RecordWell Data

Deer Creek Run Apartments

1593 S MOORLAND RD, New Berlin, WI 53151 · Waukesha County

26cited violations
10serious tier
10inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Waukesha County Environmental Health
License / ID
HSAT-96F3KE
Status
Permitted
Phone
(262) 821-5750
Official record
Waukesha County Environmental Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026232
20252104
20243114
2023320

Inspections

  1. Aug 19, 2026 Re-inspection · No items found

    No violations cited.

  2. Aug 13, 2026 Routine · 2 critical, 1 non-critical, 2 repeat
    • Not serious Non-critical

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 80.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Serious Critical Repeat

      GATES AND DOORS-SELF-CLOSING

      The gate or door does not self-close. Gate was locked during inspection.

      Correction: Provide a self-closing gate or door.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover GPM rating.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  3. Jul 16, 2025 Re-inspection · 1 critical, 3 non-critical, 3 repeat
    • Not serious Non-critical

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 99 ppm.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmer weirs not replaced as needed.

      Correction: Repair or replace skimmer weirs as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      VGBA DRAIN COVER INFO-GPM

      The VGBA log or other proof does not indicate drain cover gallons per minute rating.

      Correction: Indicate in the log the drain cover gallons per minute rating.

      Code ATCP 76.38(2)(b)3. - COVER GPM RATING

    • Serious Critical Repeat

      GATES AND DOORS-SELF-CLOSING

      The gate or door does not self-close. Gate was locked during insepction.

      Correction: Provide a self-closing gate or door.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

  4. Jul 15, 2025 Routine · 3 critical, 3 non-critical, 1 repeat
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmer weirs not replaced as needed.

      Correction: Repair or replace skimmer weirs as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER

      Pool water was not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.

      Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.

      Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-GPM

      The VGBA log or other proof does not indicate drain cover gallons per minute rating.

      Correction: Indicate in the log the drain cover gallons per minute rating.

      Code ATCP 76.38(2)(b)3. - COVER GPM RATING

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is .2 ppm Cl.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      GATES AND DOORS-SELF-CLOSING

      The gate or door does not self-close. Gate was locked during insepction.

      Correction: Provide a self-closing gate or door.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  5. Jul 25, 2024 Follow Up · 1 critical, 2 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 80 ppm.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Not serious Non-critical Repeat

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve and drain cover specifications. VGBA information missing drain cover make and model.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  6. Jul 22, 2024 Re-inspection · 2 critical, 3 non-critical, 3 repeat
    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 555 mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical Repeat

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 80 ppm.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Not serious Non-critical Repeat

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is .25 PPM chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve and drain cover specifications. VGBA information missing drain cover make and model.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  7. Jul 18, 2024 Routine · 1 critical, 2 non-critical
    • Not serious Non-critical

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 80 ppm.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Not serious Non-critical

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve and drain cover specifications. VGBA information missing drain cover make and model.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  8. Jul 14, 2023 Re-inspection · No items found

    No violations cited.

  9. Jul 6, 2023 Follow Up · 2 non-critical
    • Not serious Non-critical

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration is 50 PPM.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Not serious Non-critical

      SKIMMER/MAIN DRAIN RATIO INCORRECT

      The skimmer to main drain flow ration is not set correctly.

      Correction: Readjust the flow so that only 20% comes through the main drain and 80% comes through the skimmers.

      Code [A] ATCP 76.11(2)(a)

  10. Jul 5, 2023 Routine · No items found

    No violations cited.

Source: Waukesha County Environmental Health. History last read Nov 21, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.