RecordWell Data

Fairfield Place Condominiums

640 PEWAUKEE RD, Pewaukee, WI 53072 · Waukesha County

19cited violations
6serious tier
6inspections

Establishment

Type
Pool / recreational water (Pool - Simple with Features)
Inspected by
Waukesha County Environmental Health
License / ID
HSAT-96F3KF
Status
Permitted
Phone
(414) 540-0004 ext. Sentry Management
Official record
Waukesha County Environmental Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20261112
2024264
2023320

Inspections

  1. Jun 3, 2026 Routine · 2 critical, 9 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      LICENSE NOT POSTED

      The license is not posted for public view.

      Correction: Post the license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Not serious Non-critical Corrected on site

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Weir door on the North end of the pool is missing. Jim with Aqua Magic stopped by today and installed a weir door. Corrected.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      PIPING LABELED, TAGGED OR CODED

      The piping is not labeled with direction of flow.

      Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.

      Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN ACTION LEVEL

      The combined chlorine plan does not include the combined chlorine action level.

      Correction: Includes the combined chlorine action level in the combined chlorine plan.

      Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED

    • Not serious Non-critical

      REAGENTS REPLACED

      Several test kit reagents are not replaced as recommended by the manufacturer as there are expiration dates from 2022 and 2023.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      POOL WATER TESTED PEAK PATRON LOAD, PH AND SANITIZER

      Pool water not tested for pH and disinfectant at least one other time during the day’s peak patron load. The pH and free chlorine levels shall be redorded twice daily as an electronic monitoring controller is not present.

      Correction: Test pool water for pH and disinfectant at least one time during the day’s peak patron load.

      Code ATCP 76.18(1)(a)2 - WATER TESTED, SANITIZER, PH, PEAK LOAD P

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      POOL CLOSED SIGN

      The pool area is closed but there is no 'closed' sign.

      Correction: Provide a sign that indicates the pool area is closed.

      Code ATCP 76.34(5) - 'CLOSED' SIGN

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-INSTALLATION DATE

      The VGBA replacement log shall be updated to indicate the 2024 installation of the drain and equalizers. Currently, the log lists 6/7/21 for replacement, but there was a replacement in 2024.

      Correction: Indicate in the log of drain cover installation date.

      Code ATCP 76.38(2)(b)5. - INSTALL DATE

    • Serious Critical

      RESPONSIBLE SUPERVISOR AVAILABLE AND RESPOND

      The responsible supervisor's phone number for the pool is not posted by the emergency phone.

      Correction: Have the responsible supervisor respond within 15 minutes when action is needed.

      Code ATCP 76.21 (1)(b) - NOT AVAILABLE WITHIN 15 MINUTES

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  2. Sep 11, 2024 Follow Up · 2 critical, 1 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      LICENSE NOT POSTED

      The license is not posted for public view.

      Correction: Post the license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Serious Critical Repeat Corrected on site

      PH

      pH observed to be 6.9 and 7.0 on the 601 disk. pH shall be in the range of 7.4-7.6

      Correction: Maintain the pH at 7.4 to 7.6. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical Repeat Corrected on site

      HAZARDOUS CONDITION

      Two drain cover screws are missing. Pool closed to the public at this time. Jim with Aqua Magic added two screws. Corrected. Pool can re-open.

      Correction: Correct the hazardous condition [Describe].

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  3. Aug 27, 2024 Routine · 2 critical, 1 non-critical
    • Not serious Non-critical

      LICENSE NOT POSTED

      The license is not posted for public view.

      Correction: Post the license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Serious Critical Corrected on site

      PH

      The pH is 8.1 after several tests. Acid added and pH came down to 7.9

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical Corrected on site

      HAZARDOUS CONDITION

      Two drain cover screws are missing. Pool closed to the public at this time. Jim with Aqua Magic added two screws. Corrected. Pool can re-open.

      Correction: Correct the hazardous condition [Describe].

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  4. Aug 3, 2023 Re-inspection · No items found

    No violations cited.

  5. Jul 18, 2023 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration was verified to be at 57 and 59 PPM. Two tests were ran. Drain pool by 1/3 to 1/2 half and bring in fresh water.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

  6. Jul 7, 2023 Routine · 1 non-critical
    • Not serious Non-critical

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration was verified to be at 53, 24, 55 PPM. Three tests were ran.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

Source: Waukesha County Environmental Health. History last read Nov 21, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.