Hampton Inn & Suites - West Bend-pool

1975 S 18TH AVE, West Bend, WI 53095 · Washington County

17cited violations
4serious tier
6inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Washington Ozaukee Public Health
License / ID
HSAT-7QWMBX
Status
Permitted
Phone
(262) 438-1500
Official record
Washington Ozaukee Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026230
2025261
2024183
2023100

Inspections

  1. Nov 12, 2026 Follow Up · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is 240.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. The pool was being filled during inspection so it is likely that the high alkalinity of the source water is causing the pool alkalinity to be at this level.

      Code ATCP 76.14(5)(d) - ALKALINITY

  2. Jul 8, 2026 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 240.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. The pool was being filled during inspection so it is likely that the high alkalinity of the source water is causing the pool alkalinity to be at this level.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The pool is only tested the 5 days a maintaince staff member is working but the other two days the pool is not tested.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

  3. Dec 15, 2025 Routine · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The pool is not tested on weekends.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

  4. Jan 16, 2025 Routine · 1 critical, 4 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool. Inspector will send over a copy of the combined chlorine management template that can be used to meet this requirement.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level. On January 16th, when this inspection took place, only two tests for combined chlorine had occurred this month.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity. On January 16th, when this inspection occurred, only one alkalinity test had been taken this month.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The pool is only tested Monday to Friday and no tests on weekends have been occurring.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

    • Serious Critical Corrected on site

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions. This was done during the inspection.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

  5. Apr 24, 2024 Routine · 3 critical, 5 non-critical
    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool. A copy of the combined chlorine management plan was given to the operator at the time of inspection.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The primary operator has been out sick multiple days this month and no other staff member tested the pool during the absence.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

    • Not serious Non-critical

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available.

      Correction: Provide a biohazard kit for the pool. It is recommended to contact your chemical supplier to obtain a kit for the pool area. Please see ATCP 76 for the required contents of the biohazard kit.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Serious Critical

      OPERATOR KNOWLEDGE- ELECTRICAL INTERLOCK FUNCTION

      The person responsible is not able to describe how the chemical feeder electrical interlock functions.

      Correction: Ensure that operator can describe how the chemical feeder electrical interlock functions. Inspector is going to send the operator a copy of the chemical interlock checklist so the operator know what components he/she must understand.

      Code ATCP 76.13 (1)(c)2.b - HOW ELECTRICAL INTERLOCK FUNCTIONS

    • Serious Critical

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock. The monthly main pool log pump safety check completed has been marked for this month but no interlock challenge test was completed.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock. When completed, mark the pump safety check completed box.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

    • Serious Critical

      HAZARDOUS CONDITION

      There is a hazardous condition at the pool. The facility does not have record of when the pool side equalizer VGBA covers need to be replaced.

      Correction: Correct the hazardous condition. In accordance with DATCP REC-POL-014 replace the side equalizer VGBA covers before the next routine inspection. Keep receipts so the model number and date of purchase is available in writing.

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  6. May 16, 2023 Routine · No items found

    No violations cited.

Source: Washington Ozaukee Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.