| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 7 | 4 |
| 2025 | 1 | 4 | 0 |
| 2024 | 1 | 6 | 2 |
Inspections
-
Jun 3, 2026 Re-inspection · 1 critical, 1 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
POOL RULES POSTED
The pool rules are not posted.
Correction: Post the pool rules.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
May 27, 2026 Routine · 3 critical, 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 230.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
POOL RULES POSTED
The pool rules are not posted.
Correction: Post the pool rules.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant level is 1.3 for chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
PH
The pH is 6.9.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Aug 11, 2025 Routine · 4 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 275.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not implemented a plan to minimize combined chlorine in the pool. The written action level for combined chlorine was observed exceeded.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
POOL RULES POSTED
The pool rules are not posted.
Correction: Post the pool rules.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement onsite.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Not serious
Non-critical
Repeat
-
Jun 26, 2024 Routine · 2 critical, 4 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Observed at 25 gallons/min. .
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate must be at least 30 galllons/min.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
LABEL, NAME OF PRODUCT
Container label does not list name of product. Label was missing on container.
Correction: Provide 1. Name of the product. 2. Manufacturer’s name and address. 3. Active ingredients. 4. Directions for use. 5. Hazardous ingredient warning. 6. For chemicals used for the primary purpose of controlling microbial or algal growth, the United States Environmental Protection Agency registration numbe.
Code ATCP 76.12 (1)(a) 1. - PRODUCT NAME
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 250.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
POOL RULES POSTED
The pool rules are not posted.
Correction: Post the pool rules.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Serious
Critical
SHEPHERD'S CROOK PROVIDED
The shepherd's crook is missing.
Correction: Provide a shepherd's crook.
Code ATCP 76.26(1)(b)1.a. -SHEPHERED'S CROOK PROVIDED
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the drain cover specifications and installation date.
Correction: Obtain information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Source: Waukesha County Environmental Health. History last read Nov 21, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.