The Monticello Apartments
4849 Sheboygan AVE, Madison, WI 53705 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2023-00224
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 14 | 0 |
| 2025 | 1 | 9 | 0 |
| 2024 | 1 | 3 | 0 |
| 2023 | 3 | 8 | 0 |
Inspections
-
Aug 17, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
05a - SKIMMER/MAIN DRAIN RATIO (Pf)
The skimmer to main drain flow ratio is not set correctly. Main drain valve is full open.
Correction: Readjust the flow so that on pool with skimmers, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain. For reverse flow pools, 100% recirculation must be through gutter or skimmers.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken:
09a - FLOW METER (P
The flow meter is not functional or installed properly.
Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
11e - SDS AVAILABILITY (Pf)
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken:
16c - ALKALINITY (Pf)
The total alkalinity is 280ppm.
Correction: Maintain the total alkalinity between 60 and 180 ppm.
Code ATCP 76.14(5)(d)
-
Not serious
Action taken: Since the Chemtrol system
Corrected on site
20c - WATER TESTING - POOLS (Pf)
The water testing frequency for pH and free chlorine is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken:
21d - READABLE CHART
There is no readable chart that describes the piping, valves, and direction of water flow.
Correction: Labels, tags, or color coding shall correspond to a conspicuously posted, easily read chart that explains the system.
Code ATCP 76.11(5m)(b)
-
Not serious
Action taken:
26p - EMERGENCY NUMBERS AND ADDRESS (Pf)
The emergency numbers and/or the facility's location are not posted near the designated emergency phone.
Correction: Post the emergency numbers near or attached to the designated emergency phone.
Code ATCP 76.26(2)(d)
-
Not serious
Action taken:
26r - FIRST AID KIT - SUPPLIES MISSING (Pf)
Supplies are missing from the first aid kit. Restock or replacement of first aid kit needed.
Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.
Code ATCP 76.27(1)(b)
-
Not serious
Action taken:
26t - BIOHAZARD SAFETY KIT (Pf)
No biohazard safety kit is located at the first aid station or on the premises.
Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.
Code ATCP 76.27(2)
-
Not serious
Action taken:
29a - BASIN CLEANING
Basin has leaves, algae, slime growth, and discoloration and is in need of cleaning.
Correction: Keep the basin in a clean and sanitary condition pursuant to ATCP 76.33(1)(a).
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
Leak observed on cover for sand filter #1.
Correction: Properly locate, intall, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
32a - WATER HEATER
The water heaters are in disrepair and not operating.
Correction: Repair the water heaters and maintain it in an operating condition.
Code ATCP 76.33(4)(a)
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken:
-
Aug 21, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER (P
The flow meter is not functional or installed properly.
Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken: sanitarian recommended ins
11b - CHEMICAL - STORAGE (P)(Pf)
Chemicals are improperly stored in accordance with ATCP 76.12(2). No overspill containment provided for chlorine and acid.
Correction: Store chemicals in accordance with ATCP 76.12(2).
Code ATCP 76.12(2)
-
Not serious
Action taken:
16c - ALKALINITY (Pf)
The total alkalinity is 220ppm.
Correction: Maintain the total alkalinity between 60 and 180 ppm.
Code ATCP 76.14(5)(d)
-
Not serious
Action taken:
26p - EMERGENCY NUMBERS AND ADDRESS (Pf)
The emergency numbers and/or the facility's location are not posted near the designated emergency phone.
Correction: Post the emergency numbers near or attached to the designated emergency phone.
Code ATCP 76.26(2)(d)
-
Not serious
Any of the following conditions or situa
Corrected on site
28a - CLOSING CRITERIA (P)
The pool was not closed by the operator or responsible supervisor under the following condition: equalizer cover was not secured to the wall.
Correction: Ensure that the closing criteria are adhered to under the listed below and post signage indicating closure.
Code ATCP 76.30
-
Not serious
Action taken:
29a - BASIN CLEANING
Basin has [debris, algae] and is in need of cleaning.
Correction: Keep the basin in a clean and sanitary condition pursuant to ATCP 76.33(1)(a).
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
29b - BASIN MAINTENANCE AND REPAIR
The pool basin has several pits from paint that has popped.
Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
29g - DRINKING FOUNTAIN (P)
The drinking fountain is not functional or not clean.
Correction: Repair/clean the drinking fountain.
Code ATCP 76.33(1)(g)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No documentation is available on site for VGBA equalizer covers showing make, model, gallons per minute rating, life span, and installation date.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken:
-
Jun 27, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
Corrected on site
05a - SKIMMER/MAIN DRAIN RATIO
The skimmer to main drain flow ratio is not set correctly.
Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken:
09a - FLOW METER
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
11e - SDS AVAILABILITY
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken:
Corrected on site
-
Jun 26, 2023 Re-Inspection · No Reinspection Required
No violations cited.
-
Jun 9, 2023 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
04b - SKIMMERS/GUTTERS CLEANED - Not Corrected
Skimmers are not clean.
Correction: Maintain in a clean condition.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
29d - DECK DISINFECTION - Not Corrected
The pool deck is unclean from debris from overhanging trees. Some perimeter bricks are broken and need to be repaired.
Correction: Clean and sanitize the deck and appurtenances according to ATCP 76.33 (1)(b).
Code ATCP 76.33(1)(b)
-
Not serious
Action taken:
33c - LANDSCAPING - NOT MAINTAINED - Not Corrected
The grounds are not being maintained to prevent debris from entering the water. Trees over hand the deck area.
Correction: Maintain the grounds.
Code ATCP 76.34(6)
-
Not serious
Action taken:
-
Jun 2, 2023 Pre-Inspection · Reinspection Required
-
Not serious
Action taken:
04b - SKIMMERS/GUTTERS CLEANED
Skimmers are not clean.
Correction: Maintain in a clean condition.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
29d - DECK DISINFECTION
The pool deck is unclean from debris from overhanging trees. Some perimeter bricks are broken and need to be repaired.
Correction: Clean and sanitize the deck and appurtenances according to ATCP 76.33 (1)(b).
Code ATCP 76.33(1)(b)
-
Not serious
Action taken:
29g - DRINKING FOUNTAIN
The drinking fountain leaks.
Correction: Repair/clean the drinking fountain.
Code ATCP 76.33(1)(g)
-
Not serious
Action taken:
33c - LANDSCAPING - NOT MAINTAINED
The grounds are not being maintained to prevent debris from entering the water. Trees over hand the deck area.
Correction: Maintain the grounds.
Code ATCP 76.34(6)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date. Main drain cover has small broken grate fin. Covers visible.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
Source: Public Health Madison & Dane County. History last read Nov 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.