RecordWell Data

Little Strokes Swim Academy

1029 QUINN DR, Waunakee, WI 53597 · Dane County

12cited violations
0serious tier
6inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2016-00250
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026150
2024120
2022150
2019100
2018100
2016100

Inspections

  1. Feb 27, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken: San provided DATCP forms f Corrected on site

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)

      Documentation of interlock system is not available per requirements in ATCP 76.13(1)(c).

      Correction: Operator must be able to demostrate knowledge and provide documentation of interlock system.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken: Sanitarian provided combin Corrected on site

      16d - COMBINED CHLORINE (Pf)

      The operator does not have a combined chlorine plan.

      Correction: Provide a plan with all components required under ATCP 76.14(5)(e)

      Code ATCP 76.14(5)(e)

    • Not serious Action taken:

      26g - BREATH HOLDING PROHIBITION - SIGNAGE

      Breath holding prohibition is not posted or communicated to patrons.

      Correction: Provide signage or otherwise communicate to patrons that activites involving prolonged breath holding are prohibited.

      Code ATCP 76.29(1)(f)

    • Not serious Action taken:

      26r - FIRST AID KIT - SUPPLIES MISSING (Pf)

      Eye wash is missing from the first aid kit.

      Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.

      Code ATCP 76.27(1)(b)

    • Not serious Action taken:

      32d - CARBON MONOXIDE ALARMS (P)

      The carbon monoxide alarm in pool equipment room is expired (2022) and a carbon monoxide detector must be installed in the hallway outside of the pool equipment room (for safety and redundancy in case the detector in the equipment room malfunctions or if the alarm cannot be heard over the noise of the pumps, filter, etc).

      Correction: Install functioning carbon monoxide alarms as applicable.

      Code ATCP 76.33(4)(d)

  2. Apr 29, 2024 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Discussed with owner and h Corrected on site

      20c - WATER TESTING - POOLS

      The water testing frequency for [chemical] is not in compliance with ATCP 76.18(1). No water test records for April 12.

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date. Owner states the drain covers were replaced soon after the last inspection by health dept (2022). Owner to contact Badger Pools to obtain documentation of replacement; Sanitarian to provide VGBA log for owner to record required information and keep onsite.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  3. Apr 21, 2022 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER

      The flow meter is not functional.

      Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      20c - WATER TESTING - POOLS

      The water testing frequency for alkalinity is not in compliance with ATCP 76.18(1).

      Correction: Perform water testing in accordance with ATCP 76.18(1). Record alkalinity readings on log sheet at least once/week.

      Code ATCP 76.18(1)

    • Not serious Action taken: Bill went to get a new pho Corrected on site

      26m - TELEPHONE - NOT WORKING

      The emergency telephone in pool enclosure does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code ATCP 76.26(2)

    • Not serious Action taken: San will work with pool op

      34c - DOOR/GATE

      The men's and women's locker room doors to the pool enclosure are not self-latching or lockable. The main pool entrance door was recently equipped with a self-latching/locking mechanism, however, patrons can only leave the pool using the push mechanism if the latch is in place.

      Correction: Repair the doors immediately so that it is self-closing, self-latching, and is lockable or re-submit a new variance application.

      Code ATCP 76.34(4)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  4. Dec 17, 2019 Routine Inspection · Reinspection Required

    No violations cited.

  5. May 24, 2018 Routine Inspection · Reinspection Required

    No violations cited.

  6. Aug 4, 2016 Pre-Inspection · Reinspection Required

    No violations cited.

Source: Public Health Madison & Dane County. History last read Nov 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.