Sauk Garden Apartment Homes
8501 OLD SAUK RD, Madison, WI 53705 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 59970-55650
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2025 | 1 | 5 | 0 |
| 2024 | 1 | 3 | 0 |
| 2023 | 1 | 2 | 0 |
| 2022 | 1 | 4 | 0 |
| 2019 | 1 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2013 | 2 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
Dec 4, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER (P
The flow meter is not functional or installed properly. Appears to be stuck at 45-50gpm.
Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
11b - CHEMICAL - STORAGE (P)(Pf)
Chemicals are improperly stored in accordance with ATCP 76.12(2). No overspill protection for acid and chlorine containers stored in same area.
Correction: Store chemicals in accordance with ATCP 76.12(2). Provide overspill protection to prevent accidental mixing of acid and chlorine.
Code ATCP 76.12(2)
-
Not serious
Action taken:
22b - INDOOR OR OUTDOOR POOL WATER TEMP (P)
The temperature of the indoor pool water is 91 degrees F. Troy indicated that they try to maintain the water at 92F.
Correction: Adjust the temperature to bring it within permissible limits pursuant to ATCP 76.19(4)(b). Water temp must be between 70-90F.
Code ATCP 76.19(4)(b)
-
Not serious
Action taken: instructor (Randy Jablonic
Corrected on site
25j - LIFEGUARD - INSTRUCTIONAL PROGRAM (P)
There is no lifeguard available to supervise the public during an instructional program. Signage posted at pool entrance indicate that there were pool exercise classes that occurred in September and into mid-October.
Correction: If pool exercise classes resume, provide a currently certified lifeguard. Instructional classes are prohibited without a lifeguard available for supervision.
Code ATCP 76.23(1)
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Action taken:
-
Dec 26, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
20c - WATER TESTING - POOLS
The water testing frequency for combined chlorine is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Check combined chlorine 2x/week and record results on pool log.
Code ATCP 76.18(1)
-
Not serious
Action taken:
21a - BACKFLOW - WATER SUPPLY
The potable water supply line is below the overflow point of the receiving basin.
Correction: Install a proper air gap or a reduced pressure zone backflow assembly on the water supply line.
Code ATCP 76.19(1)
-
Not serious
Action taken:
21b - BACKFLOW - HOSE BIBBS
The hose bibb on the water supply fill line is not protected against backsiphonage.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.
Code ATCP 76.33(1)(d)
-
Not serious
Action taken:
-
Oct 26, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
20c - WATER TESTING - POOLS
The water testing frequency for combined chlorine is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Test and record combined chlorine level at least 2x/week.
Code ATCP 76.18(1)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Feb 16, 2022 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
11e - SDS AVAILABILITY
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken:
26r - BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code ATCP 76.27(1)
-
Not serious
Action taken:
26s - BIOHAZARD SAFETY KIT
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Action taken:
-
Jun 28, 2019 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 15, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 13, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 28, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 17, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Oct 7, 2013 Reinspection · No Reinspection Required
No violations cited.
-
Sep 18, 2013 Routine Inspection · Reinspection Required
No violations cited.
-
Dec 5, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Nov 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.