Lake Park West (outdoor Pool)
W169N11565 N BISCAYNE DR, Germantown, WI 53022 · Washington County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Washington Ozaukee Public Health
- License / ID
- HSAT-7QWBRQ
- Status
- Permitted
- Phone
- (414) 534-5709 ext. Bill (maintenance)
- Official record
- Washington Ozaukee Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 0 | 0 |
| 2025 | 2 | 1 | 1 |
| 2024 | 3 | 8 | 2 |
| 2023 | 1 | 0 | 0 |
Inspections
-
Jun 12, 2026 Routine · No items found
No violations cited.
-
Jun 11, 2025 Routine · 1 critical
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
This pool is required to have 1.0 PPM chlorine (no CYA used). During the inspection a chlorine residual of 0.4 was found.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
-
Jun 11, 2025 Follow Up · No items found
No violations cited.
-
Aug 26, 2024 Follow Up · 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
FILTER MEDIA INSPECTED ANNUALLY
Filter media is not being inspected annually.
Correction: Inspect the filters annually and clean and replace media as needed.
Code ATCP 76.11(6)(a) 5. - FILTER MEDIA INSPECTED ANNUALLY
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. Inspector left a copy of the combined chlorine management template with the operator.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
-
Jul 3, 2024 Follow Up · 1 critical, 2 non-critical, 1 repeat
-
Not serious
Non-critical
FILTER MEDIA INSPECTED ANNUALLY
Filter media is not being inspected annually.
Correction: Inspect the filters annually and clean and replace media as needed.
Code ATCP 76.11(6)(a) 5. - FILTER MEDIA INSPECTED ANNUALLY
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. Inspector left a copy of the combined chlorine management template with the operator.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
Repeat
INTERLOCKED-ELECTRICAL
Power to recirculation system is not interlocked with the power to the liquid chlorine feed.
Correction: Provide interlock between the power to the recirculation system and power to the chemical feeder.
Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT
-
Not serious
Non-critical
-
May 24, 2024 Routine · 1 critical, 2 non-critical
-
Not serious
Non-critical
FILTER MEDIA INSPECTED ANNUALLY
Filter media is not being inspected annually.
Correction: Inspect the filters annually and clean and replace media as needed.
Code ATCP 76.11(6)(a) 5. - FILTER MEDIA INSPECTED ANNUALLY
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. Inspector left a copy of the combined chlorine management template with the operator.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
INTERLOCKED-ELECTRICAL
Power to recirculation system is not interlocked with the power to the liquid chlorine feed.
Correction: Provide interlock between the power to the recirculation system and power to the chemical feeder.
Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT
-
Not serious
Non-critical
-
Jun 7, 2023 Routine · No items found
No violations cited.
Source: Washington Ozaukee Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.