sleeping room.

      Code ATCP 72.18(11)(b)3.

    • Not serious Priority Foundation

      Guards provided on stairs > 3 risers

      Guards are not provided on all open sides of the stairs leading to the basement in the Lodge.

      Correction: Guards shall be provided on all open sides of stairs consisting of more than 3 risers.

      Code ATCP 72.18(2)(b)1.

    • Not serious Priority Foundation

      Stairs - area formed by riser, tread, bottom guard <= 8"

      Deck staircase: The triangular area formed by the tread, riser and bottom guard on the is more than 8 inches in width.

      Correction: Modify the triangular area formed by the tread, riser and bottom guard on the deck staircase to be equal to or less than 8 inches in width.

      Code ATCP 72.18(2)(b)5.

    • Not serious Priority Foundation

      Bed spacing >= 2' egress aisle

      Lodge - Upstairs bedroom on the right (living room) Beds are not arranged to provide an aisle at least 2 feet in width from one side of each bed to create a clear path for emergency egress.

      Correction: Rearrange or remove bed(s) to provide an aisle at least 2 feet in width from one side of each bed to create a clear path for emergency egress.

      Code ATCP 72.18(3)(b)1.

    • Not serious Priority Foundation

      Bunk beds - 2.5' spacing between beds

      A vertical separation of less than 2.5 feet measured from the top of the lower mattress to the bottom of the frame of the upper bunk bed was observed in Unit #11

      Correction: Provide a vertical separation of at least 2.5 feet measured from the top of the lower mattress to the bottom of the frame of the upper bunk bed (Unit #11)

      Code ATCP 72.18(3)(d)2.

    • Not serious Priority Foundation

      Building evacuation diagram (TRH) - posted or provided

      The building evacuation diagram is not conspicuously posted in each sleeping room or is not provided in the check-in materials.

      Correction: Post the building evacuation diagram in each sleeping room or provide in the check-in materials given to guests.

      Code ATCP 72.18(6)(b)1.

    • Not serious Non-critical

      Common areas maintained in good repair

      Renter reports: the kitchen faucet is leaking onto the floor and the upstairs master bedroom shower seal is leaking onto the floor. Renter reports: Deck railing not secure/moves. Deck boards separating. Inspectors confirms.

      Correction: Maintain all common areas in a good repair.

      Code ATCP 72.19(1)(b)3

  2. Sep 4, 2025 Routine · 2 critical, 3 non-critical
    • Not serious Non-critical

      TOP BUNK-MISSING RAILS

      Guard railings on top bunk are less than 5 inches above the mattress in Cabin #8.

      Correction: Install railings that are in compliance with 16 CFR 1513. Raise guard rail height to sit at least 5 inches above the mattress.

      Code Wisconsin Statute 97.02

    • Not serious Non-critical

      UTENSIL SANITIZATION - CLEANING PROCEDURES

      Utensils/dishes sanitization procedure notice not found in the facility. The inspector left a copy of notice on the counter which must be displayed in public view for guests. No bleach provided for guests to properly sanitize in cabin 9.

      Correction: All multi-use utensils must be washed, rinsed and sanitized using approved methods, equipment and chemicals. Provide approved 3 compartment sink or approved commercial dish machine for this purpose. If there is no santizer on dishwashing unit, bleach must be provided to guests in order to properly disinfect dishes. Provide means of testing hot water sanitization, if applicable. No utensils for foo

      Code [A] ATCP 72.11 (3)(a)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      The standing shower in Cabin #1 is rusting on the bottom and bowing away from the wall.

      Correction: Shower walls should be updated, replaced, or cleaned in a manner conducive to the health, comfort and safety of its guests.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      Crawl space access door in Cabin #9 is unlocked and available to guests.

      Correction: Trim keeping the door inaccessible is insufficient. We reccommend locking this hatch so their is no health and safety risk to guests.

      Code [C] ATCP 72.15 (1)

    • Serious Critical

      SMOKE DETECTORS - REQUIREMENT

      Smoke detectors are absent in cabin #9 and are not in working order in cabin #1.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations.

      Code ATCP 72.14 (2) (c)

    • Serious Critical

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      A carbon monoxide detector is not provided [in Cabin 9, outside of each separate sleeping area (identify area) in the immediate vicinity of the sleeping rooms and/or in sleeping rooms, where a fuel-burning appliance is located].

      Correction: Provide carbon monoxide detectors in all required locations.

      Code [A] ATCP 72.145 (3)

  3. Jun 4, 2024 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      INSECT AND RODENT CONTROL

      Mice are present in Cabin #1 - live mouse found stuck to a rodent glue trap.

      Correction: Contact a pest control company to evaluate and eliminate the presence and harborage of insects and rodents.

      Code ATCP 72.15 (3)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      Guard spacing of deck for cabin #7 measures 9 inches to 18 inches.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests. Update guard spacing to meet code standards within 90 days (by September 2, 2024). Submit proof of updated guards to Sarah at 715-891-0042 or zeltens@uwosh.edu. Reinspection is required and $128 reinspection fee will be charged.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical Repeat

      GENERAL MAINTENANCE

      Hot water heaters in Cabins #1 & #6 did not have piping from pressure relief valve down to flooring.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests. Install piping from pressure relief valve down to floor within 1 month (by July 4, 2024). Submit proof of installation to Sarah at 715-891-0042 or zeltens@uwosh.edu.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      Handrail of spiral staircase in cabin 1 is sheered off, and is not maintained or in good repair.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests. Repair/replace handrail within 90 days (by September 2, 2024). Send proof of repair/replacement to Sarah at 715-891-0042 or zeltens@uwosh.edu.

      Code [C] ATCP 72.15 (1)

  4. Sep 12, 2023 Re-inspection · 1 critical, 3 non-critical, 3 repeat
    • Not serious Non-critical

      SLEEPING ROOMS - SIZE

      Futon is present in four season porch area where ceiling height is 78.5-79 inches.

      Correction: Reduce occupancy to meet minimum size and space requirements.Please remove futon from four season porch area as it does not meet ceiling height requirements for a sleeping area.

      Code ATCP 72.14 (2) (b)

    • Not serious Non-critical Repeat

      GENERAL MAINTENANCE

      Hot water heater in Cabins #5 did not have pipe from pressure relief valve down to floor.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests. Please have these installed and provide proof via photo emailed to zeltens@uwosh.edu within 2 weeks.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical Repeat

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      A carbon monoxide detector is not provided in unit 5, outside of each separate sleeping area in the immediate vicinity of the sleeping rooms and/or in sleeping rooms, where a fuel-burning appliance is located.

      Correction: Provide carbon monoxide detectors in all required locations. Please correct prior to re-inspection of cabin #5.

      Code [A] ATCP 72.145 (3)

    • Serious Critical Repeat

      PLUMBING FIXTURES – GOOD REPAIR

      The following plumbing or fixtures are not in good repair in cabin 5: bathroom sink is cracked; toilet is missing top over tank.

      Correction: Maintain plumbing and fixtures in good repair. Cabin 5 cannot be rented until corrected. Please call Sarah at 715-479-3758 or email at zeltens@uwosh.edu once repairs have been completed to schedule re-inspection.

      Code [B] ATCP 72.10 (4)

  5. Jun 15, 2023 Routine · 1 critical, 2 non-critical
    • Not serious Non-critical

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      A carbon monoxide detector is not provided in unit 5, outside of each separate sleeping area in the immediate vicinity of the sleeping rooms and/or in sleeping rooms, where a fuel-burning appliance is located.

      Correction: Provide carbon monoxide detectors in all required locations. Please correct prior to re-inspection of cabin #5.

      Code [A] ATCP 72.145 (3)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      Hot water heaters in Cabins #1 & 5 did not have pipe from pressure relief valve down to floor.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests. Please have these installed and provide proof via photo emailed to zeltens@uwosh.edu within 2 weeks.

      Code [C] ATCP 72.15 (1)

    • Serious Critical

      PLUMBING FIXTURES – GOOD REPAIR

      The following plumbing or fixtures are not in good repair in cabin 5: bathroom sink is cracked; toilet is missing top over tank.

      Correction: Maintain plumbing and fixtures in good repair. Cabin 5 cannot be rented until corrected. Please call Sarah at 715-479-3758 or email at zeltens@uwosh.edu once repairs have been completed to schedule re-inspection.

      Code [B] ATCP 72.10 (4)

Source: Vilas County Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.