Towneplace Suites By Marriott
600 N CALHOUN RD, Brookfield, WI 53005 · Waukesha County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Waukesha County Environmental Health
- License / ID
- HDEH-A78KE8
- Status
- Permitted
- Phone
- (262) 784-8450
- Official record
- Waukesha County Environmental Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 4 | 7 | 4 |
| 2025 | 3 | 14 | 6 |
| 2023 | 1 | 3 | 0 |
Inspections
-
Aug 26, 2026 Re-inspection · 1 critical, 3 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. Observed with no pressure reading.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing for every day the pool is open for use.
Correction: Record the following on the operating report, results for chemical testing every day the pool is open for use.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
DRINKING FOUNTAIN MAINTAINED
The drinking fountain is not in working condition and able to provide water during inspection. Facility maintinance stated water may not be turned on and they need to access the room located on the other side of the wall to make adjustment. Room is currenlty in service and unable to turn on during inspection. Facility GM stated water will be turned on when room service is able to service the room.
Correction: Maintain the drinking fountain in clean and sanitary condition.
Code ATCP 76.33(1)(g)2.-DRINKING FOUNTAIN CLEAN
-
Serious
Critical
Corrected on site
INTERLOCK LOG-INFORMATION
The monthly testing log is missing or incomplete. CORRECTED Education was provided and facility shall complete logs indicating monthly interlock testing is being completed.
Correction: Maintain a log that is documented with the date, results, and the name of the person performing the interlock test.
Code ATCP 76.13 (1)(c)4.a - INTERLOCK LOG, INFORMATION REQUIRED
-
Not serious
Non-critical
-
Aug 25, 2026 Re-inspection 2 · 1 critical, 1 repeat
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0ppm for chlorine. Pool was closed at time of inspection and shall remain closed until free chlorine levels can be maintained above 1ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
-
Aug 21, 2026 Re-inspection · 1 critical
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is between 25ppm and 50ppm for chlorine. Pool was closed at time of inspection and shall remain closed until free chlorine levels can be maintained above 1ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
-
Aug 20, 2026 Routine · 1 critical
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0 for liquid chlorine. Pool was closed at time of inspection and shall remain closed until free chlorine levels can be maintained above 1ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
-
Jul 25, 2025 Follow Up · 2 critical, 2 repeat
-
Serious
Critical
Repeat
Corrected on site
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Chlorine is not stored separately from acid. CORRECTED chemicals voluntarily rearranged during inspection.
Correction: Store oxidizers separately from acids.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
Repeat
Corrected on site
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed. CORRECTED education was provided and new logs shall be sent with this report.
Correction: Ensure that operator can describe how monthly testing is performed.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Serious
Critical
Repeat
Corrected on site
-
Jul 17, 2025 Follow Up · 2 critical, 4 non-critical, 6 repeat
-
Not serious
Non-critical
Repeat
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Observed expired reagents during inspection.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
FILES RETAINED 2 YEARS-ANY OTHER REPORTS REQUIRED
During inspection, pool operator was not available and peraon in charge was unable to locate files with required reports.
Correction: Maintain on premises for 2 years any reports required by the department or its agent.
Code ATCP 76.32(3)(b)5. - OTHER REPORT REQUIRED
-
Serious
Critical
Repeat
Corrected on site
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Chlorine is not stored separately from acid. CORRECTED chemicals voluntarily rearranged during inspection.
Correction: Store oxidizers separately from acids.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
Repeat
Corrected on site
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed. CORRECTED education was provided and new logs shall be sent with this report.
Correction: Ensure that operator can describe how monthly testing is performed.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Not serious
Non-critical
Repeat
-
Jul 10, 2025 Routine · 2 critical, 4 non-critical
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Observed expired reagents during inspection.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
FILES RETAINED 2 YEARS-ANY OTHER REPORTS REQUIRED
During inspection, pool operator was not available and peraon in charge was unable to locate files with required reports.
Correction: Maintain on premises for 2 years any reports required by the department or its agent.
Code ATCP 76.32(3)(b)5. - OTHER REPORT REQUIRED
-
Serious
Critical
Corrected on site
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Chlorine is not stored separately from acid. CORRECTED chemicals voluntarily rearranged during inspection.
Correction: Store oxidizers separately from acids.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
Corrected on site
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed. CORRECTED education was provided and new logs shall be sent with this report.
Correction: Ensure that operator can describe how monthly testing is performed.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Not serious
Non-critical
-
Aug 10, 2023 Routine · 3 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flowmeter is not operational.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
WATER TESTING FREQUENCY - POOLS
The water testing frequency for combined chlorine is not in compliance with ATCP 76.18(1). Water testing has not been documented since 8/7/2023. Several days each month are not documented. Discussed that if the pool is closed on a particular day to indicate it on the chemical sheet. However, if the pool is open, then chemical recordings are required to be documented.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Non-critical
SKIMMER BASKET OR WEIR MISSING
The weir door is missing on the skimmer closes to the gate.
Correction: Replace the missing equipment.
Code [B] ATCP 76.11(2)(b)
-
Not serious
Non-critical
Repeat
Source: Waukesha County Environmental Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.