Caroline Heights Apartments
13125 WATERTOWN PLANK RD, Elm Grove, WI 53122 · Waukesha County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Waukesha County Environmental Health
- License / ID
- HDEH-DB5G9P
- Status
- Permitted
- Phone
- (262) 373-9773
- Official record
- Waukesha County Environmental Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 9 | 6 |
| 2025 | 3 | 1 | 1 |
Inspections
-
Jul 7, 2026 Re-inspection · 1 critical, 1 non-critical, 1 repeat
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is less than 650 mV. The operator shall test the pool twice daily until the OPR is maintained between 650 mV and 900 mV. UPDATE (7/7): The ORP is 639-664 during the inspection. Daily operating reports indicate that the ORP has consistently been below 650 mV. The operator shall test the pool twice daily until the OPR is maintained between 650 mV and 900 mV.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Serious
Critical
Repeat
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Not serious
Non-critical
-
Jun 29, 2026 Routine · 5 critical, 2 non-critical
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is less than 650 mV. The operator shall test the pool twice daily until the OPR is maintained between 650 mV and 900 mV.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pH probe is not accurate +/- 0.2.
Correction: Maintain the pool equipment.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
CHEMICAL STORAGE ACCESS RESTRICTED
Chemical storage area access not restricted to authorized personnel only. The locking mechanism on the door handle to the pump room is not functioning.
Correction: Restrict access to chemical storage area to only authorized personnel.
Code ATCP 76.12 (2)(d) - ACCESS RESTRICTED
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
Corrected on site
TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION
Push button emergency phone does not have reliable service connection. The device did not connect to emergency services after ringing several times; the device connected to emergency services on the second test.
Correction: Provide a reliable service connection for the communication technology.
Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the pump room but no CO alarm.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Serious
Critical
GATES AND DOORS-SELF-CLOSING
The east-most gate does not self-close. The maintenance staff locked the gate so that it can not be used by patrons during the inspection.
Correction: Provide a self-closing gate or door.
Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING
-
Not serious
Non-critical
-
Jul 14, 2025 Follow Up · No items found
No violations cited.
-
Jun 18, 2025 Pre-inspection Follow Up · 1 critical
-
Serious
Critical
TELEPHONE ACCESSIBLE
A emergency push-button phone connects to a third-party emergency call center.
Correction: Provide a working telephone or other technology capable of connecting with emergency services.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Serious
Critical
-
Jun 6, 2025 Pre-inspection · No items found
No violations cited.
Source: Waukesha County Environmental Health. History last read Nov 21, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.