6409 BRIDGE RD, Madison, WI 53713 · Dane County

13cited violations
0serious tier
11inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
9724-2351
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2025140
2024190
2021100
2019100
2018100
2017100
2015200
2014200
2012100

Inspections

  1. Aug 13, 2025 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER (P

      The flow meter is not functional.

      Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      16c - ALKALINITY (Pf)

      The total alkalinity is 50 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(5)(d)

    • Not serious Action taken: In order to avoid a charge Repeat

      20e - WATER TESTING FREQUENCY - WITH ELECTRONIC MONITORING DEVICE (Pf)

      The water testing frequency for alkalinity, combined chlorine and cyanuric acid, is not in compliance with ATCP 76.18(3).

      Correction: Perform water testing in accordance with ATCP 76.18(3).

      Code ATCP 76.18(3)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  2. Aug 9, 2024 Routine Inspection · No Reinspection Required
    • Not serious Action taken: PIC adjusted onsite. Corrected on site

      05a - SKIMMER/MAIN DRAIN RATIO

      The skimmer to main drain flow ratio is not set correctly. Both are set wide open.

      Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken:

      08a - RECIRCULATION RATE - SWIM/COMBO

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 6 hours.

      Code ATCP 76.11(4)(a)

    • Not serious Action taken:

      20b - TEST KIT REAGENT STORAGE

      The test kit reagents are expired.

      Correction: Keep reagents in original containers and replace as recommended by manufacturer.

      Code ATCP 76.17(2)

    • Not serious Action taken: Use updated pool logs with

      20e - WATER TESTING FREQUENCY - ORP

      The water testing frequency for alkalinity and combined chlorine is not in compliance with ATCP 76.18(3).

      Correction: Perform water testing in accordance with ATCP 76.18(3).

      Code ATCP 76.18(3)

    • Not serious Action taken: PIC found Shepherd's Crook Corrected on site

      26i - RESCUE EQUIPMENT - MISSING

      A Sherpherd's Crook is not provided in the pool area.

      Correction: Provide a Shepherd's Crook for the facility and mount it in a conspicuous location.

      Code ATCP 76.26(1)(b)

    • Not serious Action taken:

      26q - FIRST AID KIT - SUPPLIES MISSING

      Eye wash is missing from the first aid kit.

      Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.

      Code ATCP 76.27(1)

    • Not serious Action taken:

      26s - BIOHAZARD SAFETY KIT

      No biohazard safety kit is located on the premises.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Action taken: PIC immediately repaired b Corrected on site

      34c - DOOR/GATE

      The gates to the pool enclosure are not consistently self-closing and self-latching. The gate on one side can be propped open as the bottom bars get stuck on the concrete. The other gate does not always latch when there is not sufficient momentum to reach the latch.

      Correction: Repair the door immediately so that it is self-closing, self-latching, and is lockable.

      Code ATCP 76.34(4)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date. The PIC dove down and took a picture of the main drains, the 2017 VGBA stamp was visible as well as a model # and possibly a manufacturer date of 2019. The main drains and equalizers covers appear to be in good condition.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  3. Jun 25, 2021 Routine Inspection · No Reinspection Required

    No violations cited.

  4. Jun 26, 2019 Routine Inspection · No Reinspection Required

    No violations cited.

  5. Jun 1, 2018 Routine Inspection · No Reinspection Required

    No violations cited.

  6. Jun 2, 2017 Routine Inspection · No Reinspection Required

    No violations cited.

  7. Aug 19, 2015 Routine Inspection · No Reinspection Required

    No violations cited.

  8. Jun 1, 2015 Routine Inspection · No Reinspection Required

    No violations cited.

  9. Jul 11, 2014 Reinspection · No Reinspection Required

    No violations cited.

  10. Jun 20, 2014 Routine Inspection · Reinspection Required

    No violations cited.

  11. Sep 5, 2012 Routine Inspection · No Reinspection Required

    No violations cited.