Hampton Inn & Suites - West Bend-pool
1975 S 18TH AVE, West Bend, WI 53095 · Washington County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Washington Ozaukee Public Health
- License / ID
- HSAT-7QWMBX
- Status
- Permitted
- Phone
- (262) 438-1500
- Official record
- Washington Ozaukee Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 3 | 0 |
| 2025 | 2 | 6 | 1 |
| 2024 | 1 | 8 | 3 |
| 2023 | 1 | 0 | 0 |
Inspections
-
Nov 12, 2026 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 240.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. The pool was being filled during inspection so it is likely that the high alkalinity of the source water is causing the pool alkalinity to be at this level.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
-
Jul 8, 2026 Routine · 2 non-critical, 1 repeat
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 240.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. The pool was being filled during inspection so it is likely that the high alkalinity of the source water is causing the pool alkalinity to be at this level.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING FREQUENCY OF TESTING
The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The pool is only tested the 5 days a maintaince staff member is working but the other two days the pool is not tested.
Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.
Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ
-
Not serious
Non-critical
-
Dec 15, 2025 Routine · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING FREQUENCY OF TESTING
The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The pool is not tested on weekends.
Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.
Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ
-
Not serious
Non-critical
Repeat
-
Jan 16, 2025 Routine · 1 critical, 4 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. Inspector will send over a copy of the combined chlorine management template that can be used to meet this requirement.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level. On January 16th, when this inspection took place, only two tests for combined chlorine had occurred this month.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
ALKALINITY TEST
Pool water not tested at least once a week for total alkalinity. On January 16th, when this inspection occurred, only one alkalinity test had been taken this month.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING FREQUENCY OF TESTING
The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The pool is only tested Monday to Friday and no tests on weekends have been occurring.
Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.
Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ
-
Serious
Critical
Corrected on site
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions. This was done during the inspection.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
Repeat
-
Apr 24, 2024 Routine · 3 critical, 5 non-critical
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. A copy of the combined chlorine management plan was given to the operator at the time of inspection.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
ELECTRONIC MONITORING FREQUENCY OF TESTING
The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. The primary operator has been out sick multiple days this month and no other staff member tested the pool during the absence.
Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.
Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ
-
Not serious
Non-critical
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool. It is recommended to contact your chemical supplier to obtain a kit for the pool area. Please see ATCP 76 for the required contents of the biohazard kit.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Serious
Critical
OPERATOR KNOWLEDGE- ELECTRICAL INTERLOCK FUNCTION
The person responsible is not able to describe how the chemical feeder electrical interlock functions.
Correction: Ensure that operator can describe how the chemical feeder electrical interlock functions. Inspector is going to send the operator a copy of the chemical interlock checklist so the operator know what components he/she must understand.
Code ATCP 76.13 (1)(c)2.b - HOW ELECTRICAL INTERLOCK FUNCTIONS
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock. The monthly main pool log pump safety check completed has been marked for this month but no interlock challenge test was completed.
Correction: Challenge test the chemical feeder system monthly to assess the interlock. When completed, mark the pump safety check completed box.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
HAZARDOUS CONDITION
There is a hazardous condition at the pool. The facility does not have record of when the pool side equalizer VGBA covers need to be replaced.
Correction: Correct the hazardous condition. In accordance with DATCP REC-POL-014 replace the side equalizer VGBA covers before the next routine inspection. Keep receipts so the model number and date of purchase is available in writing.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
-
May 16, 2023 Routine · No items found
No violations cited.
Source: Washington Ozaukee Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.