RecordWell Data

Elite Sports Club-men's Whirlpool

13825 W BURLEIGH RD, Brookfield, WI 53005 · Waukesha County

17cited violations
6serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
Waukesha County Environmental Health
License / ID
HDEH-BM5RBP
Status
Permitted
Phone
(262) 786-0880
Official record
Waukesha County Environmental Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026274
2025140
2024162

Inspections

  1. Jun 3, 2026 Re-inspection · 1 critical, 1 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the drain cover specifications.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  2. May 27, 2026 Routine · 3 critical, 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is 230.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant level is 1.3 for chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      PH

      The pH is 6.9.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the drain cover specifications.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  3. Aug 11, 2025 Routine · 4 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is 275.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not implemented a plan to minimize combined chlorine in the pool. The written action level for combined chlorine was observed exceeded.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement onsite.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  4. Jun 26, 2024 Routine · 2 critical, 4 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Observed at 25 gallons/min. .

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate must be at least 30 galllons/min.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      LABEL, NAME OF PRODUCT

      Container label does not list name of product. Label was missing on container.

      Correction: Provide 1. Name of the product. 2. Manufacturer’s name and address. 3. Active ingredients. 4. Directions for use. 5. Hazardous ingredient warning. 6. For chemicals used for the primary purpose of controlling microbial or algal growth, the United States Environmental Protection Agency registration numbe.

      Code ATCP 76.12 (1)(a) 1. - PRODUCT NAME

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 250.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Serious Critical

      SHEPHERD'S CROOK PROVIDED

      The shepherd's crook is missing.

      Correction: Provide a shepherd's crook.

      Code ATCP 76.26(1)(b)1.a. -SHEPHERED'S CROOK PROVIDED

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the drain cover specifications and installation date.

      Correction: Obtain information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

Source: Waukesha County Environmental Health. History last read Nov 21, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.