La Quinta Inn & Suites-whirlpool
15300 W ROCK RIDGE RD, New Berlin, WI 53151 · Waukesha County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Waukesha County Environmental Health
- License / ID
- HDEH-BPSK6D
- Status
- Permitted
- Phone
- (262) 717-0900
- Official record
- Waukesha County Environmental Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 14 | 4 |
| 2025 | 9 | 43 | 20 |
| 2024 | 1 | 4 | 1 |
| 2023 | 2 | 2 | 0 |
Inspections
-
Jul 10, 2026 Re-inspection · 4 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming. No flow observed through top and left skimmer.
Correction: Adjust skimmers to maintain vigorous skimming .
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
Repeat
FIRST AID KIT ITEMS
The first aid kit is present but missing items.
Correction: Replace the missing items in the first aid kit.
Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
AIR MOVEMENT
Heating, ventilation, and exhaust equipment not maintained and operated to provide air movement to prevent any excessive condensation.
Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation. A referral to building inspection department or fire department will be made.
Code ATCP 76.33(4)(b) - AIR MOVEMENT
-
Not serious
Non-critical
Repeat
-
Jul 8, 2026 Routine · 2 critical, 6 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming. No flow observed through top and left skimmer.
Correction: Adjust skimmers to maintain vigorous skimming .
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 38.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
FIRST AID KIT ITEMS
The first aid kit is present but missing items.
Correction: Replace the missing items in the first aid kit.
Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS
-
Not serious
Non-critical
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
AIR MOVEMENT
Heating, ventilation, and exhaust equipment not maintained and operated to provide air movement to prevent any excessive condensation.
Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation. A referral to building inspection department or fire department will be made.
Code ATCP 76.33(4)(b) - AIR MOVEMENT
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant level is 0.2 ppm Chlorine
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
CO ALARM-POOL AREA
There is a fuel-burning device in the equipment room located in the indoor pool area pool but no functional CO alarm is provided in the indoor pool area.
Correction: Provide a CO alarm in the pool area and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)2- CO ALARM POOL AREA
-
Not serious
Non-critical
Repeat
-
Jun 19, 2026 Re-inspection · 2 critical
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant level is 1.6 ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
PH
The pH is 8.2. 6/19: The pH is 6.6
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
-
Jun 27, 2025 Re-inspection 2 · No items found
No violations cited.
-
Jun 6, 2025 Follow Up · 2 critical, 2 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
Repeat
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Not serious
Non-critical
Repeat
-
May 14, 2025 Follow Up · 2 critical, 2 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
Repeat
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Not serious
Non-critical
Repeat
-
Apr 25, 2025 Re-inspection 2 · 3 critical, 2 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Apr 14, 2025 Re-inspection 2 · 3 critical, 2 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
The free chlorine concentration in the pool is 0.88 PPM.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Mar 14, 2025 Re-inspection · 2 critical, 2 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Mar 13, 2025 Re-inspection 2 · 3 critical, 3 non-critical, 6 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 49 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1.98 ppm chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A (3ppm).
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Mar 12, 2025 Re-inspection 2 · 3 critical, 5 non-critical, 6 repeat
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 49 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming. Main drain valve is wide open.
Correction: Adjust skimmers to maintain vigorous skimming . Adjust main drain valve to increase flow through skimmers.
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
STRAINER BASKET NOT CLEANED DAILY
The strainer basket observed full of hair and other non-identifiable gunk/debris build up.
Correction: Clean strainer baskets daily.
Code ATCP 76.11(2)(d) 3. - CLEANED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1.98 ppm chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A (3ppm).
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
-
Feb 27, 2025 Re-inspection · 2 critical, 5 non-critical, 4 repeat
-
Not serious
Non-critical
STRAINER BASKET NOT CLEANED DAILY
The strainer basket observed full of hair and other non-identifiable gunk/debris build up.
Correction: Clean strainer baskets daily.
Code ATCP 76.11(2)(d) 3. - CLEANED
-
Not serious
Non-critical
STRAINER BASKET OR SCREEN -- CONTINUOUS USE, MAINTAINED
Strainer basket missing.
Correction: Ensure a strainer basket or screen in in continuous use and maintained.
Code ATCP 76.11(2)(d)1 - CONTINUOUS USE, MAINTAINED
-
Not serious
Non-critical
Repeat
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming. Main drain valve is wide open.
Correction: Adjust skimmers to maintain vigorous skimming . Adjust main drain valve to increase flow through skimmers.
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS
A pool that is required to have a certified operator does not have one.
Correction: Provide a certified operator for the pool.
Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
-
Oct 8, 2024 Routine · 1 critical, 3 non-critical
-
Not serious
Non-critical
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming. Main drain valve is wide open.
Correction: Adjust skimmers to maintain vigorous skimming . Adjust main drain valve to increase flow through skimmers.
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Weirs are missing from whirlpool skimmers.
Correction: Replace skimmer weirs as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. Combined chlorine observed above an acceptable action level.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
-
Aug 15, 2023 Re-inspection · 2 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
ALKALINITY OUT OF BALANCE
The total alkalinity is 20*.
Correction: Maintain the total alkalinity between 60 and 180 ppm.
Code ATCP 76.14(4)(d)
-
Not serious
Non-critical
COMBINED CHLORINE
The combined chlorine is 1.2.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Non-critical
Repeat
-
Aug 14, 2023 Follow Up · No items found
No violations cited.
Source: Waukesha County Environmental Health. History last read Nov 21, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.