Hartford Square Condo (whirlpool)
400 HARTFORD SQUARE, Hartford, WI 53027 · Washington County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Washington Ozaukee Public Health
- License / ID
- HSAT-7QWSAQ
- Status
- Permitted
- Phone
- (262) 457-2231
- Official record
- Washington Ozaukee Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 0 | 0 |
| 2025 | 2 | 4 | 2 |
| 2024 | 1 | 3 | 0 |
| 2023 | 1 | 1 | 0 |
Inspections
-
Nov 13, 2026 Routine · No items found
No violations cited.
-
May 30, 2025 Follow Up · 1 critical, 1 non-critical
-
Not serious
Non-critical
POOL DECK-GOOD REPAIR
There are a few areas on the pool deck that are deteriorating exposing potentially hazardous areas.
Correction: Maintain pool deck area in good repair. Repair/Resurface the hazardous areas observed.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Serious
Critical
Corrected on site
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm. The measured amount at the initial routine inspection was at 21.8ppm. At the time of the follow up inspection, the level was measured at 4.8ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Not serious
Non-critical
-
May 22, 2025 Routine · 1 critical, 1 non-critical
-
Not serious
Non-critical
POOL DECK-GOOD REPAIR
There are a few areas of the pool deck that are coming apart exposing potentially hazardous areas
Correction: Maintain pool deck area in good repair. Repair/Resurface deteriorating areas of the pool deck.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm. Free chlorine measured at 21.8 ppm
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Not serious
Non-critical
-
May 20, 2024 Routine · 3 non-critical
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not available for review at the time of the inspection.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
FILES RETAINED 2 YEARS-ANY OTHER REPORTS REQUIRED
DII forms were not available at the time of the inspection. Additionally, new combined chlorine management plans and chemical interlock logs were not available at the time of the inspection.
Correction: Maintain required logs and sample forms for a minimum of 2 years.
Code ATCP 76.32(3)(b)5. - OTHER REPORT REQUIRED
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Not serious
Non-critical
-
Apr 27, 2023 Routine · 1 non-critical
-
Not serious
Non-critical
WORN PARTS NEEDING REPLACEMENT
The main grates and equalizers are in need of replacement as they are indicated to be in use past their expiration dates.
Correction: Repair/replace the component.
Code ATCP 76.37(1)(c)
-
Not serious
Non-critical
Source: Washington Ozaukee Public Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.