Parkwood Village

98 GRAND CANYON DR, Madison, WI 53705 · Dane County

10cited violations
0serious tier
14inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
9713-2339
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026140
2025120
2024110
2023130
2021100
2019100
2018100
2017100
2016100
2015100
2014200
2013100
2012100

Inspections

  1. Jun 26, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Lou will disconnect the ho

      21a - BACKFLOW - WATER SUPPLY (P)

      The potable water supply line is currently directly connected to the recirculation system piping via a white hose from the hosebibb.

      Correction: Install a proper air gap or a reduced pressure zone backflow assembly on the water supply line.

      Code ATCP 76.19(1)

    • Not serious Action taken:

      21b - BACKFLOW - HOSE BIBBS (P)

      The hose bibb on the pool deck and the hose bibb in the pump room are not protected against backsiphonage.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code ATCP 76.33(1)(d)

    • Not serious Action taken:

      21b - BACKFLOW - HOSE BIBBS (P)

      The hose bibb in the pump room is not protected against backsiphonage. White hose is installed to supply fresh water to pool directly to recirculation plumbing without backflow prevention.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb. If required, install a proper air gap or a reduced pressure zone backflow assembly on the water supply line OR disconnect white hose and use outdoor green hose for adding fresh water to pool.

      Code ATCP 76.33(1)(d)

    • Not serious Action taken:

      30a - SHOWER, TOILET AND DRESSING ROOM FACILITIES

      The toilet in the restroom on the west side of the building is in disrepair - does not properly flush.

      Correction: Repair toilet. Maintain in good repair and provide clean and sanitary conditions.

      Code ATCP 76.33(2)(a)

  2. Jun 11, 2025 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Lou will disconnect the ho

      21a - BACKFLOW - WATER SUPPLY (P)

      The potable water supply line is currently directly connected to the recirculation system piping via a white hose from the hosebibb.

      Correction: Install a proper air gap or a reduced pressure zone backflow assembly on the water supply line.

      Code ATCP 76.19(1)

    • Not serious Action taken:

      21b - BACKFLOW - HOSE BIBBS (P)

      The hose bibb on the pool deck and the hose bibb in the pump room are not protected against backsiphonage.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code ATCP 76.33(1)(d)

  3. Jun 25, 2024 Routine Inspection · No Reinspection Required
    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date. Louis indicated they replaced the 2 main drains and 4 equalizer covers in May 2024 (5 yr lifespan).

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  4. Jun 5, 2023 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      11e - SDS AVAILABILITY

      Safety data sheets are not available for all chemicals used in the facility (e.g. sulfuric acid, bicarbonate, taylor test kit reagents).

      Correction: Provide safety data sheets for all chemicals used in the facility.

      Code ATCP 76.12(4)(b)

    • Not serious Action taken:

      27d - SIGNAGE - NO DIVING

      'NO DIVING' is not posted in the pool rules.

      Correction: Post approved signage with letters at least 4 inches in height.

      Code ATCP 76.29(1)(c)

    • Not serious Other

      34e - VGBA COVERS

      Replacement date documentation is unavailable on site for VGBA main drain and equalizer covers.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  5. Jul 15, 2021 Routine Inspection · No Reinspection Required

    No violations cited.

  6. Jul 30, 2019 Routine Inspection · No Reinspection Required

    No violations cited.

  7. Jun 4, 2018 Routine Inspection · No Reinspection Required

    No violations cited.

  8. Jun 14, 2017 Routine Inspection · No Reinspection Required

    No violations cited.

  9. Jun 5, 2016 Reinspection · No Reinspection Required

    No violations cited.

  10. Jun 26, 2015 Routine Inspection · No Reinspection Required

    No violations cited.

  11. Jun 26, 2014 Reinspection · No Reinspection Required

    No violations cited.

  12. Jun 16, 2014 Routine Inspection · Reinspection Required

    No violations cited.

  13. Jun 12, 2013 Routine Inspection · No Reinspection Required

    No violations cited.

  14. Jun 13, 2012 Routine Inspection · No Reinspection Required

    No violations cited.