Apple Valley Gardens Condominiums
N84W16033 MENOMONEE AVE, Menomonee Falls, WI 53051 · Waukesha County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Waukesha County Environmental Health
- License / ID
- HSAT-96F3JV
- Status
- Permitted
- Official record
- Waukesha County Environmental Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 19 | 10 |
| 2025 | 4 | 10 | 4 |
Inspections
-
Jul 6, 2026 Re-inspection · 2 critical, 1 non-critical
-
Not serious
Non-critical
Corrected on site
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The operator backwashed the sand filter during the inspection, bringing the flow rate up to 100 GPM and the turnover rate down to 6 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Serious
Critical
RESPONSIBLE SUPERVISOR SANITATION AND TESTING
- The controller is observed to be reading 7.6 during the inspection, the feed light was on, but the acid pump was not turning/feeding. - The controller is observed to be reading 730 during the inspection and the set point is 650. The operator was unable to adjust the set point for the ORP during the inspection.
Correction: Have the responsible supervisor ensure that sanitation and testing duties are performed. The pool operator shall submit the daily operating reports to the sanitarian via email weekly.
Code ATCP 76.21 (1)(c)4. - SANITAITON AND TESTING
-
Serious
Critical
HAZARDOUS CONDITION
The main drain cover is expired; replace the main drain cover. The operator must log daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or defects are observed. The operator shall close the pool if any damage or defects are observed.
Correction: Correct the hazardous conditions.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Corrected on site
-
Jun 26, 2026 Re-inspection · 3 critical, 4 non-critical, 7 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition. This is a repeat violation. It was documented during the last inspection and again today. This violation shall be corrected prior to the next routine inspection. Failure to correct the violation will result in a reinspection as established in our reinspection criteria. The Waukesha County Code of Ordinances requires a reinspection fee to be assessed for any reinspection. Our department is available as a resource to provide suggestions and guidance on how to correct the violation.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer, test kit reagents are are expired.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
Repeat
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. Discussed testing requirements and methods.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
Repeat
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Serious
Critical
Repeat
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
The free chlorine concentration in the pool is 0.2-0.4 PPM. UPDATE (6.26.26): The free chlorine in the pool is 0.4 PPM.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Jun 25, 2026 Routine · 5 critical, 4 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition. This is a repeat violation. It was documented during the last inspection and again today. This violation shall be corrected prior to the next routine inspection. Failure to correct the violation will result in a reinspection as established in our reinspection criteria. The Waukesha County Code of Ordinances requires a reinspection fee to be assessed for any reinspection. Our department is available as a resource to provide suggestions and guidance on how to correct the violation.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer, test kit reagents are are expired.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. Discussed testing requirements and methods.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
The free chlorine concentration in the pool is 0.2-0.4 PPM.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Corrected on site
SPINE BOARD
The spine board does not have a head immobilizer. The operator removed the spine board from the pool enclosure during the inspection.
Correction: Provide a spine board in good condition and with head immobilizer.
Code ATCP 76.26(1)(d) - SPINE BOARD
-
Serious
Critical
TELEPHONE ACCESSIBLE
The telephone is not capable of connecting to emergency services; there is no dial tone.
Correction: Provide a working telephone or other technology capable of connecting with emergency services.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Jul 24, 2025 Re-inspection · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meters are not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
-
Jul 11, 2025 Follow Up · 1 critical, 1 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meters are not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Serious
Critical
Repeat
GATES AND DOORS-LATCHING
The gates do not latch.
Correction: Provide a latching door.
Code ATCP 76.34(4)(a)(1m)(b)- LATCHING
-
Not serious
Non-critical
Repeat
-
Jul 1, 2025 Re-inspection · 1 critical, 2 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meters are not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Serious
Critical
Repeat
GATES AND DOORS-LATCHING
The gates do not latch.
Correction: Provide a latching door.
Code ATCP 76.34(4)(a)(1m)(b)- LATCHING
-
Not serious
Non-critical
Repeat
-
Jun 24, 2025 Routine · 2 critical, 2 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meters are not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Serious
Critical
GATES AND DOORS-SELF-CLOSING
The gates do not self-close.
Correction: Provide a self-closing gate or door.
Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING
-
Serious
Critical
GATES AND DOORS-LATCHING
The gates do not latch.
Correction: Provide a latching door.
Code ATCP 76.34(4)(a)(1m)(b)- LATCHING
-
Not serious
Non-critical
Source: Waukesha County Environmental Health. History last read Nov 20, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.