Timber Trail Campground
7590 GOOD LUCK LN, West Bend, WI 53090 · Washington County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Washington Ozaukee Public Health
- License / ID
- HSAT-7QXPFL
- Status
- Permitted
- Phone
- (262) 338-8561
- Official record
- Washington Ozaukee Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 11 | 4 |
| 2025 | 1 | 2 | 1 |
| 2024 | 1 | 4 | 2 |
| 2023 | 1 | 0 | 0 |
Inspections
-
Jul 13, 2026 Follow Up · 1 critical, 3 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. The PSI gauge on the sand filter is damaged.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
TEST KIT APPROVED
There is no approved test kit available for monitoring chemical concentrations of water.
Correction: Obtain an approved test kit.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
Repeat
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device in showers.
Correction: Provide soap in a permanently-installed dispensing device in showers.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
The main drain covers are each missing a screw. The metal frame around the perimeter of the whirlpool is pulling away from the wall and creating a hazardous condition.
Correction: Correct the hazardous conditions by replacing screws and repairing metal frame.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Repeat
-
Jun 9, 2026 Routine · 3 critical, 4 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. The PSI gauge on the sand filter is damaged.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
TEST KIT APPROVED
There is no approved test kit available for monitoring chemical concentrations of water.
Correction: Obtain an approved test kit.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Bromine, pH, and alkalinity.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device in showers.
Correction: Provide soap in a permanently-installed dispensing device in showers.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Serious
Critical
MAXIMUM BROMINE
The maximum total bromine exceeds 10 ppm.
Correction: Close the pool until the total bromine residual is in compliance with Table ATCP 76.14 Table A.
Code ATCP 76.14(5)(g) -MAXIMUM BROMINE
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Serious
Critical
HAZARDOUS CONDITION
The main drain covers are each missing a screw. The metal frame around the perimeter of the whirlpool is pulling away from the wall and creating a hazardous condition.
Correction: Correct the hazardous conditions by replacing screws and repairing metal frame.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Repeat
-
Jun 10, 2025 Routine · 1 critical, 1 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter gauge is not being maintained in operating condition. The PSI gauge on sand filter is not operating.
Correction: Adjust or repair the flowmeter gauge and sand filter gauge.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Serious
Critical
Repeat
TELEPHONE ACCESSIBLE
A telephone or other approved communication technology capable of connecting to emergency services is not working.
Correction: Provide a working telephone or other technology capable of connecting with emergency services.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Not serious
Non-critical
Repeat
-
Jun 17, 2024 Routine · 2 critical, 2 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The whirlpool flowmeter is not being maintained in operating condition.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 270 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Serious
Critical
TELEPHONE ACCESSIBLE
A telephone or other approved communication technology capable of connecting to emergency services is not working.
Correction: Provide a working telephone or other technology capable of connecting with emergency services.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Serious
Critical
DRINKING FOUNTAIN PROVIDED
The drinking fountain is not operating.
Correction: Repair drinking fountain.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Not serious
Non-critical
-
Jun 19, 2023 Routine · No items found
No violations cited.
Source: Washington Ozaukee Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.