The Ruby At Brookfield Square
365 S MOORLAND RD, Brookfield, WI 53005 · Waukesha County
Establishment
- Type
- Pool / recreational water (Pool - Moderate with Features)
- Inspected by
- Waukesha County Environmental Health
- License / ID
- HDEH-D5JF4Z
- Status
- Permitted
- Phone
- (262) 330-0422
- Official record
- Waukesha County Environmental Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 2 | 1 |
| 2025 | 8 | 26 | 6 |
| 2024 | 2 | 7 | 0 |
Inspections
-
Jul 2, 2026 Re-inspection · 1 critical, 1 non-critical
-
Not serious
Non-critical
WATER HEATERS-MAINTAINED OPERATIONAL
Water heater or heat exchanger not in operating condition. Facility is aware of the issues with the water heater and are currently working to correct issues. Ambient outside air temperatures are ranging in the upper 80's and 90's for the next week. Facility pool temperatures are within code compliant range.
Correction: Maintain water heater or heat exchanger in operating condition.
Code ATCP 76.33(4)(a) - MAINTAINED
-
Serious
Critical
HAZARDOUS CONDITION
There is a hazardous condition at the pool. Pool left main drain observed missing 3 screws.
Correction: Correct the hazardous condition by installing all required screws in main drain.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
-
Jun 19, 2026 Follow Up · No items found
No violations cited.
-
Jun 18, 2026 Routine · No items found
No violations cited.
-
Aug 25, 2025 Follow Up · 3 non-critical, 2 repeat
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. Observed controller feeding acid when pH was recording above 8.0. Suggest repairing/replacing controller to correct set points.
Correction: Maintain the pool equipment by adjusting controller set points to be within a code compliant range.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one. Facility pool has had more than 2 re-inspections within a year. Facility is now required to obtain a certified operator for the pool by the time of opening next year.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Daily logging of Chlorine, pH and weekly alkylinity. Ensure all logging is completed on state approved daily log.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
-
Aug 22, 2025 Re-inspection 2 · 1 critical, 3 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 360 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one. Facility pool has had more than 2 re-inspections within a year. Facility is now required to obtain a certified operator for the pool by the time of opening next year.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Daily logging of Chlorine, pH and weekly alkylinity. Ensure all logging is completed on state approved daily log.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.07 for Chlorine. Facility voluntarily closed pool during inspection.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
Repeat
-
Aug 20, 2025 Re-inspection · 3 non-critical, 2 repeat
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 360 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one. Facility pool has had more than 2 re-inspections within a year. Facility is now required to obtain a certified operator for the pool by the time of opening next year.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Daily logging of Chlorine, pH and weekly alkylinity. Ensure all logging is completed on state approved daily log.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
-
Aug 8, 2025 Re-inspection · 1 critical, 1 repeat
-
Serious
Critical
Repeat
RESPONSIBLE SUPERVISOR MAINTAIN ORDER
During inspection, it was observed no chemical logging was recorder between 7/15/2025 and 7/22/2025. No pool closure was indicated on log sheets during this time.
Correction: Chemical logging shall be completed and logged every day the pool is open and operating.
Code ATCP 76.21 (1)(c)1. - MAINTAIN ORDER
-
Serious
Critical
Repeat
-
Jul 24, 2025 Follow Up · 1 critical, 1 repeat
-
Serious
Critical
Repeat
RESPONSIBLE SUPERVISOR MAINTAIN ORDER
During inspection, it was observed no chemical logging was recorder between 7/15/2025 and 7/22/2025. No pool closure was indicated on log sheets during this time.
Correction: Chemical logging shall be completed and logged every day the pool is open and operating.
Code ATCP 76.21 (1)(c)1. - MAINTAIN ORDER
-
Serious
Critical
Repeat
-
Jun 24, 2025 Re-inspection 2 · No items found
No violations cited.
-
Jun 20, 2025 Re-inspection · 2 critical, 6 non-critical, 6 repeat
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 640 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
Repeat
SKIMMERS MAINTAINED CLEAN
Skimmers, gutters, drains not maintained clean. Skimmers observed with debris buildup during inspection.
Correction: Maintain the skimmers in clean condition.
Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is between 40 and 50 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant. Loggine for all chemicals no tested or recorded daily on logs. Observed controller with alarm light flashing during inspection.
Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
Repeat
Corrected on site
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area. Corrected a service order for blankets were placed at the time of inspection.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
POOL RULES LETTER OR SYMBOL SIZE
Pool rules letters are less than 1 inches in height or symbols are less than 1 inches in height.
Correction: Correct the size of the letters or symbols, so that letters are at least one inch in height and symbols are at least 4 inches in height. Facilities manager stated that two of their pool rules sign broke over the winter and facility is ordering new signs. They should be arriving later next week. Current posted sign does not include all required pool rules. New sign shall include all rules as requir
Code ATCP 76.29(1)(a)2. -LETTER OR SYMBOL SIZE
-
Serious
Critical
Repeat
Corrected on site
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed. CORRECTED Education was provided and interlock testing shall be recorded monthly.
Correction: Ensure that operator can describe how monthly testing is performed.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Serious
Critical
CLOSING CRITERIA-FAILURE TO COMPLY WITH 76.14 OR PH LIMITS
The Responsible Supervisor or operator has not closed the pool after failure to comply with the disinfectant or sanitizer residual levels. During reinspection, pH observed above 8.0 and has been recorded above 8 for the past three days.
Correction: Close the pool in the event of failure to comply with the disinfectant or sanitizer residual levels pursuant to s. ATCP 76.14, or pH values that are less than 6.8 or equal to or greater than 8.0.
Code ATCP 76.30 (1)(c) - FAILURE TO COMPLY WITH ATCP 76.14
-
Not serious
Non-critical
-
Jun 12, 2025 Routine · 1 critical, 5 non-critical
-
Not serious
Non-critical
SKIMMERS MAINTAINED CLEAN
Skimmers, gutters, drains not maintained clean. Skimmers observed with debris buildup during inspection.
Correction: Maintain the skimmers in clean condition.
Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is between 40 and 50 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant. Loggine for all chemicals no tested or recorded daily on logs. Observed controller with alarm light flashing during inspection.
Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
Corrected on site
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area. Corrected a service order for blankets were placed at the time of inspection.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
POOL RULES LETTER OR SYMBOL SIZE
Pool rules letters are less than 1 inches in height or symbols are less than 1 inches in height.
Correction: Correct the size of the letters or symbols, so that letters are at least one inch in height and symbols are at least 4 inches in height. Facilities manager stated that two of their pool rules sign broke over the winter and facility is ordering new signs. They should be arriving later next week. Current posted sign does not include all required pool rules. New sign shall include all rules as requir
Code ATCP 76.29(1)(a)2. -LETTER OR SYMBOL SIZE
-
Serious
Critical
Corrected on site
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed. CORRECTED Education was provided and interlock testing shall be recorded monthly.
Correction: Ensure that operator can describe how monthly testing is performed.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Not serious
Non-critical
-
Jun 4, 2024 Pre-inspection Follow Up · No items found
No violations cited.
-
May 23, 2024 Pre-inspection · 7 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter was non-operational during inspection.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
CARTRIDGE FILTERS DUPLICATE SET
There is not a replacement set of cartridge filter for the spray feature.
Correction: Provide a duplicate set of cartridge filter.
Code ATCP 76.11(6)(d) 3. - DUPLICATE SET
-
Not serious
Non-critical
TEST KIT APPROVED
The facility has a Taylor K-2005 kit. Kit information will be emailed with this report.
Correction: Provide an approved kit.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
SIGNAGE 'NO LIFEGUARD ON DUTY'
The "Warning: No Lifeguard on Duty" sign is in one inch lettering.
Correction: Provide a sign to indicate 'no lifeguard on duty' in letters no smaller than 4 inches.
Code ATCP 76.23(2)- NO LIFEGUARD ON DUTY
-
Not serious
Non-critical
POOL RULES POSTED
There is not a sign that provides all of the following rules in one inch lettering: a. Do not enter the pool if you have a communicable disease or an open cut. b. Do not bring food, drink, gum, or tobacco into the pool. c. Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities. d. Do not run or engage in rough play in the pool area. e. Do not bring animals into the pool area. f. Diaper changing on the pool deck is prohibited. g. Glass and shatterable items are prohibited in the pool area.
Correction: Post the pool rules.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Not serious
Non-critical
POSTING SIGNAGE-NO DIVING
No-Diving signage is less than 4 inch lettering.
Correction: Post signage indicating No-Diving.
Code ATCP 76.29(1)(d) - NO DIVING
-
Not serious
Non-critical
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Not serious
Non-critical
Source: Waukesha County Environmental Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.