Hampton Inn & Suites Madison West
483 COMMERCE DR, Madison, WI 53719 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 72709-82360
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 21 | 0 |
| 2025 | 1 | 4 | 0 |
| 2024 | 2 | 8 | 0 |
| 2023 | 1 | 1 | 0 |
| 2022 | 1 | 1 | 0 |
| 2020 | 1 | 0 | 0 |
| 2019 | 1 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 2 | 0 | 0 |
Inspections
-
Feb 16, 2026 Re-Inspection · No Reinspection Required
No violations cited.
-
Feb 6, 2026 Re-Inspection · Reinspection Required
-
Not serious
Action taken:
13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P) - Not Corrected
Operator cannot adequately demonstrate knowledge and cannot provide documentation of interlock system.
Correction: Operator must be able to demonstrate knowledge and provide documentation of interlock system. Once monthly, testing of the interlock system shall be conducted. A log of the monthly test shall be kept and include the date, results, and the name of the person performing the test.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken: Discussed requirement for
Corrected on site
14f - NO DISINFECTANT FEEDER (P) - Not Corrected
The whirlpool is not being automatically and continually disinfected via a disinfectant feeder. Operator states he thinks system is being turned off by guests at the end of the night using the emergency shut-off. Operator states children may also be playing with the emergency shut off.
Correction: The disinfection feeder shall be continuously operating.
Code ATCP 76.14(1)
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf) - Not Corrected
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
20e - WATER TESTING FREQUENCY - WITH ELECTRONIC MONITORING DEVICE (Pf) - Not Corrected
The water testing frequency for free chlorine, combined chlorine, and pH is not in compliance with ATCP 76.18(3).
Correction: Perform water testing in accordance with ATCP 76.18(3). Free chlorine, combined chlorine, and pH shall be tested daily, including weekends.
Code ATCP 76.18(3)
-
Not serious
Action taken:
21d - READABLE CHART - Not Corrected
There is no readable chart that describes the piping, valves, and direction of water flow.
Correction: Labels, tags, or color coding shall correspond to a conspicuously posted, easily read chart that explains the system.
Code ATCP 76.11(5m)(b)
-
Not serious
Action taken:
26r - FIRST AID KIT - SUPPLIES MISSING (Pf) - Not Corrected
Gauze pads, gauze roller bandage, and adhesive bandages are missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.
Code ATCP 76.27(1)(b)
-
Not serious
Action taken:
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED - Not Corrected
Sand observed on bottom of basin. Per operator, sand filter lateral is broken. Drinking fountain inside enclosure is in disrepair.
Correction: Equipment shall be maintained in good repair. Repair sand filter. There is a drinking fountain located immediately outside the enclosure that meets drinking fountain requirements. Either repair drinking fountain inside enclosure or remove it.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
-
Feb 5, 2026 Routine Inspection · Reinspection Required
-
Not serious
Other
Corrected on site
05a - SKIMMER/MAIN DRAIN RATIO (Pf)
The skimmer to main drain flow ratio is not set correctly. Main drain valve was 100% open.
Correction: Readjust the flow so that on pool with skimmers, only 20% of the flow comes through the main drain and 80% comes through the skimmers. Action taken: Valves were adjusted.
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET
A spare strainer basket for the skimmers is not located on site.
Correction: Provide a spare basket.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken:
13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)
Operator cannot adequately demonstrate knowledge and cannot provide documentation of interlock system.
Correction: Operator must be able to demonstrate knowledge and provide documentation of interlock system. Once monthly, testing of the interlock system shall be conducted. A log of the monthly test shall be kept and include the date, results, and the name of the person performing the test.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken: Pool was closed. Operator
14a - CHLORINE TOO LOW (P)
The chlorine residual was 2.0 ppm at the time of the inspection.
Correction: Close the pool and raise the chlorine residual to 3.0 ppm. Call inspector to schedule a reopening inspection.
Code ATCP 76.14(4)(a)
-
Not serious
Action taken: Pool was closed. Device ci
Corrected on site
14f - NO DISINFECTANT FEEDER (P)
The whirlpool is not being automatically and continually disinfected via a disinfectant feeder. Operator states he thinks system is being turned off by guests at the end of the night using the emergency shut-off. Operator states children may also be playing with the emergency shut off.
Correction: The pool must be closed and the disinfectant feeder put into continuous use before the facility can re-open.
Code ATCP 76.14(1)
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf)
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
20b - TEST KIT REAGENT STORAGE (Pf)
All test kit reagents (excluding DPD powder) are being used past their expiration date.
Correction: Replace reagents when expired.
Code ATCP 76.17(2)
-
Not serious
Action taken:
20e - WATER TESTING FREQUENCY - WITH ELECTRONIC MONITORING DEVICE (Pf)
The water testing frequency for free chlorine, combined chlorine, and pH is not in compliance with ATCP 76.18(3).
Correction: Perform water testing in accordance with ATCP 76.18(3). Free chlorine, combined chlorine, and pH shall be tested daily, including weekends.
Code ATCP 76.18(3)
-
Not serious
Action taken:
21d - READABLE CHART
There is no readable chart that describes the piping, valves, and direction of water flow.
Correction: Labels, tags, or color coding shall correspond to a conspicuously posted, easily read chart that explains the system.
Code ATCP 76.11(5m)(b)
-
Not serious
Action taken: Phone was repaired.
Corrected on site
26n - TELEPHONE - NOT WORKING (P)
The emergency telephone does not work.
Correction: Provide a functional emergency telephone immediately.
Code ATCP 76.26(2)
-
Not serious
Action taken:
26r - FIRST AID KIT - SUPPLIES MISSING (Pf)
Gauze pads, gauze roller bandage, and adhesive bandages are missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.
Code ATCP 76.27(1)(b)
-
Not serious
Any of the following conditions or situa
Corrected on site
28a - CLOSING CRITERIA (P)
The pool was not closed by the operator or responsible supervisor under the following conditions: 1) emergency telephone is not working and 2) free chlorine in whirlpool is less than 3.0 ppm.
Correction: Ensure that the closing criteria are adhered to under the listed below and post signage indicating closure.
Code ATCP 76.30
-
Not serious
Action taken:
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
Sand observed on bottom of basin. Per operator, sand filter lateral is broken. Drinking fountain inside enclosure is in disrepair.
Correction: Equipment shall be maintained in good repair. Repair sand filter. There is a drinking fountain located immediately outside the enclosure that meets drinking fountain requirements. Either repair drinking fountain inside enclosure or remove it.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in the indoor pool area.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Other
Corrected on site
-
Feb 13, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: Flow was at 0% through wei
Corrected on site
04a - SKIMMER FUNCTION
All weir skimmers are not adequately removing surface debris. Weirs were floating and one was upside down,
Correction: Readjust the flow through the skimmers to maintain vigorous skimming action through all skimmers.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken: Operator stated that they
Corrected on site
05a - SKIMMER/MAIN DRAIN RATIO
The skimmer to main drain flow ratio is not set correctly. Main drain was set to 100% and weirs were are 0%.
Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken:
20c - WATER TESTING - POOLS
The water testing frequency for pH, Combined chlorine and ORP is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
Humidifier in pump room is creating a large amount of water to pool on top of HVAC system. Piping to sand filters are also leaking and not in good repair.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken: Flow was at 0% through wei
Corrected on site
-
May 2, 2024 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
04c - SKIMMER BASKET/WEIR - Not Corrected
A weir door is missing in whirlpool skimmer in which a floating basket is not used.
Correction: Replace.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: PIC informed quotes have b
29b - BASIN DEFECTS - Not Corrected
The pool basin has significant pitting.
Correction: Repair the pool basin so it is finished and easily cleanable.
Code ATCP 76.33(1)(a)
-
Not serious
Other
34e - VGBA COVERS - Not Corrected
VGBA logs have not been updated. 1) From routine inspection, main drains are printed with label "Lawson Aquatics #MLD-GO-1818". Documentation (VGBA log) shows different model number than what is installed in the pool. 2) According to log VGBA equalizer covers expired in January.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Apr 5, 2024 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
04c - SKIMMER BASKET/WEIR
A weir door is missing in whirlpool skimmer in which a floating basket is not used.
Correction: Replace.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: Whirlpool drained and refi
Corrected on site
16d - COMBINED CHLORINE
The combined chlorine is 1.4ppm.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Action taken: Sanitarian provided origin
Corrected on site
25m - WHIRLPOOL ATTENDANT - WA COMPLEX
No formal plans are in place to ensure an attendant is available for periodic supervision of the whirlpool in the water attraction complex. PIC informed staff (housekeeping, pool PIC, front desk) enters pool area about 4-5 times per day for various tasks (collecting towels, pool testing).
Correction: The whirlpool must be closed until periodic supervision by an attendant is available.
Code ATCP 76.22(1)(d)
-
Not serious
Action taken: PIC informed quotes have b
29b - BASIN DEFECTS
The pool basin has significant pitting.
Correction: Repair the pool basin so it is finished and easily cleanable.
Code ATCP 76.33(1)(a)
-
Not serious
Other
34e - VGBA COVERS
Several screws missing on VGBA main drain covers. Drains are printed with label "Lawson Aquatics #MLD-GO-1818". Documentation (VGBA log) shows different model number than what is installed in the pool. According to log VGBA equalizer covers expired in January. Invoices not included in logs.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Apr 19, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE
The water testing frequency for chlorine, pH, alkalinity are not in compliance with ATCP 76.18(2).
Correction: Perform water testing in accordance with ATCP 76.18(2).
Code ATCP 76.18(2)
-
Not serious
Action taken:
-
Mar 10, 2022 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
-
Mar 12, 2020 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 16, 2019 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 26, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Mar 13, 2017 Routine Inspection · Reinspection Required
No violations cited.
-
Jul 27, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 7, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Sep 26, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Oct 25, 2012 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 20, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Nov 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.