The Monticello Apartments

5015 Sheboygan AVE, Madison, WI 53705 · Dane County

60cited violations
0serious tier
8inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2023-00223
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262240
20252100
20242110
20232150

Inspections

  1. Jul 2, 2026 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER (P - Not Corrected

      The flow meter is not functional or installed properly.

      Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      11b - CHEMICAL - STORAGE (P)(Pf) - Not Corrected

      Chemicals are improperly stored in accordance with ATCP 76.12(2). Acid and chlorine stored in same space without spill protection.

      Correction: Store chemicals in accordance with ATCP 76.12(2). Use overspill platform or other means to prevent accidental mixing of acid and chlorine.

      Code ATCP 76.12(2)

    • Not serious Action taken: pool closed

      14a - CHLORINE TOO LOW (P) - Not Corrected

      The chlorine residual was 0ppm Cl at the time of the inspection.

      Correction: Close the pool and raise the chlorine residual to be within acceptable range of 1.5-10ppm Cl. Call inspector to schedule a reopening inspection.

      Code ATCP 76.14(4)(a)

    • Not serious Action taken:

      16c - ALKALINITY (Pf) - Not Corrected

      The total alkalinity is 240 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(5)(d)

    • Not serious Action taken:

      20c - WATER TESTING - POOLS (Pf) - Not Corrected

      The water testing frequency for pH, free chlorine, alkalinity, and CYA are not in compliance with ATCP 76.18(1). No testing records since 6/18.

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Action taken:

      21b - BACKFLOW - HOSE BIBBS (P) - Not Corrected

      The hose bibb by the recirculation pump is not protected against backsiphonage. Hose used only for priming the system, disconnected at all other times.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code ATCP 76.33(1)(d)

    • Not serious Action taken: pool closed

      26n - TELEPHONE - NOT WORKING (P) - Not Corrected

      The emergency telephone does not work.

      Correction: Close pool. Provide a functional emergency telephone immediately. Contact sanitarian to schedule reinspection to re-open the pool.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26t - BIOHAZARD SAFETY KIT (Pf) - Not Corrected

      No biohazard safety kit is located at the first aid station or on the premises.

      Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.

      Code ATCP 76.27(2)

    • Not serious Action taken:

      29a - BASIN CLEANING - Not Corrected

      Basin has sediment and is in need of cleaning.

      Correction: Keep the basin in a clean and sanitary condition pursuant to ATCP 76.33(1)(a).

      Code ATCP 76.33(1)(a)

    • Not serious Action taken:

      31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED - Not Corrected

      Stair rail at shallow end of pool is loose.

      Correction: Tighten anchor bolts for stair rail. Properly locate, install, maintain and repair equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Action taken:

      32d - CARBON MONOXIDE ALARMS (P) - Not Corrected

      There is no carbon monoxide alarm in pool equipment room where there is a fuel burning appliance.

      Correction: Install functioning carbon monoxide alarms as applicable.

      Code ATCP 76.33(4)(d)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf) - Not Corrected

      No documentation is available on site for VGBA equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  2. Jul 1, 2026 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER (P

      The flow meter is not functional or installed properly.

      Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      11b - CHEMICAL - STORAGE (P)(Pf)

      Chemicals are improperly stored in accordance with ATCP 76.12(2). Acid and chlorine stored in same space without spill protection.

      Correction: Store chemicals in accordance with ATCP 76.12(2). Use overspill platform or other means to prevent accidental mixing of acid and chlorine.

      Code ATCP 76.12(2)

    • Not serious Action taken: pool closed

      14a - CHLORINE TOO LOW (P)

      The chlorine residual was 0ppm Cl at the time of the inspection.

      Correction: Close the pool and raise the chlorine residual to be within acceptable range of 1.5-10ppm Cl. Call inspector to schedule a reopening inspection.

      Code ATCP 76.14(4)(a)

    • Not serious Action taken:

      16c - ALKALINITY (Pf)

      The total alkalinity is 240 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(5)(d)

    • Not serious Action taken:

      20c - WATER TESTING - POOLS (Pf)

      The water testing frequency for pH, free chlorine, alkalinity, and CYA are not in compliance with ATCP 76.18(1). No testing records since 6/18.

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Action taken:

      21b - BACKFLOW - HOSE BIBBS (P)

      The hose bibb by the recirculation pump is not protected against backsiphonage. Hose used only for priming the system, disconnected at all other times.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code ATCP 76.33(1)(d)

    • Not serious Action taken: pool closed

      26n - TELEPHONE - NOT WORKING (P)

      The emergency telephone does not work.

      Correction: Close pool. Provide a functional emergency telephone immediately. Contact sanitarian to schedule reinspection to re-open the pool.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26t - BIOHAZARD SAFETY KIT (Pf)

      No biohazard safety kit is located at the first aid station or on the premises.

      Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.

      Code ATCP 76.27(2)

    • Not serious Action taken:

      29a - BASIN CLEANING

      Basin has sediment and is in need of cleaning.

      Correction: Keep the basin in a clean and sanitary condition pursuant to ATCP 76.33(1)(a).

      Code ATCP 76.33(1)(a)

    • Not serious Action taken:

      31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED

      Stair rail at shallow end of pool is loose.

      Correction: Tighten anchor bolts for stair rail. Properly locate, install, maintain and repair equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Action taken:

      32d - CARBON MONOXIDE ALARMS (P)

      There is no carbon monoxide alarm in pool equipment room where there is a fuel burning appliance.

      Correction: Install functioning carbon monoxide alarms as applicable.

      Code ATCP 76.33(4)(d)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  3. Jun 30, 2025 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER (P - Not Corrected

      The flow meter is not functional or installed properly.

      Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      16c - ALKALINITY (Pf) - Not Corrected

      The total alkalinity is 240 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(5)(d)

    • Not serious Action taken:

      26t - BIOHAZARD SAFETY KIT (Pf) - Not Corrected

      No biohazard safety kit is located at the first aid station or on the premises.

      Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.

      Code ATCP 76.27(2)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf) - Not Corrected

      No documentation is available on site for VGBA equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  4. Jun 27, 2025 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER (P

      The flow meter is not functional or installed properly.

      Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      16c - ALKALINITY (Pf)

      The total alkalinity is 240 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(5)(d)

    • Not serious Action taken: pool closed. Spectrum sche

      26n - TELEPHONE - NOT WORKING (P)

      The emergency telephone does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26t - BIOHAZARD SAFETY KIT (Pf)

      No biohazard safety kit is located at the first aid station or on the premises.

      Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.

      Code ATCP 76.27(2)

    • Not serious Any of the following conditions or situa Corrected on site

      28a - CLOSING CRITERIA (P)

      The pool was not closed by the operator or responsible supervisor under the following condition: emergency pool phone was not working.

      Correction: Ensure that the closing criteria are adhered to under the listed below and post signage indicating closure.

      Code ATCP 76.30

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  5. Jul 3, 2024 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      11e - SDS AVAILABILITY - Not Corrected

      Safety data sheets are not available for all chemicals used in the facility.

      Correction: Provide safety data sheets for all chemicals used in the facility.

      Code ATCP 76.12(4)(b)

    • Not serious Action taken:

      30b - SHOWERS - Not Corrected

      The showers are not functioning properly. Men's shower does not have water, women's shower comes on when cold water at sink is turned on.

      Correction: Repair the showers.

      Code ATCP 76.33(2)(b)

    • Not serious Other

      34e - VGBA COVERS - Not Corrected

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  6. Jun 27, 2024 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      11b - CHEMICAL - STORAGE

      Chemicals are improperly stored in accordance with ATCP 76.12(2).

      Correction: Store chemicals in accordance with ATCP 76.12(2).

      Code ATCP 76.12(2)

    • Not serious Action taken:

      11e - SDS AVAILABILITY

      Safety data sheets are not available for all chemicals used in the facility.

      Correction: Provide safety data sheets for all chemicals used in the facility.

      Code ATCP 76.12(4)(b)

    • Not serious Action taken: system is designed to be r

      13a - INCORRECT DISINFECTANT FEEDER

      Pool is manually fed liquid chlorine. Trichlor erosion feeder system is disconnected.

      Correction: Discontinue manually feeding liquid chlorine. Close pool until the proper disinfectant is acquired and utilized.

      Code ATCP 76.13(1)

    • Not serious Action taken: pool closed until a functi

      26m - TELEPHONE - NOT WORKING

      The emergency telephone does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26o - EMERGENCY NUMBERS AND ADDRESS

      The emergency numbers and/or the facility's location are not posted near the designated emergency phone. Signage is posted on door to pump room.

      Correction: Post the emergency/non-emergency numbers near the designated emergency phone. Provide additional signage to indicate location of 911 emergency phone.

      Code ATCP 76.26(2)

    • Not serious Any of the following conditions or situa

      28a - CLOSING CRITERIA

      The pool was not closed under the following condition: emergency phone not working.

      Correction: Ensure that the closing criteria are adhered to under the listed below.

      Code ATCP 76.30

    • Not serious Action taken:

      30b - SHOWERS

      The showers are not functioning properly. Men's shower does not have water, women's shower comes on when cold water at sink is turned on.

      Correction: Repair the showers.

      Code ATCP 76.33(2)(b)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  7. Jun 1, 2023 Re-Inspection · No Reinspection Required
    • Not serious Action taken: On 6-1-2023, pool volume e

      08a - RECIRCULATION RATE - SWIM/COMBO - Not Corrected

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 6 hours.

      Code ATCP 76.11(4)(a)

    • Not serious Action taken: On 6-1-2023, alkalinity 26

      16c - ALKALINITY - Not Corrected

      The total alkalinity is 260ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Action taken: On 6-1-2023, bids being se

      29d - DECK DISINFECTION - Not Corrected

      Brick work around interior deck perimeter is broken and needing repair.

      Correction: Repair surfaces to prevent broken bricks on the deck surface.

      Code ATCP 76.33(1)

    • Not serious Action taken: On 6-1-2023, getting bid f

      32c - LIGHTING - Not Corrected

      The pool lighting in not functional.

      Correction: Replace the bulb and maintain all lighting in operating condition. Restrict pool open hours until repaired.

      Code ATCP 76.33(4)(c)

    • Not serious Other

      34e - VGBA COVERS - Not Corrected

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  8. May 26, 2023 Pre-Inspection · Reinspection Required
    • Not serious Action taken:

      05a - SKIMMER/MAIN DRAIN RATIO

      The skimmer to main drain flow ratio does not appear to be set correctly.

      Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken:

      06a - SPARE STRAINER BASKET

      A spare strainer for the skimmers is not located on site.

      Correction: Provide a spare basket or screen.

      Code ATCP 76.11(2)(d)

    • Not serious Action taken:

      08a - RECIRCULATION RATE - SWIM/COMBO

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 6 hours.

      Code ATCP 76.11(4)(a)

    • Not serious Action taken:

      16c - ALKALINITY

      The total alkalinity is 260ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Action taken:

      21c - DIRECTION OF FLOW

      The water treatment system piping is not marked with a permanent label indicating direction of flow.

      Correction: Mark the water treatment system piping to indicate direction of flow.

      Code ATCP 76.11(5m)

    • Not serious Action taken: Operator contacted Newman

      28d - MONTHLY REPORTS AVAILABLE

      VGBA, pump curve and pool plans are not available for review.

      Correction: Keep records available for review.

      Code ATCP 76.32(3)

    • Not serious Action taken:

      29d - DECK DISINFECTION

      Brick work around interior deck perimeter is broken and needing repair.

      Correction: Repair surfaces to prevent broken bricks on the deck surface.

      Code ATCP 76.33(1)

    • Not serious Action taken:

      30a - SHOWER, TOILET AND DRESSING ROOM FACILITIES

      Pool house shower rooms are not clean.

      Correction: Clean and disinfect the walls, partitions and floors of showers, toilet rooms and dressing areas.

      Code ATCP 76.33(2)(a)

    • Not serious Action taken:

      32c - LIGHTING

      The pool lighting in not functional.

      Correction: Replace the bulb and maintain all lighting in operating condition. Restrict pool open hours until repaired.

      Code ATCP 76.33(4)(c)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)