Stoughton High School
600 LINCOLN AVE, Stoughton, WI 53589 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 73525-81773
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2024 | 1 | 8 | 0 |
| 2023 | 1 | 3 | 0 |
| 2019 | 1 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
Jul 1, 2026 Routine Inspection · Reinspection Required
-
Not serious
Action taken: The new pool supervisor pl
25f - LIFEGUARD - CERTIFICATIONS MAINTAINED (P)
The certifications for several lifeguards have expired and need renewal.
Correction: The lifeguard must be relieved of duties until a current certification can be verified. If the minimum lifeguard requirements in the approved staffing plan are not met as a result, the guarded pool or portion must be closed.
Code ATCP 76.22(2)(a)
-
Not serious
Action taken:
26g - BREATH HOLDING PROHIBITION - SIGNAGE
Breath holding prohibition is not posted or communicated to patrons.
Correction: Provide signage or otherwise communicate to patrons that activites involving prolonged breath holding are prohibited.
Code ATCP 76.29(1)(f)
-
Not serious
Action taken: The new pool supervisor pl
-
Mar 20, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
20b - TEST KIT REAGENT STORAGE
The test kit reagents for alkalinity were expired.
Correction: Replace reagents as recommended by the manufacturer.
Code ATCP 76.17(2)(b)
-
Not serious
Action taken: Water test log template fr
20c - WATER TESTING - POOLS
The water testing frequency for alkalinity and combined chlorine are not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Ensure alkalinity is tested once per week, and combined chlorine is tested twice per week.
Code ATCP 76.18(1)
-
Not serious
Action taken: Template will be provided
24a - LIFEGUARD - STAFFING PLAN
The staffing plan is not up to date with current operations and is missing some information.
Correction: Create a written plan pursuant to the requirements of ATCP 76.22 and submit it for approval.
Code ATCP 76.22(1)(a)
-
Not serious
Action taken:
25f - LIFEGUARD - CERTIFICATIONS MAINTAINED
Certifications for multiple people have expired.
Correction: The lifeguard must be relieved of duties until a current certification can be verified. If the minimum lifeguard requirements in the approved staffing plan are not met as a result, the guarded pool or portion must be closed.
Code ATCP 76.22(2)(a)
-
Not serious
Action taken:
26o - EMERGENCY NUMBERS AND ADDRESS
The facility's location is not posted near the designated emergency phone.
Correction: Post the emergency numbers near the designated emergency phone.
Code ATCP 76.26(2)
-
Not serious
Action taken:
27c - SIGNAGE - SMALL LETTERS
The letters on the pool rules signage are less than 1-inch in height.
Correction: Provide an approved sign.
Code ATCP 76.29(1)(b)
-
Not serious
Action taken:
30e - SOAP
Soap dispensers are not provided at showers in locker rooms.
Correction: Provide soap at all hand washing sinks and showers.
Code ATCP 76.33(2)(e)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
Both diving boards were observed to have peeling paint.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
-
Feb 7, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
20e - WATER TESTING FREQUENCY - ORP
The water testing frequency is not in compliance with ATCP 76.18(3). The pool is not always tested on the weekends when in use.
Correction: Perform water testing in accordance with ATCP 76.18(3).
Code ATCP 76.18(3)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
1) Railings around the perimeter of the pool are not all securely fastened. Some wobble, especially the railing on the shallow end of the pool. 2) Evidence of rust on tiles by the railings where secured.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Other
Repeat
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Dec 16, 2019 Routine Inspection · No Reinspection Required
No violations cited.
-
May 14, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 2, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 17, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
May 29, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 26, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 14, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Mar 26, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Nov 3, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.